Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
2.1.7 Industry Canada ........................17 Use in hazardous areas ......................18 Requirements for special applications ..................19 Description ............................21 SITRANS LR560 overview ..................... 21 Installing/mounting ..........................23 Basic safety instructions ......................23 4.1.1 Installation location requirements ................... 24 4.1.2 Proper mounting ........................
Page 5
Table of contents Basic safety notes ........................35 5.1.1 Incorrect connection to power source ..................36 Connecting SITRANS LR560 ....................37 Basic PLC/mA configuration with HART ................38 Nameplates for hazardous area installations ................. 39 5.4.1 FM/CSA Class 1, Div 2 installation and connection diagram ..........39 Instructions specific to hazardous area installations ..............
Page 6
SIGNAL PROCESSING (2.7.) ....................121 8.2.7.1 NEAR RANGE (2.7.1.) ......................121 8.2.7.2 FAR RANGE (2.7.2.) ......................121 8.2.7.3 ECHO SELECT (2.7.3.) ......................122 8.2.7.4 SAMPLING (2.7.4.) ....................... 124 8.2.7.5 ECHO LOCK (2.7.4.1.) ......................124 SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 10
Technical support ........................201 QR code label ........................201 Certificates ..........................201 HMI menu structure..........................203 HMI menu ..........................203 List of abbreviations ..........................209 List of abbreviations ......................209 Glossary ............................. 211 Index..............................217 SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Introduction LR560 mA/HART manual usage Note This manual applies to the SITRANS LR560 mA/HART version only. HART is a registered trademark of the HART Communication Foundation. Designated use Use the device to measure process medium in accordance with the information in the Operating Instructions.
Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends to apply product updates as soon as available and to always use the latest product versions. Use of product versions that are no longer supported, and failure to apply latest updates may increase customer’s exposure to cyber threats.
The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
Observe the safety rules, provisions and laws applicable in your country during connection, assembly and operation. These include, for example: ● National Electrical Code (NEC - NFPA 70) (USA) ● Canadian Electrical Code (CEC) (Canada) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
2.1.5 Radio Equipment Directive (RED) compliance (Europe) Hereby, Siemens declares that the SITRANS LR560 is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU. The LR560 complies with EN 302 372 for use in closed storage vessels, when installed according to the installation requirements of EN 302 372, and may be used in all EU countries.
Industry Canada The SITRANS LR560 complies with Industry Canada standard RSS211 (March 2015). 1. The installation of the SITRANS LR560 shall be done by trained installers, in strict compliance with the manufacturer's instructions. 2. The use of this device is on a “no-interference, no-protection” basis. That is, the user shall...
● They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations. WARNING Use in hazardous areas Risk of explosion. • Only use equipment that is approved for use in the intended hazardous area and labelled accordingly. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Note Operation under special ambient conditions We highly recommend that you contact your Siemens representative or our application department before you operate the device under special ambient conditions as can be encountered in nuclear power plants or when the device is used for research and development purposes.
Page 21
Safety notes 2.3 Requirements for special applications SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Description SITRANS LR560 overview SITRANS LR560 is a 2-wire, 78 GHz FMCW radar level transmitter for continuous monitoring of solids and liquids in vessels to a range of 100 m (329 ft). The plug-and-play performance is ideal for all solids applications, including those with extreme dust and high temperatures to +200 °C (+392 °F).
Refer to the information in Technical data (Page 163). Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
• In plants with strong vibrations, mount the transmitter in a low vibration environment. CAUTION Aggressive atmospheres Damage to device through penetration of aggressive vapors. • Ensure that the device is suitable for the application. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Damage to device if the enclosure is open or not properly closed. The type of protection specified on the nameplate or in Technical data (Page 163) is no longer guaranteed. • Make sure that the device is securely closed. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Pressure equipment directive (PED, 2014/68/EU) Note Pressure-rated version only • SITRANS LR560 units are pressure tested, meeting or exceeding the requirements of the ASME Boiler and Pressure Vessel Code and the European Pressure Equipment Directive. • The serial numbers stamped in each process connection body provide a unique identification number indicating date of manufacture.
