PE6000 User Manual
Function
Code
P4-38
DI valid mode selection 1
Group P5: Output Terminals
The PE6000 provides an analog output (AO) terminal, a digital output (DO) terminal, a relay
terminal and a FM terminal (used for high-speed pulse output or open-collector switch signal
output) as standard. If these output terminals cannot satisfy requirements, use an optional I/O
extension card that provides an AO terminal (AO2), a relay terminal (relay 2) and a DO terminal
(DO2).
Function
Code
P5-00
FM terminal output mode
The FM terminal is programmable multiplexing terminal. It can be used for high-speed pulse
output (FMP), with maximum frequency of 100 kHz. Refer to P5-06 for relevant functions of FMP. It
can also be used as open collector switch signal output (FMR)
Function
Code
P5-01
FMR function (open-collector output terminal)
P5-02
Relay function (T/A-T/B-T/C)
P5-04
DO1 function selection (open-collector output terminal)
Parameter Name
Parameter Name
Parameter Name
Setting Range
Unit's digit (DI1 valid mode)
0: High level valid
1: Low level valid
Ten's digit (DI2 valid mode)
0, 1 (same as DI1)
Hundred's digit (DI3 valid mode)
0, 1 (same as DI1)
Thousand's digit (DI4 valid mode)
0, 1 (same as DI1)
Ten thousand's digit (DI5 valid mode)
0, 1 (same as DI1)
Setting Range
0: Pulse output (FMP)
1: Switch signal output (FMR)
113
Description of Function Codes
Default
Default
Default
00000
0
0
2
1