Group U0: Monitoring Parameters - Pioneer PE6000 Series User Manual

Table of Contents

Advertisement

PE6000 User Manual
• Measure the AI1 voltage and save it to AC-00.
• View the displayed value of U0-21 and save the value to AC-01.
• Send a voltage signal (approximately 8 V) to AI1.
• Measure AI1 voltage and save it to AC-02.
• View the displayed value of U0-21 and save the value to AC-03.
At correction of AI2, the actually sampled voltage is respectively queried in U0-22.
For AI1 and AI2, 2 V and 8 V are suggested as the correction voltages.
AC-12
AC-13
AC-14
AC-15
These parameters are used to correct the AO.
They have been corrected upon delivery. When you resume the factory values, these
parameters will be restored to the factory-corrected values. You need not perform correction in the
applications.
Target voltage indicates the theoretical output voltage of the AC drive. Measured voltage
indicates the actual output voltage value measured by instruments such as the multimeter.

Group U0: Monitoring Parameters

Group U0 is used to monitor the AC drive's running state. You can view the parameter values
by using operation panel, convenient for on-site commissioning, or from the host computer by
means of communication (address: 0x7000-0x7044).
U0-00 to U0-31 are the monitoring parameters in the running and stop state defined by P7- 03
and P7-04. For more details, see Table 5-2. (PAGE 114)
AO1 target voltage 1
Setting Range
AO1 measured voltage 1
Setting Range
AO1 target voltage 2
Setting Range
AO1 measured voltage 2
Setting Range
Default
Default
Default
Default
179
Description of Function Codes
Factory-corrected
0.500–4.000 V
Factory-corrected
0.500–4.000 V
Factory-corrected
6.000–9.999 V
Factory-corrected
6.000–9.999 V