Chapter 5
Maintaining the Router
•
•
•
•
•
•
OL-13832-01
Removing and Replacing AC and DC Power Subsystem Components
RPF1 (Reverse Polarity Feeder 1) (flashing yellow)—The PDU (Feeder 1) is
miswired. See
Step 8
of the
on page
5-27. During normal operation, this indicator remains off.
RP21(Reverse Polarity Feeder 2) (flashing yellow)—The PDU (Feeder 2) is
mis-wired. See
Step 8
procedure on page
5-27. During normal operation, this indicator remains off.
Fail (red)—Lights in conjunction with the following indicators (which flash)
to show the type of power supply failure:
–
F1LO
F2LO
–
OC
–
OT
–
OC (Over Current) (flashing red)—Indicates the input or output current has
exceeded its limit and that an overload or short circuit has occurred:
–
Set the power supply switch to off (0) and then back to the on (1)
position.
If the indicator is still flashing, eject and reseat the power supply.
–
If the indicator is still flashing, replace the power supply.
–
OT (Over Temperature) (steady or flashing red)—Indicates that the power
supply is in an overtemperature condition, causing a shut-down to occur.
Flashing red—Indicates a locked power supply fan. Replace the power
–
supply.
Steady red—Indicates an overtemperature condition. Verify that all fans
–
in the blower module are operating properly.
If all the blower module fans function, replace the power supply.
–
INOK (green)—Indicates that the power supply is operating normally, and
the source DC voltage is within the nominal operating range of –48 to
–60 VDC. This indicator lights when the power switch is set to the on (1)
position. If there is a power supply failure, the INOK indicator shuts off.
"Removing and Replacing a DC PDU" procedure
of the
"Removing and Replacing a DC PDU"
Cisco XR 12410 Router Installation Guide