Siemens RUGGEDCOM RS930L Installation Manual
Siemens RUGGEDCOM RS930L Installation Manual

Siemens RUGGEDCOM RS930L Installation Manual

Hide thumbs Also See for RUGGEDCOM RS930L:

Advertisement

Quick Links

RUGGEDCOM RS930L
Installation Guide
10/2013
Preface
Introduction
Installing the Device
Communication Ports
Technical Specifications
Dimension Drawings
Certification
1
2
3
4
5
6

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RUGGEDCOM RS930L

  • Page 1 Preface Introduction Installing the Device RUGGEDCOM RS930L Communication Ports Technical Specifications Dimension Drawings Installation Guide Certification 10/2013...
  • Page 2: Security Information

    Warranty Siemens warrants this product for a period of five (5) years from the date of purchase, conditional upon the return to factory for maintenance during the warranty term. This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void.
  • Page 3: Table Of Contents

    RUGGEDCOM RS930L Installation Guide Table of Contents Table of Contents Preface ........................ Alerts ..............................v Related Documents ..........................v Accessing Documentation ........................v Training .............................. vi Customer Support ..........................vi Chapter 1 Introduction ......................1.1 Feature Highlights ........................1 1.2 Ports, Controls and Indicator LEDs ....................2 Chapter 2 Installing the Device ....................
  • Page 4 RUGGEDCOM RS930L Table of Contents Installation Guide 4.4 Mechanical Specifications ......................18 Chapter 5 Dimension Drawings ..................Chapter 6 Certification ......................6.1 Agency Approvals ........................21 6.2 FCC Compliance ........................21 6.3 Industry Canada Compliance ...................... 21 6.4 EMI and Environmental Type Tests ..................... 22...
  • Page 5: Preface

    Installation Guide Preface Preface This guide describes the RUGGEDCOM RS930L. It describes the major features of the device, installation, commissioning and important technical specifications. It is intended for use by network technical support personnel who are responsible for the installation, commissioning and maintenance of the device.
  • Page 6: Training

    Siemens sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, please contact Customer Support at: Toll Free (North America): 1 866 922 7975...
  • Page 7: Introduction

    Introduction Introduction The RUGGEDCOM RS930L is a six-port industrially hardened, fully managed Ethernet switch supporting Ethernet over VDSL (EoVDSL) allowing up to 5km LAN segments over telephone grade cable (or other legacy serial cabling) at up to 35 Mbps. The RS930L allows for aggregation of Ethernet enabled devices at a remote location back to the central control room with EoVDSL using existing telephone grade cable (or other legacy serial cabling).
  • Page 8: Ports, Controls And Indicator Leds

    Chapter 1 RUGGEDCOM RS930L Introduction Installation Guide Ethernet Over VDSL (EoVDSL) • Up to 5 km (3 mi) LAN segments • Symmetric data rates up to 35 Mbps • Asymmetric data rates up to 40 Mbps • Automatically selects fastest data rate based on distance and quality of cable •...
  • Page 9 RUGGEDCOM RS930L Chapter 1 Installation Guide Introduction Figure 1: Front Panel 1. Power Indicator LEDs 2. Alarm Indicator LED 3. RS232 Serial Console Port Power Indicator LEDs The power indicator LED illuminates when power is being supplied to the device.
  • Page 10 RUGGEDCOM RS930L Chapter 1 Installation Guide Introduction Ports, Controls and Indicator LEDs...
  • Page 11: Installing The Device

    This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. Changes or modifications not expressly approved by Siemens AG could invalidate specifications, test results, and agency approvals, and void the user's authority to operate the equipment.
  • Page 12: Mounting The Device On A Din Rail

    Chapter 2 RUGGEDCOM RS930L Installing the Device Installation Guide • Section 2.1.1, “Mounting the Device on a DIN Rail” • Section 2.1.2, “Mounting the Device to a Panel” Section 2.1.1 Mounting the Device on a DIN Rail For DIN rail installations, the RS930L can be equipped with a DIN rail bracket pre-installed on the back of the chassis.
  • Page 13: Connecting Power

    Ground. Note that all line-to-ground transient protection circuitry will be disabled. IMPORTANT! Siemens requires the use of external surge protection in VDSL applications where the line may be subject to surges greater than that for which the device is rated. Use the following specifications as a guide for VDSL external surge protection: •...
  • Page 14: Connecting High Ac/Dc Power

    Chapter 2 RUGGEDCOM RS930L Installing the Device Installation Guide • Insertion Loss: < 0.1 dB at 10 MHz • Peak Surge Current: 10 kA, 8x20µs waveform The following sections describe how to connect power to the device: • Section 2.2.1, “Connecting High AC/DC Power”...
  • Page 15: Connecting Low Dc Power

    RUGGEDCOM RS930L Chapter 2 Installation Guide Installing the Device Figure 4: Terminal Block Wiring 1. Positive/Live (+/L) Terminal 2. Negative/Neutral (-/N) Terminal 3. Surge Ground Terminal 4. Braided Ground Cable Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
  • Page 16: Connecting The Failsafe Alarm Relay