● There is a signal transmitted outside the beam angle, therefore false targets may be detected. Emission cone ● Keep emission cone free of interference from ladders, pipes, I-beams, or filling streams. ① Emission cone SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
–40 to +100 °C (–40 to +212 °F) or –40 to +200 °C (–40 to +392 °F) de- pending on the version 4.2.4 Sunshield The LR560 display can be protected by an optional sun shield if the instrument will be mounted in direct sunlight. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
– Holding the electronics enclosure firmly, loosen the Aimer locking ring using the supplied C spanner, until the LR560 drops down slightly. The enclosure can then be turned freely. 2. Direct SITRANS LR560 so the antenna is pointed at an angle perpendicular to the material surface, if possible.
• It is the customer’s responsibility to ensure that any vacuum or pressure in the measured vessel is maintained, considering the hole that passes through the process connection and SITRANS LR560 antenna system. Air Consumption (flow rate versus applied pressure) Air pressure (psi) Approx.
The optional display can be rotated as required, to one of 4 positions, 90 degrees apart, see Connecting SITRANS LR560 (Page 37). It can also be used to transfer parameters from one device to another, see COPY PARAMETERS TO DISPLAY (1.3.) (Page 108).
• Secure the remaining connections so that no damage can result if the process is started unintentionally. DANGER Pressure applications Danger to personnel, system and environment will result from improper disassembly. • Never attempt to loosen, remove, or disassemble process connection while vessel contents are under pressure. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (36 °F). • Before taking the device into operation let the device adapt for several hours in the new environment. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Risk of explosion through compensating currents between hazardous area and the non-hazardous area. • Shielded cables that cross into hazardous areas should be grounded only at one end. • If grounding is required at both ends, use an equipotential bonding conductor. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Connecting 5.2 Connecting SITRANS LR560 WARNING Incorrect selection of type of protection Risk of explosion in areas subject to explosion hazard. This device is approved for several types of protection. 1. Decide in favor of one type of protection. 2. Connect the device in accordance with the selected type of protection.
Depending on the system design, the power supply may be separate from the PLC, or integral to it. HART resistance (total loop resistance, that is, cable resistance plus 250 Ohm [resistor]) must be less than 550 Ohm for the device to function properly. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
FM/CSA Class 1, Div 2 installation and connection diagram The FM/CSA Class 1, Div 2 connection drawing A5E02795836 listed on the device nameplate can be downloaded from our website LR560 (www.siemens.com/LR560). Go to Support > Installation Drawings > Level Measurement > Continuous-Radar > SITRANS L560.
‘n’ or increased safety ‘e’ or flameproof ‘d’. ● The supply to the equipment shall be rated for a prospective short-circuit current of not more than 10 kA and shall be protected by a suitably-rated fuse. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Damage to device if the enclosure is open or not properly closed. The type of protection specified on the nameplate or in Technical data (Page 163) is no longer guaranteed. • Make sure that the device is securely closed. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 43
LEL. A value of 25% of the LEL is regarded as definitely safe. • Do not introduce combustible or hazardous gases into a restricted breathing enclosure (type of protection Ex nR). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
6.2 Activating the radar device Activating the radar device Power up the instrument. A transition screen showing first the Siemens logo and then the current firmware revision is displayed while the first measurement is being processed. The first time the device is configured, you will be prompted to select a language (English, German, French, Spanish or Chinese).
Page 45
① parameter name ② parameter number ③ parameter value/selection Press UP or DOWN arrow to switch In response to a key press request. For details, see Key functions in measurement mode (Page 47). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
6.4.1 Local operation SITRANS LR560 carries out its level measurement tasks according to settings made via parameters. The settings can be modified locally via the optional local graphical display which consists of an LCD display with buttons. You can use either the push buttons or an infrared handheld programmer to make changes.
