PE6000 User Manual
Group A5: Control Optimization Parameters
DPWM switch over frequency upper limit
A5-00
This parameter is valid only for V/F control.
It is used to determine the wave modulation mode in V/F control of asynchronous motor. If the
frequency is lower than the value of this parameter, the waveform is 7-segment continuous
modulation. If the frequency is higher than the value of this parameter, the waveform is 5-segment
intermittent modulation.
The 7-segment continuous modulation causes more loss to switches of the AC drive but
smaller current ripple. The 5-segment intermittent modulation causes less loss to switches of the
AC drive but larger current ripple. This may lead to motor running instability at high frequency. Do
not modify this parameter generally.
For instability of V/F control, refer to parameter P3-11. For loss to AC drive and temperature
rise, refer to parameter F0-15.
A5-01
This parameter is valid only for V/F control.
Synchronous modulation indicates that the carrier frequency varies linearly with the change
of the output frequency, ensuring that the ratio of carrier frequency to output frequency remains
unchanged. Synchronous modulation is generally used at high output frequency, which helps
improve the output voltage quality.
At low output frequency (100 Hz or lower), synchronous modulation is not required. This is
because asynchronous modulation is preferred when the ratio of carrier frequency to output
frequency is high.
Synchronous modulation takes effect only when the running frequency is higher than 85 Hz. If
the frequency is lower than 85 Hz, asynchronous modulation is always used.
Setting Range
PWM modulation mode
Setting Range
0
1
169
Description of Function Codes
Default
12.00 Hz
0.00–15.00 Hz
Default
Asynchronous modulation
Synchronous modulation
0