10.4
Communication via PROFIBUS DP
10.4.1
PROFIBUS connection
Electric shock during connection while voltage is present
When connecting the PROFIBUS cable while voltage is present, there is a danger of
coming into contact with live components behind the terminal.
Touching live components can result in death or serious injury.
• Only connect the PROFIBUS cable to connector X126 when the unit is in a de-
Position of PROFIBUS connection and diagnostics LEDs
The PROFIBUS connection and diagnostics LEDs are located on the Control Unit (CUD).
The PROFIBUS connection is via a 9-pin Sub-D socket X126. The connections are
electrically isolated.
See also Figure 6-44 Terminal/connector arrangement on the "Control Unit (CUD)"
(Page 156) and Chapter "Description of the LEDs on the CUD (Page 635)".
PROFIBUS connection
Table 10- 33 PROFIBUS connector assignment
Connector
Pin
X126
1
2
3
4
5
6
7
8
9
"Control Unit (CUD)" module
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
WARNING
energized state.
Signal name
-
-
RxD/TxD-P
CNTR-P
DGND
VP
-
RxD/TxD-N
-
10.4 Communication via PROFIBUS DP
Technical specifications
Not assigned
Not assigned
RS485 receive/transmit data P (B)
Control signal (TTL)
PROFIBUS data ground
Positive supply voltage (5 V +/-10%)
Not assigned
RS485 receive/transmit data N (A)
Not assigned
Descriptions of functions
455