hit counter script

Cisco Nexus 93120TX Installation Manual page 36

Nx-os mode switch hardware
Hide thumbs Also See for Nexus 93120TX:
Table of Contents

Advertisement

Grounding the Chassis
its grounding pad to the rack. Otherwise, you must connect the chassis grounding pad directly to the data
center ground.
Step 1
Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the covering from the end of the grounding
wire.
Step 2
Insert the stripped end of the grounding wire into the open end of the grounding lug, and use a crimping tool to crimp
the lug to the wire (see Callout 2 in the following figure). Verify that the ground wire is securely attached to the grounding
lug by attempting to pull the wire out of the crimped lug.
Figure 9: Grounding the Cisco Nexus 93120TX Chassis
1
Chassis grounding pad
2
Grounding cable, with 0.75 in. (19 mm) of insulation
stripped from one end, inserted into the grounding
lug and crimped in place
Step 3
Secure the grounding lug to the chassis grounding pad with two M4 screws (see Callouts 1 and 3 in the previous figure),
and tighten the screws to 11 to 15 in-lb (1.24 to 1.69 N·m) of torque.
Step 4
Prepare the other end of the grounding wire and connect it to an appropriate grounding point in your site to ensure an
adequate earth ground for the switch. If the rack is fully bonded and grounded, connect the grounding wire as explained
in the documentation provided by the vendor for the rack.
Cisco Nexus 93120TX NX-OS Mode Switch Hardware Installation Guide
26
3
Two M4 screws used to secure the grounding lug to
the chassis
Installing the Chassis

Advertisement

Table of Contents
loading

Table of Contents