Advertisement

Accessories

CHG-120F Battery Charger

The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the ES-200X FACP. The FACP battery charger must be dis-
abled, through user programming, when using the CHG-120F. The batteries and charger can be housed in the BB-55F battery box which can
be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than
26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
1.6.6 ECC-50/100
The ECC-50/100 is a single channel, 50 watt, 25 V
fication applications, or both. Automatic activation of the ECC-50/100 is possible via eight Command Input Circuits (CMD) or via the ANN
BUS serial communications link from the ES-200X FACP.
1.6.7 ECC-FFT
An ECC-FFT Fire Fighter Telephone provides supervision, annunciation, and control for local and remote telephone handsets. The ECC-
FFT's keypad provides indications of phone activation and corresponding trouble conditions. Not for use in Canadian applications.
1.6.8 W-GATE(A) Wireless Gateway
The W-GATE(A) Wireless Gateway acts as a bridge between a group of wireless fire devices and a LiteSpeed SLC loop on the ES-200X. It
is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply evaluated for life safety. Available wireless devices
include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise heat detector, a monitor module, and a
relay module. A maximum of 196 wireless devices can be used in the system. For details about wireless devices, system setup, and
operation, see the SWIFT
1.6.9 ANN-BUS Annunciators/Modules
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
DISCONNECT ALL SOURCES OF POWER (AC AND DC) BEFORE INSTALLING OR REMOVING ANY MODULES OR
WIRING.

Guidelines

A variety of optional annunciation devices can be connected to an ANN-BUS communication circuit. ANN Series devices can be
connected to the primary communication circuit (EIA-485) terminals on TB9. A secondary communication circuit for these devices is
available at TB8. Each ANN-BUS communication circuit supports up to eight (8) annunciators. Compatible devices include the
following:
– ANN-80 LCD Annunciator (UL applications only)
– ANN-100 LCD Annunciator (FM and Canadian applications only)
– ANN-S/PG Serial/Parallel Printer Interface Module

– ANN-I/O LED Driver Module

– ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
– ANN-RLED Annunciator Module (red alarm LEDs only)
– ANN-RLY Relay Module (can be mounted in the supplied FACP chassis)
When operating two ANN-BUS circuits, only one ANN-S/PG Printer module can be used in the system.
The panel is capable of operating a primary ANN-BUS (TB9) and a secondary ANN-BUS (TB10) simultaneously.
Only one audio system (ECC-50/100 or ACC-25/50) may be connected to the ANN-BUS.

ANN-80/ANN-100 Remote Fire Annunciators

The ANN-80 and ANN-100 Annunciators are 80 character, backlit LCD remote fire annunciators. They mimic the display on the control
panel and will annunciate device type, point alarm, trouble or supervisory conditions, zone assignments plus any custom alpha labels pro-
grammed into the FACP. The annunciators also provide system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm
Silenced conditions. Additionally, the annunciators are capable of remotely performing critical system functions such as Acknowledge,
Silence, Reset and Drill. Communication between the annunciators and the FACP is accomplished over a two wire RS-485 serial interface
employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote
UL-listed, filtered, regulated, power supply.
The function buttons and piezo sounder may be individually enabled and disabled through the FACP software. Refer to "ANN-80/100
Options" on page 101 for a description of this feature and programming information.

ANN-S/PG Serial/Parallel Interface Module

The ANN-S/PG Serial/Parallel Interface module allows the connection of a remote serial or parallel printer to the FACP for a real-time log of
system events, detector status reports and event history. The module is provided with a plastic enclosure for surface mounting.
ANN-I/O LED Driver Module
The ANN-I/O is an LED driver module that can be used in a wide variety of applications, including as an interface with most customized
graphic annunciators. The ANN-I/O can drive up to 40 LEDs. The module is provided with a plastic wall mount.
ES-200X Series Manual — P/N LS10131-000FL-E:F 5/23/2022
RMS
®
Smart Wireless Integrated Fire Technology Instruction Manual #LS10036-000FL-E.
, emergency voice evacuation panel that may be used for fire applications, mass noti-
Product Description