hit counter script
Cisco Nexus 93180YC-FX3S Installation Manual

Cisco Nexus 93180YC-FX3S Installation Manual

Hide thumbs Also See for Nexus 93180YC-FX3S:

Advertisement

Quick Links

Replacing Components
Replacing a Fan Module
You can replace a fan module while the switch is operating so long as you perform the replacement within
one minute. If you cannot perform the replacement within one minute, leave the original fan module in the
chassis to maintain the designed airflow until you have the replacement fan module on hand and can perform
the replacement.
Caution
If you are replacing a module during operations, be sure that the replacement fan module has the correct
direction of airflow, which means that it has the same airflow direction as the other modules in the chassis.
Also, be sure that the airflow direction takes in air from a cold aisle and exhausts to a hot aisle. Otherwise,
the switch can overheat and shutdown.
If you are changing the airflow direction of all the modules in the chassis, you must shutdown the switch
before replacing all the fan and power supply modules with modules using the other airflow direction. During
operations, all of the modules must have the same direction of airflow.
Removing a Fan Module
Warning
Statement 263 Fan Warning
The fans might still be turning when you remove the fan assembly from the chassis. Keep fingers, screwdrivers,
and other objects away from the openings in the fan assembly's housing.
Step 1
On the fan module that you are removing, press the two sides of the fan module handle next to where it connects to the
fan module and pull on the handles enough to unseat it from its connectors.
Step 2
Holding the handle, pull the module out of the chassis.
Replacing a Fan Module, on page 1
Replacing a Power Supply Module, on page 2
Replacing Components
1

Advertisement

Table of Contents
loading

Summary of Contents for Cisco Nexus 93180YC-FX3S

  • Page 1 Replacing Components • Replacing a Fan Module, on page 1 • Replacing a Power Supply Module, on page 2 Replacing a Fan Module You can replace a fan module while the switch is operating so long as you perform the replacement within one minute.
  • Page 2: Installing A Fan Module

    Replacing Components Installing a Fan Module Do not touch the electrical connectors on the back side of the module and prevent anything else from coming Caution into contact with and damaging the connectors. Installing a Fan Module Before you begin •...
  • Page 3: Removing An Hvac/Hvdc Power Supply

    Replacing Components Removing an HVAC/HVDC Power Supply Step 1 Pull the power cord out from the power receptacle on the power supply to be removed and verify that the LED turns off. Note The LED might be on and amber colored to indicate that the input power has been disconnected. Step 2 Remove the power supply from the chassis by pushing and holding its thumb latch to the left and pulling the power supply part way out of the chassis.
  • Page 4: Installing An Ac Power Supply

    Replacing Components Installing an AC Power Supply Step 1 Turn off the circuit breaker for the power feed to the power supply that you are replacing. Be sure that the LEDs turn off on the power supply that you are removing. Step 2 Remove the power cable from the power supply by doing the following: •...
  • Page 5: Installing An Hvac/Hvdc Power Supply

    Replacing Components Installing an HVAC/HVDC Power Supply If the power supply does not fit into the open slot, turn the module over before sliding it carefully into the open Note slot. Step 2 Test the installation by trying to pull the power supply out of the slot without using the release latch. If the power supply does not move out of place, it is secured in the slot.
  • Page 6: Installing A Dc Power Supply

    Replacing Components Installing a DC Power Supply Step 3 If the DC power cables and a grounding cable are already connected to an electrical connector block, insert the block into the power receptacle on the power supply. If the electrical cables have not been connected to the electrical connector block, wire them as described in Wiring a 48 V DC Electrical Connector Block, on page Step 4...
  • Page 7 Replacing Components Wiring a 48 V DC Electrical Connector Block Step 4 Verify that the power supply is operational by making sure that the power supply LED is green. Wiring a 48 V DC Electrical Connector Block You must connect the ground, negative, and positive DC power cables to a connector block in order to connect the power cables to a 48 V DC power supply.
  • Page 8 Replacing Components Wiring a 48 V DC Electrical Connector Block Wire retainer lever -48V (+DC) cable Orange plastic button on top of the connector Grounding cable (8 AWG recommended) -48V (-DC) cable Step 5 Use a small screwdriver to depress the spring-loaded wire retainer lever on the lower spring-cage wire connector. Insert your green (ground) wire into the aperture and then release the lever.

Table of Contents