Rack-Mount the Chassis
The rack must be of the following type:
• A standard 19-inch (48.3-cm) wide, 4-post EIA rack with mounting posts that conform to English universal
• The rack post holes can be square 0.38-inch (9.6 mm), round 0.28-inch (7.1 mm), #12-24 UNC, or #10-32
• The minimum vertical rack space per appliance must be 1 RU, equal to 1.75 inches (44.45 mm).
• The slide rails for the chassis have an adjustment range of 24 to 36 inches (610 to 914 mm).
Note
Safety Warnings
Warning
Step 1
Attach the inner rails to the sides of the chassis:
a) Align an inner rail with one side of the chassis so that the three keyed slots in the rail align with the three pegs on the
side of the chassis.
b) Set the keyed slots over the pegs, and then slide the rail toward the front to lock it in place on the pegs. The front slot
has a metal clip that locks over the front peg.
c) Install the second inner rail to the opposite side of the chassis.
Figure 32: Attach the Inner Rail to the Side of the Server
Cisco Email Security Appliance C195, C395, C695, and C695F Hardware Installation Guide
32
hole spacing per section 1 of ANSI/EIA-310-D-1992.
UNC when you use the supplied slide rails.
The slide rails that ship with the chassis do not require tools for installation if you install them in a rack
that has square 0.38-inch (9.6 mm), round 0.28-inch (7.1 mm), or #12-24 UNC threaded holes.
Take note of the following warning:
Statement 1006 Chassis Warning for Rack-Mounting and Servicing
To prevent bodily injury when mounting or servicing this unit in a rack, you must take special
precautions to ensure that the system remains stable. The following guidelines are provided to
ensure your safety:
• This unit should be mounted at the bottom of the rack if it is the only unit in the rack.
• When mounting this unit in a partially filled rack, load the rack from the bottom to the top
with the heaviest component at the bottom of the rack.
• If the rack is provided with stabilizing devices, install the stabilizers before mounting or
servicing the unit in the rack.
Rack-Mount the Chassis