Chapter 2
Preparing for Installation
Figure 2-2
broadband router. The dimensions for the other models of Cisco uBR7100 series routers are identical.
Figure 2-2
To use the rack-mounting hardware provided with the router, consider the following guidelines:
•
To mount the router between two posts or rails using the brackets, the inner clearance (the width
between the inner sides of the two posts or rails) must be at least 17 inches (43.18 cm).
The height of the chassis is 3.5 inches (8.89 cm).
•
•
When mounting the router in four-post or telco-type racks, be sure to use all the screws and the
brackets provided to secure the chassis to the rack posts.
If you plan to use an equipment shelf, ensure that the shelf is constructed to support the weight and
•
dimensions of the chassis.
designing a customized shelf. We recommend that you use the rack-mount kit designed for
Cisco uBR7100 series routers.
OL-5916-01
shows the chassis outer dimensions and required footprint for the Cisco uBR7114 universal
Cisco uBR7114 Router Footprint and Outer Dimensions
Chassis width
17.5 in. (44.45 cm)
Figure 2-2
Cisco uBR7100 Series and Cisco uBR7100E Series Universal Broadband Router Hardware Installation Guide
shows the chassis footprint, which you need if you are
Site Requirement Guidelines
2-7