WARNINGS Sensepoint XCD RFD is designed for installation and use in Class I, Division 1, Groups B,C & D Hazardous Areas in the Americas. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned.
The Start-up/Surge/In rush current is dependant on the type of power supply used. The typical start-up current for Sensepoint XCD RFD is less than 800mA. Measure the start- up current using the specific power supply before installation to ensure suitability for your application.
The construction of Sensepoint XCD RFD allows it to be used in hazardous area locations; it may also be used in other areas not classified as hazardous. Sensepoint XCD RFD is suitable for use in Class I Division 1 areas.
The Sensepoint XCD/RFD Transmitter is designed to work with the following flammable gas sensor types described in below sections 4.2.1, 4.2.2 and 4.2.3. Sensepoint XCD sensors use electro-catalytic technologies. The Sensepoint XCD RFD is cCSAus approved for use in North America.
¾”NPT thread only. The 705 HT is UL approved only. Details for connecting these sensors with the Sensepoint XCD RFD transmitter are provided in sections 5 and 6. For more sensor specific details, refer to the Technical Handbook Part No.
SPXCDHMRFENU Issue 1 4.3 Accessories A range of accessories are available to allow use of Sensepoint XCD RFD in a wide variety of applications. These include Pipe mounting bracket, Sunshade deluge cover, Sensor collecting cone, Sensor flow Housing and Remote sensor mounting junction boxes.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 4.4 Options ® 4.4.1 Modbus ® One of the most common field buses in the industry, the optional Modbus interface allows the XCD to connect to a bus of devices and transmit data to PLCs or controllers (see Appendix A).
Page 11
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 (MODBUS ID SETTING) Set id>>Set ModBus slave ID>>Set Baud rate>>Set Parity 1) Slave ID shall be set 1~247 2) Baud rate setting 9600 or 19200 3) Parity setting (No, Even, Odd) From the Configuration Mode screen, select‘’. To set the ModBus Slave ID, use the up- down ‘’switches to move to the desired position and use ‘’to select it.
17. WARNINGS Sensepoint XCD RFD is designed for installation and use in Class I, Division 1, Group B,C & D Hazardous Areas in the Americas. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned.
5.2 Mounting the transmitter The Sensepoint XCD RFD transmitter has an integral mounting plate consisting of four mounting holes on the transmitter body. The transmitter may be fixed directly to a surface mounting, or to a horizontal or vertical pipe/structure, 40.0-80.0mm (1.6 to 3.1 inches) in...
1. Connect the remote sensor/junction box to the Sensepoint XCD RFD transmitter using suitable cable with wires of diameter 0.5 ~ 2.5mm2 (20AWG ~ 13AWG). 2. Connect the cable to the transmitter enclosure via the bottom entry.
SPXCDHMRFENU Issue 1 6 Electrical connections WARNINGS Sensepoint XCD RFD is designed for installation and use in Class I, Division 1, Group B,C & D Hazardous Areas in the Americas. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned.
Caution: All electrical connections should be made in accordance with any relevant local or national legislation, standards or codes of practice. The Sensepoint XCD RFD transmitter may be wired in either Current SOURCE or Current SINK configuration. These two options are offered to allow greater flexibility in the type of control system that it can be used with.
Note: Terminal Blocks are Terminal block for plug/socket type Sensepoint or 705 and may be Flammable sensor removed to ease wiring. Diagram 6: Sensepoint XCD RFD Terminal module Terminal Module Connections Terminal Marking Connection Description Number +VE Supply(16-32VDC) -VE Supply(0VDC)
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 6.3 Power The Sensepoint XCD transmitter requires a power supply from the controller of between 16Vdc and 32Vdc. Ensure that a minimum supply of 16Vdc is measured at the sensor, taking into account the voltage drop due to cable resistance.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 6.4 Cabling The use of industrial grade, suitably armoured field cable is recommended. For example, screened 3 cores (plus screen 90% coverage), suitably mechanically protected copper cable with a suitable 3/4" explosion-proof gland with 0.5 to 2.5 mm2 (20 to 13 AWG) conductors.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 The Earth Screen of the field cable should be “tied to Earth” or connected to Ground at one point only. It is common practise to adopt a STAR EARTH connection regime where all instrumentation Screens are connected at one common point.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 7 Default configuration The Sensepoint XCD RFD transmitter is supplied with the following default configuration. Function Value/Setting Meaning XCD RFD recognizes the XCD RFD sensor cartridge Automatic for Sensepoint XCD RFD according to the gas type within its own sensor family Sensor Type sensors.
