Maximum Power Available for 3-kW AC Power Supplies

Maximum Power Available for 3-kW AC Power Supplies
The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3-kW power supplies depending on power inputs, numbers of
power supplies, and the mode used.
Power Inputs
1 input (220 V)
1 input (110 V)

Maximum Power Available for 3-kW DC Power Supplies

The maximum power available for operations depends on the input power from your power source, the number
and output capabilities of your power supplies, and the power redundancy mode that you use. The following
table lists the amount of power available for 3-kW DC power supplies depending on power inputs, numbers
of power supplies, and the mode used.
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
78
Power Supplies
Combined Mode
1
3000 W
2
6000 W
3
9000 W
4
12000 W
5
15000 W
6
18000 W
7
21000 W
8
24000 W
1
1450 W
2
2900 W
3
4350 W
4
5800 W
5
7250 W
6
8700 W
7
10150 W
8
11600 W
Power Supply
Input Source
Redundancy
Redundancy
Mode
Mode
3000 W
3000 W
6000 W
3000 W
9000 W
6000 W
12000 W
6000 W
15000 W
9000 W
18000 W
9000 W
21000 W
12000 W
1450 W
1450 W
2900 W
1450 W
4350 W
2900 W
5800 W
2900 W
7250 W
4350 W
8700 W
4350 W
10150 W
5800 W
Managing the Switch
Full Redundancy
Mode
3000 W
3000 W
6000 W
6000 W
9000 W
9000 W
12000 W
1450 W
1450 W
2900 W
2900 W
4350 W
4350 W
5800 W
OL-30452-01.