7.11
P2/PC 02(High temperature protection of IPM module or High pressure protection
diagnosis and solution)
Description: If the temperature of IPM module is higher than a certain value, the LED displays the failure code.
For some models with high pressure switch, outdoor pressure switch cut off the system because high pressure
is higher than 638 PSI, and then the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• IPM module board
• High pressure protector
• System blockages
Troubleshooting and repair:
Note: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric
control box should be replaced as a whole.
Check the fastening screws on
the PCB and IPM radiator.
Are they
fixed tightly?
NO
Tighten the screws and apply
silicon grease.
Troubleshooting
Replace the outdoor
YES
control PCB.
32
(continued on next page)