Programming
3.6.8 Walktest
PROGRAMMING
Walktest allows an individual to test the fire alarm system without the necessity to reset the control
1=HISTORY
panel after each device activation. Pressing 2 while viewing the Programming Screen #3 will cause
2=WALKTEST
3=OPTION MODULES
the following Walktest options to be displayed:
Programming Screen #3
To perform a silent walktest which will not sound the NACs, press 1 while viewing the Walktest
Screen. To perform an audible walktest, which will sound the NACs, press 2 while viewing the
Walktest Screen. When either option is chosen, the panel will enter Walktest Mode and the follow-
ing screen will be displayed::
From this screen, it is possible to view the walktest log, untested system points or a summary of the
addressable devices tested during the current walktest. The user can select between any of these
screens without interrupting the current walktest session. The walktest session will not end until
the Unit In Walktest screen is exited by pressing the Escape key.
Pressing 1 for View Walktest Log while viewing the Unit In Walktest screen will cause a screen sim-
ilar to one of the following two screens to be displayed:
NO EVENTS IN
WALKTEST LOG
If there are no events in the current walktest session, the first screen will be displayed, indicating no
events have been stored in the walktest log. If any events have been stored, a screen similar to the
second will be displayed indicating the latest event. As walktest events occur, the display will
change to indicate the latest event. All stored events can be scrolled on the screen by pressing the
up or down arrow keys. To return to the first event, press the 1st Event key.
116
WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen
UNIT IN WALKTEST
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY
Unit In Walktest Screen
ALARM: MONITOR
NORTH CLASSROOM
OR
10*15A 020510 1M006
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Master Programming Level
Z001