4.22.8 Program Check
4.22.9 History
4.22.10 Annunciators
READ STATUS
1=ANNUNCIATORS
2=PHONE LINES
3=CENTRAL STATION
Read Status Screen #4
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be
displayed:
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to one of the Notification Appliance Circuits. Use the up
and down arrow keys to view all NACs.
Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any
output zones have not been programmed to at least one input zone. Use the up and down arrow
keys to view all zones.
Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to at least one output zone. Use the up and down arrow
keys to view all zones.
Pressing 3 while viewing Read Status Screen #3 will display the following screen:
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
The operator can view all events which have been stored in the history file, only alarms or other
events, such as troubles or supervisories, by pressing the corresponding number key.
Pressing 1 while viewing Read Status Screen #4 will display the following screens:
TERM ENABLED
2=ACS OPTIONS
3=ANN-BUS OPTIONS
PROGRAM CHECK
HISTORY
ANNUNCIATORS
Annunciator Screen
Operating Instructions
YES
167