Battery Testing
1. Conduct a hydrometer test of the battery electrolyte.
IMPORTANT: Make sure the area around the cells is
clean before opening the battery caps.
A. Measure the specific gravity of each cell with a
hydrometer. Draw electrolyte in and out of the
hydrometer barrel prior to taking a reading to warm--
up the hydrometer. At the same time take the tem-
perature of the cell.
B. Temperature correct each cell reading. For each
o
o
10
F (5.5
C) above 80
specific gravity reading. For each 10
o
o
low 80
F (26.7
C) subtract 0.004 from the specific
gravity reading.
Example: Cell Temperature
Cell Gravity
o
o
100
F minus 80
o
(37.7
C minus 26.7
o
20
F multiply by 0.004/10
o
(11
C multiply by 0.004/5.5
ADD (conversion above)
o
Correction to 80
C. If the difference between the highest and lowest
cell specific gravity is 0.050 or greater or the lowest
cell specific gravity is less than 1.225, charge the bat-
tery. Charge at the recommended rate and time giv-
en in Battery Charging (in this section) or until the
specific gravity for all cells is 1.225 or greater with the
difference in specific gravity between the highest and
lowest cell less than 0.050. If these charging condi-
tions can not be met, replace the battery.
2. Perform a high--discharge test with an adjustable
load tester.
This is one of the most reliable means of testing a battery
as it simulates the cold--cranking test. A commercial bat-
tery load tester is required to perform this test.
CAUTION
Follow the battery load tester manufacturer's
instructions when using a load tester.
A. Check the voltage across the battery terminals
prior to testing the battery. If the voltage is less than
12.4 VDC, recharge the battery.
B. If the battery has been charged, apply a 150 amp
load for fifteen (15) seconds to remove the surface
charge. Use a battery load tester following the
manufacturer's instructions.
Electrical System
o
o
F (26.7
C) add 0.004 to the
o
o
F (5.5
100
1.245
o
F equals 20
F
o
o
C equals 11.0
C)
o
F equals 0.008
o
C equals 0.008)
0.008
o
F (26.7
C)
1.253
C. Make sure battery terminals are free of corrosion.
D. Measure the temperature of the center battery
cell.
E. Connect a battery load tester to the battery ter-
minals following the load tester manufacturer's in-
structions. Connect a digital multimeter to the battery
terminals.
F. Apply a test load of 325 amps (one half the Crank-
ing Performance rating of the battery) for fifteen (15)
seconds.
G. Take a battery voltage reading after the load has
C) be-
been applied to the battery for fifteen (15) seconds,
then remove the load. Record the voltage reading.
H. Using the table below, determine the minimum
o
F
voltage for the cell temperature reading:
Minimum
Voltage
9.6
9.5
9.4
9.3
9.1
8.9
8.7
8.5
I. If the test voltage is below the minimum, replace
the battery. If the test voltage is at or above the mini-
mum, return the battery to service.
Page 5 - - 52
Battery Electrolyte
Temperature
o
o
70
F (and up)
21.1
o
60
F
15.6
o
50
F
10.0
o
40
F
o
30
F
--1.1
o
20
F
--6.7
o
10
F
--12.2
o
0
F
--17.8
Groundsmaster 4500--D/4700--D
C (and up)
o
C
o
C
o
4.4
C
o
C
o
C
o
C
o
C