Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide First Published: 2020-07-22 Americas Headquarters Cisco Systems, Inc. 170 West Tasman Drive San Jose, CA 95134-1706 http://www.cisco.com Tel: 408 526-4000 800 553-NETS (6387) Fax: 408 527-0883...
Page 2
Any products and features described herein as in development or available at a future date remain in varying stages of development and will be offered on a when-and if-available basis. Any such product or feature roadmaps are subject to change at the sole discretion of Cisco and Cisco will have no liability for delay in the delivery or failure to deliver any products or feature roadmap items that may be set forth in this document.
Installing the Chassis Safety Installation Options with Rack-Mount Kits Airflow Considerations Installation Guidelines Unpacking and Inspecting the Switch Installing the Switch Using the NXK-ACC-KIT-1RU Rack-Mount Kit Grounding the Chassis Starting the Switch Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 4
Cable Management Guidelines A P P E N D I X B System Specifications Environmental Specifications Switch Dimensions Switch and Module Weights and Quantities Transceiver and Cable Specifications Switch Power Input Requirements Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 5
A P P E N D I X C LEDs Switch Chassis LEDs Fan Module LEDs Power Supply LEDs A P P E N D I X D Additional Kits Rack Mount Kit NXK-ACC-KIT-1RU Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
• Overview, on page 1 Overview The Cisco Nexus 93180YC-FX3S switch (N9K-C93180YC-FX3S) is a 1-rack unit (RU), fixed-port switch designed for deployment in data centers. This switch has the following ports: • 48 100M/1/10/25-Gigabit Ethernet SFP28 ports (ports 1-48). • 6 10/25/40/50/100-Gigabit QSFP28 ports (ports 49-54) •...
Page 8
The following figure shows the switch features on the port side of the chassis. 1PPS and 10MHz SMB 48 100M/1/10/25-Gigabit ports Ethernet SFP28 ports GPS/GNSS antenna 6 10/25/40/50/100-Gigabit connector QSFP28 ports LEDs Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 9
1 (left) and 2 (right) Fan modules (4) with slots USB port numbered from 1 (left) to 4 (right) Console port ToD port The following figure shows the side of the chassis. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 10
If the switch has port-side exhaust airflow (blue coloring for fan modules), you must locate the ports in the hot aisle. If you locate the air intake in a hot aisle, the switch can overheat and shut down. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Altitude Requirements Altitude rating is based on power supply installed; see critical components list in the system CB report for altitude rating. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
The wiring is unlikely to emit radio interference if you use a twisted-pair cable with a good distribution of grounding conductors. If you exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
The switch includes two power supplies (1-to-1 redundancy with current sharing) in one of the following combinations: • Two 650-W AC power supplies (NEBS compliant) • Two 1200-W HVAC/HVDC power supplies Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 14
IEC 60950 based safety standards. Note We recommend 8-AWG wire for DC installations in the U.S. Note For the power cables to use with the power supplies, see Power Cable Specifications, on page Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
(for proper mounting of the bottom-support brackets or other mounting hardware). Also, you must have power receptacles that are located within reach of the power cords that are used with the switch. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
17.3 in (43.9 cm) Width of the front clearance area (equal to the width of the chassis with two rack-mount brackets that are attached to it). 19.0 in (43.3 cm) Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 17
Preparing the Site Clearance Requirements Note Both the front and rear of the chassis must be open to both aisles for airflow. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 18
Preparing the Site Clearance Requirements Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Starting the Switch, on page 21 Safety Before you install, operate, or service the switch, see the Regulatory, Compliance, and Safety Information for the Cisco Nexus 3000 and 9000 Series for important Safety Information. Warning Statement 1071 Warning Definition IMPORTANT SAFETY INSTRUCTIONS Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents.
You can install the switch using the following rack-mount options: • Rack-mount kit (NXK-ACC-KIT-1RU) which you can order from Cisco. This option offers you easy installation, greater stability, increased weight capacity, added accessibility, and improved removability with front and rear removal.
Page 21
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the protective devices is rated not greater than 40A for the regular DC power supplies (rated 48-60VDC) and 10A for the HVDC power supplies. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
You must supply the eight 10-32 or 12-24 screws required to mount the slider rails and switch to the rack. Before you begin • You have inspected the switch shipment to ensure that you have everything ordered. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 23
The holes that you use depend on the requirements of your rack and the amount of clearance required for interface cables (3 inches [7.6 mm] minimum) and module handles (1 inch [2.5 mm] minimum). Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 24
Holding the switch with both hands, position the two rear rack-mount brackets on the switch between the rack or cabinet posts that do not have slider rails attached to them (see the following figure). Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 25
Tighten the 10-32 screws to 20 in-lb (2.26 N·m) or tighten the 12-24 screws to 30 in-lb (3.39 N·m). Step 5 If you attached a grounding wire to the chassis grounding pad, connect the other end of the wire to the facility ground. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Verify that the ground wire is securely attached to the grounding lug by attempting to pull the wire out of the crimped lug. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
• The rack must be close enough to the dedicated power source so that you can connect the switch to the power source by using a designated power cables. • You have the designated power cables for the power supplies that you are connecting to the dedicated power sources. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 28
If there is a safety cover for the terminals, place and secure it over the terminals to avoid an electrical shock hazard. e) Turn on the power at the circuit breaker for the DC power source. Step 4 Verify that the power supply LED is on and green. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 29
A setup utility automatically launches the first time that you access the switch and guides you through the basic configuration. For instructions on how to configure the switch and check module connectivity, see the appropriate Cisco Nexus 9000 Series configuration guide.