SPXCDHMRFENU Issue 1 8 Normal Operation Sensepoint XCD RFD is supplied configured and ready for use according to the “Default Settings” table shown above. However these setting may be tailored to a specific application requirement using the Sensepoint XCD RFD configuration menu system.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 8.2 System Status Display indications, current output and relay states for various operational conditions are shown in the following table. For further details of error messages and trouble shooting see section 12.3.
Communication with the XCD RFD is achieved by positioning the Magnetic Wand at one of three different positions on the front glass window of the Sensepoint XCD RFD transmitter. Activation of the switches is verified by observing the Magnetic Wand Activation Icon on the LCD display...
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 9 First time switch on (Commissioning) WARNING The following procedure requires the Transmitter Cover to be removed while carrying out supply voltage checks. Therefore the appropriate permits to work should be sought in preparation.
Page 26
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Note: For a full description of each screen shown in Diagram 12, please refer to Section 13.3 “Review Mode” of this Manual. Diagram 12: Normal Start up procedure (For the Flammable sensor version) 11.
If no residual gas is present then the background air can be used to perform the zero calibration. Contact your Honeywell Analytics representative for details of suitable calibration kits.
Page 28
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 (ZERO CALIBRATION) 1. If the ambient air is NOT considered reliable to use to set the ZERO, then remove the weather protection and fit the Gassing Cap accessory (see Section 4.3) onto the sensor and apply a clean source of zero gas or compressed air.
Page 29
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 (SPAN CALIBRATION) 11.The display shows the current calibration span gas concentration while flashing the ‘ ’ icon. Use ‘ ’ to change the calibration span gas concentration, and ‘ ’ when ...
Page 30
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 19.Promptly switch off the calibration span gas and remove the Sensepoint XCD Gassing Cap from the sensor to allow the gas to disperse. 20.When the reading falls below 50% of the calibration gas level the display indicates a countdown .
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 11 General Maintenance WARNINGS Access to the interior of the transmitter, when carrying out any work, must only be conducted by trained personnel. Before carrying out any work ensure local regulations and site procedures are followed.
A fault condition will be signalled by the detector if the sensor is removed with the unit under power. 12.1 Sensor replacement The sensors that are used with the Sensepoint XCD RFD have no serviceable parts. When they have reached the end of their operational life, simply replace the sensor or the sensor cartridge.
Page 33
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 WARNING Ensure that the same Gas Type and Range of Sensor is fitted in place of the old Sensor. The sensor head must be fitted with the supplied weather protection, and mounted so that the sinter is pointing downward to provide ingress protection IPX6.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 12.2 Replacing Modules within the Transmitter Two replaceable module assemblies are located within the transmitter housing. The Display Module and the Terminal Module. The Display Module is simply removed by unplugging it from the Terminal Module (this procedure is done during normal installation).
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 12.3 Faults and Warnings The table below provides details of possible error. Message Description Action The unit has not been calibrated for the configured calibration interval W-01 Calibration needed Calibration is necessary due to change...
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 13 Menu’s and Advanced Configuration 13.1 Abort Function In Review Mode or Configuration Mode the user can escape one step back from the current position using the Abort Function. To do this the user must activate the Enter switch for more than 3 seconds with the Magnetic Wand.
Page 37
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Menu Display Description Execute zero/span calibration Set calibration gas level Set Calibration After zero, the option exists to proceed with span calibration, or return to the Menu. Select the type of sensor from the sensor list.
Page 38
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Configure relay on delay time, relay off delay Relay Operation time and latch/non-latch Set location (or TAG number) Set Location Change temperature display unit. Set Temperature Unit °C (Celsius) or °F (Fahrenheit)
Page 39
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Monitoring Mode Menu Switch ( > 3 Seconds) Quit/ESC command Auto quit after no activity of timeout Access permitted? Abort Release mA O/P Inhibit mA O/P Force Current Set Calibration Set Alarms...
