NFPA 72 Remote Station Protective Signaling System
Notes:
1.
Enable 4XTMF supervision in FACP System Setup programming. Refer to page 84 for more information.
2.
Refer to "4XTMF Transmitter Module Installation" on page 31 for detailed information.
Cutting TBL Jumper allows the
reverse polarity circuit to open with
a system trouble condition if no
alarm condition exists.
ES-200X Series Manual — P/N LS10131-000FL-E:F 5/23/2022
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver Model RS82.
Figure C.2 Remote Station Connection Using 4XTMF Module
NFPA Standard-Specific Requirements
Polarity Shown is
+
-
Normal Standby
+
Power-limited
-
Ω
(Dummy load with a 4.7K
, ¼ watt resistor
when no connection is made)
4XTMF Transmitter Module
143