Case 1: Dual Supervisor Migration
Step 6
System switchover is then initiated. This process moves the supervisor 3E module from the HA-standby mode to Active
mode. The SSH/telnet session is disconnected during the switchover. You have to then reconnect to the SSH/telnet session.
Also, ensure that the console link and the management link is connected to the newly inserted supervisor-3E module.
Sup2E syslogs
<Thu May 16 01:37:26 2019> Supervisor-2 (N77-SUP2E) will switchover to
Supervisor-3 (N77-SUP3E) now
<Thu May 16 01:37:26 2019> Switchover is successful, Supervisor-3 (N77-SUP3E)
is now active
Switch(config)#
User Access Verification
Switch login:
Sup3E syslogs
Switch(standby)# 2019May 16 01:37:26 Switch %$ VDC-1 %$ %KERN-2-SYSTEM_MSG: [
553.259393] Switchover started by redundancy driver - kernel
2019May 16 01:37:26 Switch %$ VDC-1 %$ %SYSMGR-2-HASWITCHOVER_PRE_START: This
supervisor is becoming active (pre-start phase).
2019May 16 01:37:27 Switch %$ VDC-1 %$ %SYSMGR-2-SWITCHOVER_OVER: Switchover
completed.
Step 7
After the switchover to the supervisor 3E module is completed, the boot parameters are set for the supervisor migration
process. Do not set any configuration parameters until the boot parameters are set. After the boot parameters are set, the
migration process is complete. Use the show boot command to display the current boot variables and the show module
command to display the modules installed in the switch.
Sup3E syslogs
2019May 16 01:37:39 Switch %$ VDC-1 %$ %BOOTVAR-2-SUP3_MIGRATION_CONFIG_STARTED:
Setting boot parameters for supervisor migration process, it might take some
time. Please do not replace Supervisor-2 (N77-SUP2E) in standby slot with
Supervisor-3 (N77-SUP3E) and set any config parameters until migration is
complete.
Switch# 2019Apr 23 00:18:53 Switch %$ VDC-1 %$ %BOOTVAR-2-SUP3_MIGRATION_
COMPLETE: Migration process is complete now. Supervisor-2 (N77-SUP2E) in standby
slot can now be replaced with Supervisor-3 (N77-SUP3E).
Switch# show boot
Current Boot Variables:
sup-1
kickstart variable = bootflash:/n7700-s3-kickstart.8.4.1.bin
system variable = bootflash:/n7700-s3-dk9.8.4.1.bin
Boot POAP Disabled
sup-2
kickstart variable = bootflash:/n7700-s3-kickstart.8.4.1.bin
system variable = bootflash:/n7700-s3-dk9.8.4.1.bin
Boot POAP Disabled
Boot Variables on next reload:
sup-1
kickstart variable = bootflash:/n7700-s3-kickstart.8.4.1.bin
system variable = bootflash:/n7700-s3-dk9.8.4.1.bin
Boot POAP Disabled
sup-2
kickstart variable = bootflash:/n7700-s3-kickstart.8.4.1.bin
system variable = bootflash:/n7700-s3-dk9.8.4.1.bin
Boot POAP Disabled
Cisco Nexus Operating System (NX-OS) Software
TAC support: http://www.cisco.com/tac
Copyright (c) 2002-2019, Cisco Systems, Inc. All rights reserved.
The copyrights to certain works contained in this software are
owned by other third parties and used and distributed under
license. Certain components of this software are licensed under
the GNU General Public License (GPL) version 2.0 or the GNU
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
98