Programming
3.
4.
5.

Module Programming

Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or
POINT PROGRAM
change the programming of an addressable module. The following screen will be displayed by the
SELECT TYPE
1=DETECTOR
control panel:
2=MODULE
Point Program Screen #2
Pressing 1 while viewing the Modules Screen will display the following screen which allows the
programmer to add a new module address to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in
the three digit module address, such as 005.
When the last digit is keyed-in, the following screen will be displayed:
78
With the cursor on the last letter of the Noun field, press the zero key again to increment the
room number to 305.
Press the right arrow key to advance the zone field.
Select a zone number from 00 to 99. Z00 (default zone) is the general alarm zone. Z01
through Z99 may be selected to link software zones.
1=ADD
2=DELETE
3=EDIT
Add Module
ENTER MODULE#
***
1=CONTROL
2=MONITOR
MODULES
Modules Screen
ADD MODULE
Add Module Screen #1
ADD MODULE
Add Module Screen #2
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010