Ntp-L42 Install The Air Plenum In Ncs 2002 Shelf - Cisco NCS 2006 Hardware Installation Manual

Ncs 2000 series
Table of Contents

Advertisement

NTP-L42 Install the Air Plenum in NCS 2002 Shelf

Rack / Cabinet
ANSI 23-inch rack
ANSI 23-inch cabinet
ETSI cabinet
1 A minimum opening of 20.600 inches is required to install the vertical air plenum behind the front rails.
The ANSI 19-inch two post rack that is compatible with air plenum installation is available from Telect,
Note
with part number 12545-301.
Figure 13: Minimum rear opening for ANSI 19-inch and ETSI configuration
NTP-L42 Install the Air Plenum in NCS 2002 Shelf
Purpose
Cisco NCS 2000 Series Hardware Installation Guide
28
Installing the Air Flow Regulator
Front-to-back air flow
Supported
Supported
1
Supported
This procedure installs the air plenum to orient the
air flow in front-to- back direction in the NCS 2002
shelf.