Description of Function Codes

Group P2: Vector Control Parameters

Group P2 is valid for vector control, and invalid for V/F control.
Function
Code
P2-00
P2-01
P2-02
P2-03
P2-04
P2-05
Speed loop PI parameters vary with running frequencies of the AC drive.
If the running frequency is less than or equal to "Switchover frequency 1" (P2-02), the speed
loop PI parameters are P2-00 and P2-01.
If the running frequency is equal to or greater than "Switchover frequency 2" (P2-05), the speed
loop PI parameters are P2-03 and P2-04.
If the running frequency is between P2-02 and P2-05, the speed loop PI parameters are
obtained from the linear switchover between the two groups of PI parameters, as shown in Figure
5-2.
Figure 5-2 Relationship between running frequencies and PI parameters
parameters
The speed dynamic response characteristics in vector control can be adjusted by setting the
proportional gain and integral time of the speed regulator.
Parameter Name
Speed loop proportional gain 1
Speed loop integral time 1
Switchover frequency 1
Speed loop proportional gain 2
Speed loop integral time 2
Switchover frequency 2
PI
Setting Range
1–100
0.01–10.00s
0.00 to F2-05
0–100
0.01–10.00s
P2-02 to maximum
output frequency
Frequency
reference
92
PE6000 User Manual
Default
30
0.50s
5.00 Hz
20
1.00s
10.00 Hz