    Chapter 2 RUGGEDCOM RS930L Installing the Device Installation Guide Figure 5: Terminal Block Wiring 1. Positive Terminal 2. Negative Terminal 3. Surge Ground Terminal 4. Braided Ground Cable Connect the negative wire from the power source to the negative terminal on the terminal block.
  • Page 17: Connecting To The Device

    RUGGEDCOM RS930L Chapter 2 Installation Guide Installing the Device Figure 6: Failsafe Alarm Relay Wiring 1. Normally Open 2. Common 3. Normally Closed Section 2.4 Connecting to the Device The following describes the various methods for accessing the ROS console and Web interfaces on the device.
  • Page 18: Cabling Recommendations

    Section 2.5 Cabling Recommendations Siemens does not recommend the use of copper cabling of any length for critical, real-time substation automation applications. All copper Ethernet ports on RUGGEDCOM products include transient suppression circuitry to protect against damage from electrical transients and conform with IEC 61850-3 and IEEE 1613 Class 1 standards.
  • Page 19: Communication Ports

    RUGGEDCOM RS930L Chapter 3 Installation Guide Communication Ports Communication Ports The RS930L can be equipped with various types of communication ports to enhance its abilities and performance. To determine which ports are equipped on the device, refer to the factory data file available through ROS .
  • Page 20: Eovdsl Wiring

    Communication Ports Installation Guide Siemens offers two flavors of VDSL: Universal EoVDSL and Long-Reach EoVDSL. Universal EoVDSL ports are Master/Slave selectable and offer symmetric data rates up to 35 Mbps with distances up to 2.5 km (1.6 mi). Long- Reach EoVDSL ports are fixed as either Master or Slave but offer asymmetric data rates up to 40 Mbps with distances up to 5 km (3.1 mi).
  • Page 21: Configuration And Setup

    RUGGEDCOM RS930L Chapter 3 Installation Guide Communication Ports • Twisted-pairs are an effective way of reducing both magnetic and capacitive interference because they reduce the magnetic loop area to nearly zero and maintain a consistent distribution of capacitances to both ground and other sources.
  • Page 22 Chapter 3 RUGGEDCOM RS930L Communication Ports Installation Guide On 24 American Wire Gage (AWG) Polyethylene Insulated Cable (PIC) twisted-pair wiring, the following performance is typical with Universal EoVDSL ports: Downstream / Time to Achieve Port Up Distance (km) Distance (feet)
  • Page 23: Technical Specifications

    RUGGEDCOM RS930L Chapter 4 Installation Guide Technical Specifications Technical Specifications The following sections provide important technical specifications related to the device and available modules: • Section 4.1, “Power Supply Specifications” • Section 4.2, “Failsafe Relay Specifications” • Section 4.3, “Operating Environment”...
  • Page 24: Operating Environment

    Chapter 4 RUGGEDCOM RS930L Technical Specifications Installation Guide Section 4.3 Operating Environment Parameter Range Comments Ambient Operating Temperature -40 to 85 °C Measured from a 30 cm (12 in) radius surrounding the center of the (-40 to 185 °F) enclosure.
  • Page 25: Dimension Drawings

    RUGGEDCOM RS930L Chapter 5 Installation Guide Dimension Drawings Dimension Drawings NOTE All dimensions are in millimeters, unless otherwise stated. 65.13 116.59 7.87 Figure 10: Overall Dimensions...
  • Page 26 Chapter 5 RUGGEDCOM RS930L Dimension Drawings Installation Guide 13.64 101.60 11.18 78.74 120.65 Figure 11: Panel and DIN Rail Mount Dimensions...
  • Page 27: Certification

    RUGGEDCOM RS930L Chapter 6 Installation Guide Certification Certification The RS930L device has been thoroughly tested to guarantee its conformance with recognized standards and has received approval from recognized regulatory agencies. • Section 6.1, “Agency Approvals” • Section 6.2, “FCC Compliance”...
  • Page 28: Emi And Environmental Type Tests

    Chapter 6 RUGGEDCOM RS930L Certification Installation Guide Section 6.4 EMI and Environmental Type Tests The RS930L has passed the following EMI and environmental tests. IEC 61850-3 Type Tests Test Description Test Levels Severity Levels IEC 61000-4-2 Enclosure +/- 8 kV...
  • Page 29: Environmental Type Tests

    RUGGEDCOM RS930L Chapter 6 Installation Guide Certification Test Description Test Levels Severity Levels IEC 60255-5 Dielectric Strength Signal ports 2 kVAC (Fail-Safe Relay output) DC Power ports 1.5 kVDC AC Power ports 2 kVDC HV Impulse Signal ports 5 kV (Fail-Safe Relay Output)
  • Page 30 Chapter 6 RUGGEDCOM RS930L Certification Installation Guide Test Description Test Levels Severity Levels IEC 60068-2-30 Humidity (Damp Test Db 95% (non-condensing), Heat, Cyclic) 55 °C (131 °F), 6 cycles IEC 60255-21-1 Vibration 2 g @ 10-150 Hz Class 2 IEC 60255-21-2...