Installing Cable Management Frames on a Chassis
a) Position one of the cable management side frame assemblies on the vertical mounting bracket attached to one side
of the front of the chassis so that the following screw holes align:
• Five screw holes in the assembly should align with the screw holes in five studs on the mounting bracket (see
the following figure).
Figure 15: Attaching a Cable Management Assembly to the Chassis
1
Vertical mounting bracket on the chassis
2
Cable management assembly
3
M4 x 12 mm screws (five) secure the upper
portion of assembly to the mounting bracket
• Four screw holes in the two angled brackets on the assembly should align with the four screw holes in the chassis.
If these screw holes do not align together or the angled brackets do not touch the chassis, try positioning the
assembly on the opposite side of the chassis.
b) Secure the upper portion of the assembly to the chassis vertical mounting bracket with five M4 x 12 mm, flat-head,
Phillips screws. Tighten each screw to 11.5 to 15 in-lb (1.3 to 1.7 N·m) of torque.
c) Secure the bottom portion of the assembly to the chassis using two M4 x 12 MM flat-head Phillips screws in each
of the two angled brackets on the assembly. Tighten each screw to 11.5 to 15 in-lb (1.3 to 1.7 N·m) of torque.
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
36
4
M4 x 12 mm screws (two) secure the upper
bracket to the chassis
5
M4 x 12 mm screws (two) secure the lower
bracket to the chassis
Installing the Chassis
OL-30452-01.