4.1 Standard Function Parameters

Table 4.1 Standard Function Parameters
Function
Parameter Name
Code
P0-00
G/P type display
P0-01
Motor 1 control mode
Command source
P0-02
Main frequency
P0-03
source X selection
Auxiliary frequency
P0-04
source Y selection
Range of auxiliary
P0-05
frequency Y for X and
Range of auxiliary
P0-06
frequency Y for X and
Group P0: Standard Function Parameters
1: G type (constant torque load)
2: P type (variable torque load
e.g. fan and pump)
0: Sensorless vector control
(SVC)
2: Voltage/Frequency (V/F)
control
0: Operation panel control (LED
off)
1: Terminal control (LED on)
selection
2: Communication control (LED
blinking)
0: Digital setting (preset
frequency P0-08, UP/DOWN can
be modified, non-retentive at
power failure)
1: Digital setting (preset
frequency P0-08, UP/DOWN can
be modified, retentive at power
failure)
2: AI1
3: AI2
4: Keyboard potentiometer
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
The same as P0-03 (Main
frequency source X selection)
0: Relative to maximum
frequency 1: Relative to main
Y operation
frequency X
0%–150%
Y operation
Setting Range
45
Function Code Tables
Default
Modification
Model
dependent
2
0
0
0
0
100%