NTP-L47 Mounting NCS 2015 Shelf
Stability hazard. The rack stabilizing mechanism must be in place, or the rack must be bolted to
Warning
the floor before you slide the unit out for servicing. Failure to stabilize the rack can cause the rack
to tip over. Statement 1048
Warning
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
installation. Install only in accordance with national and local wiring regulations. Statement 1045
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure
that the protective device is rated not greater than: 40A and between -40.5 VDC to -57.6 VDC.
Statement 1005
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure
Warning
that the protective device is rated not greater than: 10A-20A, 100-240 VAC~. Statement 1005
To prevent the system from overheating, do not operate it in an area that exceeds the maximum
Warning
recommended ambient temperature of: 131°F (55°C). Statement 1047
Take care when connecting units to the supply circuit so that wiring is not overloaded. Statement
Warning
1018
To prevent bodily injury when mounting or servicing this unit in a rack, you must take special
Warning
precautions to ensure that the system remains stable. The following guidelines are provided to ensure
your safety:
• This unit should be mounted at the bottom of the rack if it is the only unit in the rack.
• When mounting this unit in a partially filled rack, load the rack from the bottom to the top
with the heaviest component at the bottom of the rack.
• If the rack is provided with stabilizing devices, install the stabilizers before mounting or
servicing the unit in the rack. Statement 1006
To prevent airflow restriction, allow clearance around the ventilation openings to be at least:1 inch
Warning
(25.4 mm) Statement 1076
Make sure that the correct type of 19-inch ANSI rack is used for mounting the NCS 2015 shelf.
Note
Cisco NCS 2000 Series Hardware Installation Guide