DLP-L51 Connecting Office Power (DC) to the NCS 2002 Shelf (ETSI Only)
Note
Figure 48: Connecting Office Power — DC Power Modules (ANSI Only)
Caution
Caution
Step 12 Return to your originating procedure (NTP).
DLP-L51 Connecting Office Power (DC) to the NCS 2002 Shelf (ETSI Only)
Purpose
Cisco NCS 2000 Series Hardware Installation Guide
88
Use only pressure terminal connectors, such as ring and fork types, when terminating the battery,
battery return, and frame ground conductors.
Before you make any crimp connections, coat all bare conductors (battery, battery return, and
frame ground) with an appropriate antioxidant compound. Bring all unplated connectors, braided
strap, and bus bars to a bright finish, then coat with an antioxidant before you connect them. You
do not need to prepare tinned, solder-plated, or silver-plated connectors and other plated connection
surfaces, but always keep them clean and free of contaminants.
When terminating power, return (RET), and frame ground, do not use soldering lug, screwless
(push-in) connectors, quick-connect, or other friction-fit connectors.
Connecting Power and Ground
This task connects power to the NCS 2002 shelf
(ETSI Only).