Programming
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select whether the Ack/Step button on any installed
ANN-80 or ANN-100 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80/100 Options Screen
#1 causes the display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No (Ack/Step button
never functions). In Canadian mode, the FACP cannot be controlled by the ANN-100 so the Reset feature is unavailable. This option is
called STEP ENABLE in Canadian mode. Enabling the Step feature will allow the user to scroll through events on the screen.
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the Silence button on any installed ANN-80
or ANN-100 annunciator will function normally or always be ignored. Pressing 1 while viewing the ANN-80/100 Options Screen #2 causes
the display to toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether the Reset button on any installed ANN-80 or
ANN-100 annunciator will function normally or always be ignored. Pressing 2 while viewing the ANN-80/100 Options Screen #2 causes the
display to toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No (Reset button never functions). In
Canadian mode, the Reset feature is unavailable. The programming option will change to LMP BTN ENABLE in Canadian applications.
Pressing 2 while viewing the ANN-80/100 Options Screen #2 causes the display to toggle between Lmp Btn Enable Yes (the ANN-100 will
perform a local test of all LEDs) and Lmp Btn Enable No.
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether the Drill button on any installed ANN-80 or
ANN-100 annunciator will function normally or always be ignored. Pressing 3 while viewing the ANN-80/100 Options Screen #2 causes the
display to toggle between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill button never functions). In
Canadian mode, the Drill feature is unavailable. The programming option will change to SND BTN ENABLE in Canadian applications.
Pressing 3 while viewing the ANN-80/100 Options Screen #2 causes the display to toggle between Snd Btn Enable Yes (the ANN-100 will
perform a test of its local sounder by turning it on for 5 seconds) and Snd Btn Enable No.
Key Control Enable (Canadian Mode Only)
XXX ANN-BUS
1=KEY CTRL ENABLED
ANN-BUS Options Screen #2
3.5.9 Password Change
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
A flashing cursor will appear in the center of the display. Enter the current user password and enter a new eight digit password. After the
eighth digit is entered, the following screen will be displayed:
Re-enter the new password to accept the change. The display will return to the initial Password Change Screen.

Invalid Password

If a password is entered incorrectly, the panel will display Invalid Message and a code.
The programmer may hit the escape key and re-enter the password correctly.

Incorrect Password/Timeout

A user has nine attempts to enter the correct password. If the password is incorrect after the nine attempts, the administrator must wait 30
seconds for another attempt. However, if the password has been forgotten, it will need to be reset by the administrator.
102
The Key Control feature is only available when the FACP is in Canadian mode of operation. Canadian mode
usually limits the functionality of annunciators. Enabling key control allows annuciator key presses to be pro-
cessed normally. To enable the annunciator Key Control, press 1 while viewing ANN-BUS Options screen #2
so that the display reads Key Ctrl Enabled Y. Each press of the 1 key will cause the display to toggle between
Key Ctrl Enabled Y and Key Ctrl Enabled N.
The factory set passwords, which have been programmed into the control panel, can be changed by selecting
the Password Change option. Pressing 1 while viewing Programming Screen #4 will cause the following screen
to be displayed:
MODIFY USER X
ENTER PASSWORDS
USER X :
Password Change Screen
VERIFY NEW PASSWORD
Password Change Screen
MODIFY USER X
USER X PASSWORD
IS INCORRECT
PRESS ENTER OR ESC
INVALID PASSWORD
PRESS ENTER OR ESC
NEW:
MODIFY USER X
NEW PASSWORD CANNOT
BE ALL THE SAME CHAR
PRESS ENTER OR ESC
00 ATTEMPTS
REMAINING