Notification Appliance Circuits
2.4.2 Style Y (Class B) NAC Wiring
4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7K ohm, ½ watt P/N:71252 UL-listed
Polarized Strobes
Notification Appliance Circuit
polarity shown in alarm state
circuit number
2.4.3 Style Z (Class A) NAC Wiring
Notification Appliance Circuit
polarity shown in alarm state
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
NAC 1
NAC 3
Polarized Bells
Polarized Horns
Figure 2.7 NAC Style Y (Class B) Wiring
2 Style Z (Class A) Notification Appliance
Circuits, supervised and power-limited
Polarized Bell
Polarized Strobe
Polarized Horn
NAC 1
Figure 2.8 NAC Style Z (Class A) Wiring
NAC 4
NAC 2
Polarized Bells
Polarized Strobes
Polarized Horns
Dummy Load all unused circuit
TB4
Polarized Bell
Polarized Strobe
Polarized Horn
NAC 2
Installation
49