Page 30
Installing the Chassis Starting the Switch Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
When running cables in overhead or subfloor cable trays, we strongly recommend that you locate power cables and other potential noise sources as far away as practical from network cabling that terminates on Cisco equipment. In situations where long parallel cable runs cannot be separated by at least 3.3 feet (1 meter), we recommend that you shield any potential noise sources by housing them in a grounded metallic conduit.
Page 32
Connect the other end of the RJ-45 rollover cable to the console or to a modem. What to do next You are ready to create the initial switch configuration (see Creating the Initial Switch Configuration, on page 27). Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
To connect the switch to the network, you can use the default choices for each configuration except the IP address, which you must provide. You can perform the other configurations later as described in the Cisco Nexus 9000 Series NX-OS Fundamentals Configuration Guide.
RJ-45 connectors. For longer connections, you can use an optical cable with SFP transceivers (LH or SX type). Note Use only one of these management ports—the switch does not support the use of both management ports. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
When removing transceivers from the switch, it is best to remove the optical cable first and then remove the transceiver. To determine which transceivers, adapters, and cables are supported by this switch, see the Cisco Transceiver Modules Compatibility Information document. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 36
Connecting the Switch to the Network Connecting Interface Ports to Other Devices Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
On the fan module that you are removing, press the two sides of the fan module handle next to where it connects to the fan module and pull on the handles enough to unseat it from its connectors. Step 2 Holding the handle, pull the module out of the chassis. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
• Ensure that the chassis is grounded. For grounding instructions, see Grounding the Chassis, on page Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
You can remove one power supply while the other one provides power to the switch. To disconnect the power supply from its power cables, you must shut off the power from the power source and then disconnect the connector for the power cables. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
If the power supply does not move out of place, it is secured in the slot. If the power supply moves, carefully press it all the way into the slot until it clicks in place. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
If using a DC power source, turn on the circuit breaker for the DC power source connected to the power supply. Step 6 Verify that the power supply is operational by making sure that the power supply LED is green. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
You must connect the ground, negative, and positive DC power cables to a connector block in order to connect the power cables to a 48 V DC power supply. Note The recommended wire gauge is 8 AWG. The minimum wire gauge is 10 AWG. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 43
Verify that the other ends of the cables are attached to the DC power source and ground. Step 5 Turn on the circuit breaker Step 6 You are now ready to turn on the DC power source. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 44
Replacing Components Connecting a Power Cable to an NXA-PDC-930W Power Supply Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
• Standard 19-inch (48.3 cm) (two- or four-post EIA cabinet or rack, with mounting rails that conform to English universal hole spacing per section 1 of ANSI/EIA-310-D-1992). For more information, see Requirements Specific to Perforated Cabinets, on page Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
To help with cable management, you might want to allow additional space in the rack above and below the chassis to make it easier to route all of the fiber optic or copper cables through the rack. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
0 to 13,123 feet (0 to 4,000 meters) Environment Specification Temperature Ambient operating temperature 32 to 104°F (0 to 40°C) Ambient nonoperating –40 to 158°F (–40 to 70°C) Relative Nonoperating 5 to 85% humidity Operating 12 to 75% Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
– 930-W DC port-side exhaust (blue) (NXA-PDC-930W-PE) – 930-W DC port-side intake (burgundy) (NXA-PDC-930W-PI) Transceiver and Cable Specifications To determine which transceivers, adapters, and cables are supported by this switch, see https://www.cisco.com/ c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Maximum input volt-amperes 760 VA at 100 VAC Maximum output power per power supply 650 W Maximum inrush current 11 A (sub-cycle duration) Maximum hold-up time 12 ms at 650 W Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
12 V at 2.5 A Efficiency rating Climate Savers Platinum Efficiency (80Plus Platinum certified) Form factor RSP1 930-W DC Power Supply Specifications These specifications apply to the following power supplies: • NXA-PDC-930W-PE Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
CAB-9K10A-EU 250 VAC, 10 A, CEE 7/7 plug, 8.2 feet (2.5 m) India CAB-IND-10A 10 A, 8.2 feet (2.5 m) India CAB-C13-C14-2M-IN Power Cord Jumper, C13-C14 Connectors, 6.6 feet (2.0 m) Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
HVAC 2-foot (0.6 m) cable with Saf-D-Grid and SD connectors 277V AC CAB-HVAC-C14-2M HVAC 6.6-foot (2.0 m) cable with Saf-D-Grid and C14 (use for up to 240 V) connector 250V AC Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Part Number Description Photo NXA-PDC-930W-PE/PI The 930W DC power supply (NXA-PDC-930W-PE/PI) is shipped with cable CAB-48DC-40A-8AWG. Regulatory Standards Compliance Specifications The following table lists the regulatory standards compliance for the switch. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Page 54
• CNS13438 Class A EMC: Immunity • EN55024 • CISPR24 • EN300386 • KN 61000-4 series RoHS The product is RoH-6 compliant with exceptions for leaded-ball grid-array (BGA) balls and lead press-fit connectors. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Temperature exceeds the major alarm threshold. The switch is not receiving power. Green Fans and power supply modules are operational. Amber At least one fan or power supply module is not operating. Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Power supply is not receiving power. Green Flashing amber Power supply warning—possibly one of the following conditions: • High voltage • High power • Low voltage • Slow power supply fan Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...
Hazardous substances list for customers in China The following table lists and illustrates the console cable (CAB-CONSOLE-RJ45) that can be ordered. Illustration Description Quantity Console cable with DB-9F and RJ-45F connectors Cisco Nexus 93180YC-FX3S NX-OS Mode Switch Hardware Installation Guide...