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 13.2.1 Configuration mode operation table Configuration mode allows the user to perform calibration and configure parameters such as full scale range, calibration gas level, calibration interval, inhibit current & timeout, alarm settings, relay settings, set a password, etc. To activate Configuration mode hold the magnet over the ENTER switch for at least 3 seconds and then remove.
Page 41
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 PEAK READING CURRENT GAS DISPLAYED WITH OUTPUT CONCENTRATION INHIBITED ‘ ’ ICON AND DISPLAYED WITH bumP UNIT RETURNS TO PEAK STRING FLASHING. OUTPUT INHIBITED ‘ ’ tESt MENU MODE APPLY BUMP TEST ICON FLASHING.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 13.3 Sensor / Gas Selection 13.3.1 Sensor Selection “Select Sensor” sets the identity of the type of mV sensor attached to the XCD RFD when it does not detect the sensor type automatically.
Page 43
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 The current configuration of the XCD RFD is displayed and by using the ‘’ switch to enter “SEL gAS” menu. To select a flammable gas, use ‘’ to move through the list, and then use ‘’...
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 13.4 Review Mode The instrument will enter Review mode when the “Enter” switch is activated with the Magnetic Wand and held for around one second. Names, displays and descriptions for each review item in Review Mode are shown in the following table.
Page 45
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Location Location in which the transmitter is installed Power Power voltage* Temperature Internal Transmitter temperature* Peak conc. Maximum concentration detected up to now Test Result There is no fault detected. Table 13: Transmitter menu descriptions...
Page 46
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Menu Switch (1s to 3s) Review Monitoring Mode Mode Auto end to cycle S/W Version Test Result 2 second delay 2 second delay SRS Version Peak Reading 2 second delay 2 second delay...
* Extended operating temperature range of -40°C to +65°C (-40°F to +149°F) for all sensor , with an accuracy of +/- 30% of applied gas from -20°C to -40°C (-4°F to -40°F) and +55°C to +65°C (+131°F to +149°F). Long term operation at this range may cause decline in sensor performance. Contact Honeywell Analytics for any additional data or details. Certification International IEC Ex II 2 GD Ex d IIC Gb T6(Ta -40ºC to +65ºC) Ex tb IIIC T85ºC Db IP66...
Analytics reserves the right to charge for any site attendance where any fault is not found with the equipment. Honeywell Analytics shall not be liable for any loss or damage whatsoever or howsoever occasioned which may be a direct or indirect result of the use or operation of the Contract Goods by the Buyer or any Party.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 18 Certification 18.1 North America cCSAus Supplement to Certificate of Compliance Certificate: 2404330 Master Contract: 246287 The products listed, including the latest revision described below, are eligible to be marked in accordance with the referenced Certificate.
Page 60
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Certificate of Compliance Certificate: 2404330 Master Contract: 246287 Project: 2524595 Date Issued: September 28, 2012 Issued to: Honeywell Analytics Inc. 405 Barclay Blvd Lincolnshire, IL 60069 Attention: John Stratman The products listed below are eligible to bear the CSA...
Page 61
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Certificate: 2404330 Master Contract: 246287 Project: 2524595 Date Issued: September 28, 2012 Note: XX may be 00 to 02, 05 to 07, 10 to 18, 20 to 22 and 30 depending on which gas cell is installed in the Sensepoint Toxic sensor head.
Page 62
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Certificate: 2404330 Master Contract: 246287 Project: 2524595 Date Issued: September 28, 2012 CLASS 4828 01 CLASS 4828 81 Class I, Division 1, Groups B, C and D; Sensepoint XCD/RFD Stationary Combustible Gas Transmitter, Input rated 16 to 32 VDC, 5 watts max.
