Model SS3 Multi-Spectrum Digital Electro-Optical Fire Detectors
Installation Guide and Operating Manual
MAN0932_V1_1508002_Rev B_08-12
2.3.1
Wiring as Standalone
Connect the 24 volt DC Power Supply wires into the connector and firmly tighten down the slotted
screws with a small screwdriver. DO NOT CONNECT ANY WIRES TO J1 - Pin 2 or J1 - Pin 3. Do
NOT over tighten or the screws may strip or break. Refer to Figure 4, Model SS3 Detector Wiring.
2.3.2
Wiring to FS2000 (FireBus)
Connect the FireBus Cable wires into the connector and firmly tighten down the two slotted screws with a
small screwdriver. Do NOT over tighten or the screws may strip or break.
SS3 Detector Wiring.
2.3.3.
Wiring the Fire Relay
For Stand-Alone or FS2000 systems: Connect the initiating circuit wires to the four pin WECO terminal.
Install the wires into Pins 7 and 8 (for Normally Open relay) or Pins 6 and 7 (for Normally Closed relays)
and firmly tighten down the slotted screws with a small screwdriver. There is an internal 10K ohm
resistor between Pins 5 and 6 for circuits which require an End of Line (Supervision) resistor. One
common configuration is to Jumper Pins 5 to 8 and connect the initiating circuit to Pins 7 and 8.
Refer to Figure 4, Model SS3 Detector Wiring, for more details on relay connections.
Pin 1
Black
Green or Blue
G
(-)
NOT USED
ROUND
Pin 1
Black
Green or Blue
G
(-)
F
ROUND
IRE
Pin 2
Pin 3
White or Yellow
NOT USED
Pin 2
Pin 3
White or Yellow
B
(R
)
F
B
US
X
IRE
US
Pin 4
Red
P
(+)
OWER
Refer to Figure 4, Model
Pin 4
Red
(T
)
P
(+)
X
OWER
3