Zone Type - Honeywell FIre-LITe ALArms MS-9600LS Manual

Addressable fire alarm control panel
Hide thumbs Also See for FIre-LITe ALArms MS-9600LS:
Table of Contents

Advertisement

Programming

Zone Type

ZONE SETUP
1=ZONE TYPES
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on
2=ZONES AVAILABLE
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
3=ZONE MESSAGE
screen similar to the following:
Zone Setup Screen #3
This display will show the system zones (default and user programmed) and their associated types.
Note that an up and/or down arrow will appear in the upper right corner of the display, indicating
that additional screens of zone information exists. Press the up or down arrow keys to view zones
Z00 through Z99.
Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For exam-
ple, to change the zone type for zone Z02 in the screen illustrated above, press 3. The following
screens will be displayed:
ZONE TYPE PROG
1=MONITOR
2=SMOKE PHOTO
3=WATERFLOW
Zone Type Program Screen #1
ZONE TYPE PROG
1=MEDICAL
2=HAZARD
3=TAMPER
Zone Type Program Screen #3
To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.
IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Water-
flow silenceable zone type to the selected zone. Any signaling devices programmed to the same
zone can be silenced by pressing the Alarm Silence key or by using the auto-silence feature.
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page 100.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only
change how it is reported to the Central Station.
98
ZONE TYPE PROG
1=Z00
MONITOR
2=Z01
MONITOR
3=Z02
MONITOR
Zones Installed Screen
1=HEAT
2=PULL STATION
3=DUCT
Zone Type Program Screen #2
1=SUPERVISORY
2=PROC. MON
3=SMOKE ION
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Master Programming Level
ZONE TYPE PROG
ZONE TYPE PROG
Zone Type Program Screen #4