Master Programming Level
Disable
ZONE SETUP
1=ENABLE
2=DISABLE
3=SPECIAL PURPOSE
Zone Setup Screen #1
This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next to the Z, prompting the programmer to
enter a three digit zone number (001 - 099). When the third digit is entered, the zone will be disabled and the cursor will return to the original
position next to the Z. Another zone can then be disabled.
Special Purpose Zone
Pressing 3 for Special Purpose, while viewing Zone Setup Screen #1, will display the following screens:
Zones 097, 098, 099, and 096 (and Zones 094 and 095 in Canadian mode) can be programmed for normal zone operation or for special pur-
pose applications. In the above illustration, the four zones are shown Off, which means they can be programmed to function in the same
manner as all other zones, by assigning them to input and output devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the display to toggle between PAS 97 On and
PAS 97 Off. When Zone 097 is programmed On, a PAS (Positive Alarm Sequence) activation of any smoke detector will cause Zone 097 to
activate. By assigning Zone 097 to a control module in the Programming Zone Assignment Screen, an output device connected to the control
module can be used to indicate a PAS condition in the control panel. Do not assign Zone 97 to a Notification Appliance Circuit when using
this zone to indicate a PAS condition. Attempting to do so will generate an error message and will be prevented by software checks.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause the display to toggle between Pre-signal
98 On and Pre-signal 98 Off. When Zone 098 is programmed On, a Pre-signal activation of any device will cause Zone 098 to activate. By
assigning Zone 098 to a control module in the Programming Zone Assignment Screen, an output device connected to the control module can
be used to indicate a Pre-signal condition in the control panel. Do not assign Zone 098 to a Notification Appliance Circuit when using this
zone to indicate a Pre-signal condition. Attempting to do so will generate an error message and will be prevented by software checks.
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause the display to toggle between Two Stage
99 On and Two Stage 99 Off. Refer to "Two Stage Operation" on page 80 for a description of this feature. Two-stage operation and the in-
suite silence feature cannot be used at the same time.
Pressing 1 while viewing the Special Purpose Zone Screen #2 will cause the display to change to Local Alm 96 On. Each press of the 1 key
will cause the display to toggle between Local Alm 96 On and Local Alm 96 Off. When Zone 096 is programmed On, a Local Alarm activa-
tion of any smoke detector will cause Zone 096 to activate. By assigning Zone 096 to a control module in the Programming Zone Assign-
ment Screen, an output device connected to the control module can be used to indicate a local alarm condition in the control panel. Local
Alarm Zone alarms are not reported to the Central Station.
When the panel is set to Canadian mode, pressing 2 while viewing the Special Purpose Zone Screen #2 will cause the display to change to
CO Active 95 On. Each press of the 2 key will cause the display to toggle between CO Active 95 On and CO Active 95 Off. When enabled,
this zone will activate when a CO Alarm is active on the panel without requiring direct zone mapping to an input device.
When the panel is set to Canadian mode, pressing 3 while viewing the Special Purpose Zone Screen #2 will cause the display to change to In
Suite Sil 94 On. Each press of the 3 key will cause the display to toggle between In Suite Sil 94 On and In Suite Sil 94 Off. When enabled, this
zone works in conjunction with the In Suite Silence Timer. When enabled, this zone will activate only when a fire alarm is active on the
panel and will not activate via zone mapping to an input device. When the In Suite Silence Timer expires, all silenceable output devices and
NACs that are activated by only the In Suite Silence Zone will silence. If an output or NAC is activated by a general zone and the In Suite
Silence Zone, the output or NAC will not silence when the In Suite Silence Timer expires. This timer restarts with each new fire alarm that
occurs on the system. If the timer expires, all silenced outputs and NACs that were silenced by the In Suite Silence Timer will resound with
a new fire alarm and the In Suite Silence Timer will restart. In-suite silence cannot be used at the same time as two-stage operation.
Zones Installed
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ES-200X Series Manual — P/N LS10131-000FL-E:F 5/23/2022
Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:
ZONE TO DISABLE
Z
SPECIAL PURPOSE
1=PAS 97
OFF
2=PRESIGNAL 98
OFF
3=TWO STAGE 99
OFF
Special Purpose Zone Screen #1
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to the follow-
ing:
ZONES INSTALLED
000 001 002 003 004
005
Zones Installed Screen
Disable Screen
SPECIAL PURPOSE
1=LOCAL ALM 96
2=CO ACTIVE 95
3=IN SUITE SIL 94 OFF
Special Purpose Zone Screen #2
Programming
OFF
OFF
71