Appendix
A.3 I/O Connections and Wiring
Terminal Block Wiring - 7ME39406ML00 I/O Module (4-Channel)
FUS1010, 7ME35309 only
(Refer to manual drawing 1010N-8MS2-7 (sheet 2 of 2)
Table A- 13
Note
Flow meter requires external power supply. Shunt as shown. Current is controlled within
loop. 4-20mA inputs and outputs are isolated.
Vc = +30V (max) Loop Supply 1k ohm (max)
188
Input/Output Wiring (TB3) - 7ME39406ML00 I/O Module (4-Channel)
Pin#
Signal
1
Iout 1+
2
Iout 1-
3
Iout 2+
4
Iout 2-
5
Iout 3+
6
Iout 3-
7
Iout 4+
8
Iout 4-
Function
Isolated Loop Supply
Isolated Loop Return
Isolated Loop Supply
Isolated Loop Return
Isolated Loop Supply
Isolated Loop Return
Isolated Loop Supply
Isolated Loop Return
Operating Instructions, 12/2014, A5E03086491-AC
Description
4-20mA proportional to spanned, se-
lected variable (loop power).
4-20mA outputs also provide a fault
indication by dropping to 2mA if as-
signed to flow rate and under fault
conditions.