6.2 Common Faults and Solutions
You may come across the following faults during the use of the AC drive. Refer to the following
table for simple fault analysis.
Table 6-1 Troubleshooting to common faults of the AC drive
SN
Fault
There is no display
1
at power-on.
"HC" is displayed
2
at power-on.
"Err23" is
3
displayed at
power-on.
The AC drive
display is normal
upon power-on.
4
But "HC" is
displayed after
running and stops
immediately.
Possible Causes
1: There is no power supply to the AC
drive or the power input to the AC drive
is too low.
2: The power supply of the switch on
the drive board of the AC drive is
faulty.
3: The rectifier bridge is damaged.
4: The control board or the
operation panel is faulty.
5: The cable connecting the control
board and the drive board and the
operation panel breaks.
1: The cable between the drive board
and the control board is in poor
contact.
2: Related components on the control
board are damaged.
3: The motor or the motor cable is
short circuited to the ground.
4: The HALL device is faulty.
5: The power input to the AC drive is
too low.
1: The motor or the motor output cable
is short-circuited to the ground.
2: The AC drive is damaged.
1:The cooling fan is damaged or
locked-rotor occurs.
2: The external control terminal cable
is short circuited.
191
Troubleshooting and Resolutions
Solutions
1: Check the power
supply.
2: Check the bus
voltage.
3: Re-connect the
34-core cables.
4: Contact our
company for technical
support.
1: Re-connect the
34-core cables.
2: Contact our
company for technical
support.
1: Measure the
insulation of the motor
and the output cable
with a megger.
2: Contact our
company for technical
support.
1: Replace the
damaged fan.
2: Eliminate external
fault