Power Cords Supported by the Cisco ASR 1006 Router
Cisco ASR 1000
System Input Rating
Series Router DC
(Amps)
Power Supply
For example, the
Cisco ASR 1002
Router DC power
supply, with 16
Amp input rating
must use an AWG
#12 gauge wire for
a 20 A circuit
breaker and an
AWG #10 gauge
wire for a 30 A
circuit breaker.
Power Cords Supported by the Cisco ASR 1006 Router
The following power cords are supported by the Cisco ASR 1006 Router:
• CAB-AC20A-90L-IN—20 A AC right-angle power cord—International
• CAB-4000W-US1—Power cord, 250 VAC 20 A, Right Angle C19, NEMA 6-20 Plug, US
• CAB-US520-C19-US—NEMA 5-15 to IEC-C19 14ft US
The Cisco ASR 1006 Router modular chassis supports redundant power entry modules (PEMs). In the Cisco
ASR 1006 Router, at least one PEM must be functioning. In the event that one of the fans fails, the remaining
fans are sufficient to cool the entire chassis. However, fan speed may have to be increased. For power
consumption specifications, see the
At least one power supply must be powered on before the software is started.
Note
Note
All Cisco ASR 1000 Series Router AC power supplies must be connected to a branch circuit that does
not exceed 20 A.
Detailed instructions for removing and replacing the Cisco ASR 1000 Series AC and DC power supplies
Note
are provided in
14-55
Connecting AC Input Power to Cisco ASR 1006 Router
Follow these steps to connect an AC-input power supply to the Cisco 1006 chassis:
Cisco ASR 1000 Series Router Hardware Installation Guide
166
Circuit Breaker
Amps
"Removing and Replacing the Cisco ASR 1006 Router Power Supplies" section on page
.
AWG # Wire
"Cisco ASR 1006 Router Specifications" section on page A-1
Cisco ASR 1006 Router Overview and Installation
.