Troubleshooting By Error Code; E0/Eh 00/Eh 0A / F4/Ec 51 (Eeprom Parameter Error Diagnosis And Solution) - Pioneer QUANTUM INVERTER Series Service & Troubleshooting Manual

Hide thumbs Also See for QUANTUM INVERTER Series:
Table of Contents

Advertisement

7. Troubleshooting by Error Code

7.1

E0/EH 00/EH 0A / F4/EC 51 (EEPROM parameter error diagnosis and solution)

Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
Troubleshooting and repair:
Remarks:
EEPROM: A read-only memory whose contents can be erased and reprogrammed using a pulsed voltage.
The location of the EEPROM chip on the indoor and outdoor PCB is shown in the following two images:
Note: For certain models, outdoor PCB cannot be removed separately. In this case, the outdoor electric
control box should be replaced as a whole. This pictures are only for reference, actual appearance may vary.
Troubleshooting and repair of compressor driven chip EEPROM parameter error and communication error
between outdoor main chip and compressor driven chip are same as F4/EC 51.
Shut off the power supply and
turn it on 2 minutes later.
Is it still displaying
the error code?
YES
Replace the indoor main
PCB
E0/EH 00
outdoor
(
) /
main PCB
F4
EC 51).
(
/
Troubleshooting
NO
The unit is operating normally .
19