Advertisement

Permanent Connection
In the case of a permanent connection, it is necessary that you install a double pole switch
between the hob and the electricity supply (mains), with a minimum gap of 3 mm between
the switch contacts and of a type suitable for the required load in compliance with the
current electric regulations.
The switch must not break the yellow and green earth cable at any point.
Ensure that the hob supply cord does not come into contact with surfaces with
temperatures higher than 50 deg. C.
Replacement of the cable
The connection of the voltage cable to the appliance's terminal block is of type "Y". This
means that its replacement requires the specific equipment of a technician.
In this case, only cable types H05 V2V2-F (T90) must be used. The cable section must
be suitable to the voltage and the working temperature.
The yellow/green earth wire must be approximately 2 cm longer than the phase wires.

Wiring diagram

1. IGNITOR SWITCHES
2. IGNITOR UNIT