Page 63
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Certificate: Master Contract: 2404330 246287 Project: Date Issued: 2524595 September 28, 2012 UL 1203 (4th Ed.)- Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations ANSI/ISA -12.12.01-2010 - Non-Incendive Electrical Equipment for Use in Class I and II, Division 2 and Class III, Divisions 1 and 2 Hazardous( Classified) Locations.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 18.2 Inmetro Certificates ORSKE ERITAS ERTIFICADO DE ONFORMIDADE DNV 13.0006 09/05/2016 Certificado nº: Válido até: Certificate #/Certificado nº Validity Term/Fecha de Vencimiento Produto: TRANSMISSOR PARA DETECÇÃO DE GÁS Product/Producto Tipo / Modelo: XCD/RFD Type –...
Page 65
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 ORSKE ERITAS ERTIFICADO DE ONFORMIDADE DNV 13.0006 09/05/2016 Certificado nº: Válido até: Certificate #/Certificado nº Validity Term/Fecha de Vencimiento Descrição do Equipamento: O transmissor para detecção de gás modelo XCD/RFD consiste de um invólucro cilíndrico fabricado em liga de alumínio ou aço inoxidável com tampa roscada e visor de vidro temperado, o invólucro do transmissor possui três furos, sendo...
Page 66
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 ORSKE ERITAS ERTIFICADO DE ONFORMIDADE DNV 13.0006 09/05/2016 Certificado nº: Válido até: Certificate #/Certificado nº Validity Term/Fecha de Vencimiento Observações: 1. Este Certificado de Conformidade é válido para os produtos de modelo e tipo idêntico ao protótipo ensaiado.
Page 67
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 ORSKE ERITAS ERTIFICADO DE ONFORMIDADE DNV 13.0039 X 09/05/2016 Certificado nº: Válido até: Certificate #/Certificado nº Validity Term/Fecha de Vencimiento Produto: SENSOR DE GÁS Product/Producto Tipo / Modelo: Type – Model/Tipo – Modelo Solicitante: HONEYWELL ANALYTICS INC.
Page 68
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 ORSKE ERITAS ERTIFICADO DE ONFORMIDADE DNV 13.0039 X 09/05/2016 Certificado nº: Válido até: Certificate #/Certificado nº Validity Term/Fecha de Vencimiento Descrição do Equipamento: O sensor de gás modelo 705 consiste de um invólucro sextavado de alumínio para o sensor e um sensor de cartucho fabricado em aço inoxidável.
Page 69
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 ORSKE ERITAS ERTIFICADO DE ONFORMIDADE DNV 13.0039 X 09/05/2016 Certificado nº: Válido até: Certificate #/Certificado nº Validity Term/Fecha de Vencimiento 4. Os produtos devem ostentar, na sua superfície externa e em local visível, a Marca de Conformidade e as características técnicas da mesma de acordo com as especificações da ABNT NBR IEC 60079-0 /...
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 19 Cross Interference and Cross Calibration 19.1 Cross Calibration Flammable Gas Detector For greater accuracy, a catalytic gas detector should be calibrated using a certified gas/air mixture equal to 50% LEL of the actual target gas intended to be monitored.
Page 72
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 Propane Propan-2-ol Styrene Tetra hydrafuran Toluene Triethylamine Xylene Table 14 . Star Rating of Gases To cross calibrate the Sensepoint XCD combustible gas sensor: (1) Obtain the star rating for both the calibration test gas and the gas to be detected from...
Page 73
0-100%LEL Ethylene, when using 50% LEL Methane as the calibration gas. Section 19.1 is used for Sensepoint XCD Catalytic Sensor only, RFD with 705 and 705HT. Please contact your local Honeywell Analytics sales or service distributor, or regional offce should further clarification or additional information be required.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 XCD Transmitter ® Appendix A - Modbus Protocol A-2 A.1 Modbus and the XCD The XCD gas detector may be fitted with the optional Modbus board. Authoritative information on the MODBUS Upgrade Kit can be found at www.modbus.org. The XCD supports Modbus/RTU over an RS-485 physical layer.
Sensepoint XCD RFD Technical Manual SPXCDHMRFENU Issue 1 A.2 Modbus Registers ModBus Register Information Type Size Note Address 30001 Main SW Version of XCD 30002 EEP Version of XCD 30003 WatchDog s/w Version of XCD 30004 Location string string[12] 30010...