1
Power switch
2
Ground lead service loop
Insert the stripped end of the +V lead all the way into the +V lead receptacle and tighten the receptacle
Step 6
screw using the same 3/16-inch flat-blade screwdriver. Repeat this step for the –V lead.
Note
After tightening the receptacle screw for the ground, +V, and –V DC-input leads, use a cable tie (see
Step 7
Figure
Note
Switch the circuit breaker to the on position.
Step 8
This completes the procedure for connecting DC-input power. Your installation is complete. Proceed to
Chapter 4, "Observing System Startup and Performing a Basic Configuration"
perform a basic configuration.
Cisco 7200 VXR Installation and Configuration Guide
3-44
Connecting DC-Input Power
1
3
2
4
Make sure the entire stripped end of each lead is inserted all the way into its receptacle. If any
exposed wire at the stripped end of a lead is visible after inserting the lead into its receptacle,
remove the lead from the receptacle, use the wire stripper to cut the stripped end of the lead, and
repeat
Step 4
through
Step
3-33) to secure the three leads to the power supply faceplate.
When securing the ground, +V, and –V DC-input leads to the power supply faceplate, leave a
small service loop in the ground lead to ensure that the ground lead is the last lead to disconnect
from the power supply if a great deal of strain is placed on all three leads (see
3
Cable tie
4
DC power leads
6.
Chapter 3
Installing a Cisco 7200 VXR Router
Figure
to start the router and to
3-33).