The following tools, equipment, and supplies necessary to connect the system ground to the chassis:
Use the following procedure to attach the grounding lug to the chassis ground connector on your chassis:
Step 1
Use the wire stripper to strip one end of the AWG #6 wire approximately 0.75 inches (19.05 mm).
Insert the AWG #6 wire into the wire receptacle on the grounding lug.
Step 2
Step 3
Use the crimping tool to carefully crimp the wire receptacle around the wire; this step is required to
ensure a proper mechanical connection.
Step 4
Attach the grounding lug with the wire so that the grounding wire does not overlap the power supply.
Figure 4-12
1
2
Locate the chassis ground connector on the side of your chassis.
Step 5
Insert the two screws through the holes in the grounding lug.
Step 6
Use the Number 2 Phillips screwdriver to carefully tighten the screws until the grounding lug is held
Step 7
firmly to the chassis. Do not overtighten the screws.
Connect the opposite end of the grounding wire to the appropriate grounding point at your site to ensure
Step 8
an adequate chassis ground.
This completes the procedure for attaching a chassis ground connection. Go to the following cabling
sections for information on attaching cables.
OL-13208-03
Phillips screwdriver
Dual-lug chassis ground component
Grounding wire
Attaching a Grounding Lug to the Chassis Ground Connector
Chassis ground lead wire
Grounding stud
Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation and Initial Configuration Guide
2
1
3
Ground screws
4
Chassis ground connector holes
Attaching a Chassis Ground Connection
3
4
4-19

Advertisement

Table of Contents
loading

Table of Contents

Save PDF