hit counter script

Cisco Nexus 93180YC-FX3 Hardware Installation Manual page 33

Aci-mode switch
Hide thumbs Also See for Nexus 93180YC-FX3:
Table of Contents

Advertisement

Installing the Switch Chassis
Chassis
N9K-C9336C-FX2-E
N9K-C9348GC-FXP
N9K-C93108TC-FX
N9K-C93108TC-FX3P
N9K-C93180YC-FX
N9K-C93180YC-FX3
N9K-C93180YC-FX3S
N9K-C93600CD-GX
Note
You supply the screws to mount the airflow sleeve.
Before you begin
• Verify that your shipment is complete.
• Install your rack in a secure location.
Insert the airflow sleeve into the rack and attach it as follows:
a) Holding the airflow sleeve (N9K-AIRFLOW-SLV) with both hands, position it in front of the fan side of the chassis.
b) Holding the airflow sleeve level, insert screws (12-24 or 10-32, depending on the rack type) in each of the two front
rack-mount flanges (using a total of two screws) and into the cage nuts or threaded holes in the vertical rack-mounting
rails (see the following figure).
c) Tighten the 10-32 screws to 20 in-lb (2.26 N·m) or tighten the 12-24 screws to 30 in-lb (3.39 N·m).
Minimum Rack Depth
806.90 mm
672.49 mm
781.29 mm
672.49 mm
781.29 mm
672.49 mm
672.49 mm
824.80 mm
Cisco Nexus 93180YC-FX3 ACI-Mode Switch Hardware Installation Guide
Installing the Airflow Sleeve (N9K-AIRFLOW-SLV)
Maximum Rack Depth
898.70 mm
764.29 mm
873.09 mm
769.69 mm
873.09 mm
784.25 mm
784.25 mm
916.60 mm
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

N9k-c93180yc-fx3N9k-c93180yc-fx3h

Table of Contents

Save PDF