hit counter script

Installing The System Ground - Cisco ME-C6524GS-8S Installation Manual

Me 6500 series
Table of Contents

Advertisement

Installing the System Ground

Figure 3-3
Installing the Rubber Feet
OK
OK
N
FA
OK
UT
INP
UT
TP
OU
-
+
o

Installing the System Ground

The system (NEBS) ground provides additional grounding for EMI shielding requirements and is
intended to satisfy the Telcordia Technologies NEBS requirements for supplemental bonding and
grounding connections.
To connect the system ground, you need the following tools and materials:
The grounding lug and the grounding lug screws are supplied as part of the accessory kit. The grounding
Note
wire and the tools are not supplied as part of the accessory kit.
Cisco ME 6500 Series Ethernet Switch Installation Guide
3-8
OK
OK
N
FA
OK
UT
INP
UT
TP
OU
-
+
o
Grounding lug—A two-hole standard 90-degree barrel lug. Supports up to 6 AWG wire.
Grounding screws—Two M4 x 8 mm pan-head screws.
Grounding wire—The grounding wire should be sized according to local and national installation
requirements. Depending on the power supply and system, a 12 AWG to 6 AWG copper conductor
is required for U.S. installations. We recommend that you use commercially available 6 AWG wire.
The length of the grounding wire depends on the proximity of the switch to proper grounding
facilities.
No. 1 Phillips screwdriver.
Wire-stripping tool to remove the insulation from the grounding wire.
Crimping tool to crimp the grounding wire to the grounding lug.
Chapter 3
Installing the Switch
OL-8900-03

Advertisement

Table of Contents
loading

This manual is also suitable for:

Me-c6524gt-8sMe 6524

Table of Contents