The handheld programmer used with this device contains lithium batteries that are non- replaceable. WARNING Potential hazard This device contains lithium batteries. Lithium batteries may present a potential hazard if they are abused electrically or mechanically. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
RIGHT arrow opens Opens the top level menu. PROGRAM mode UP or DOWN arrow Local display shows measured value in either linear units or per- toggles between cent. linear units and per- cent SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Parameters are identified by name and organized into function groups, then arranged in a 5- level menu structure, see HMI menu (Page 203). 2. SETUP 2.7. SIGNAL PROCESSING 2.7.3. ECHO SELECT 2.7.3.1. ALGORITHM SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 50
• In Navigation mode, ARROW keys move to the next menu item in the direction of the arrow. • For Quick Access to parameters via the handheld programmer, press Home , and then enter the menu number, for example: 3.2. Echo Profile. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 51
Open Edit mode. LEFT arrow menu or parameter Open parent menu. Mode menu or parameter Change to MEASUREMENT mode. Home menu or parameter Open top level menu: menu 1. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 52
Secondary Value to be displayed in secondary region of LCD. Plus or minus sign Numeric editing Changes the sign of the entered value. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
5. After modifying a value, press RIGHT to accept it and press DOWN to move to the next item. 6. At any time, you can press UP to go back, or LEFT to cancel and return to Measurement mode. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 54
Selecting SLOW changes setting for AVERAGE AMOUNT (2.7.5.3.) (Page 126) to 0.9. Description: Use a setting just faster than the maximum vessel filling or vessel empty- ing rate (whichever is greater). Parameter view Edit mode SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 55
Distance to material surface referenced from Low calibration point SPACE Distance to material surface referenced from High calibration point DISTANCE Distance to material surface referenced from Sensor reference point Purpose: Sensor measurement units. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 56
0.000 to 40.000 m or 0.000 to 100.000 m Purpose: Distance from Sensor Reference Point to High Calibration Point: usually process full level. See Operating (Page 59) for an illustration. Parameter view Edit mode SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Position the intersection of the cross-hairs at the center of that area, an area select Zoom, and press RIGHT . Press LEFT to Zoom out. Update the Select Measure and press RIGHT profile Return to Select Exit then press RIGHT the previous menu SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Sensor measurement units. Operation LEVEL Material level referenced from low calibration point Low Calibration Point 15.5 Process empty level. High Calibration Point Process full level. Wizard Complete FINISH Save new settings and exit Wizard SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
SIMATIC PDM Version Check the support page of our website to make sure you have the latest version of SIMATIC PDM, the most recent Service Pack (SP) and the most recent hot fix (HF): Siemens Industry Online Support (https://support.industry.siemens.com/cs/?lc=en-WW) Browse to Product Support >...
4. After the reset is complete upload parameters to the PC/PG. 5. Configure the device via the Quick Start wizard. Set Address Open the menu Device>Set Address, enter a value for New Address and click on Assign Address. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
• For a vessel with obstructions see Auto False Echo Suppression via SIMATIC PDM (Page 69). Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to 4. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 63
PC/PG and ensure PDM is synchronized with the device. 2. If required, change the language for the local user interface. 3. Click on NEXT to accept the default values. (Description, Message, and Installation Date fields can be left blank.) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 64
• Selecting CONCRETE changes the setting for POSITION DETECT (2.7.3.3) (Page 122) to Rising Edge and for ALGORITHM (2.7.3.1) (Page 122) to ALF. Select the application type (steel or concrete silo construction), operation type (level, space, or distance) and then click on NEXT. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 65
Operating 7.1 Remote operation Step 3 – Ranges Note SLOW Response Rate Selecting SLOW Response Rate changes setting for AVERAGE AMOUNT (2.7.5.3.) (Page 126) to 0.9. Set the parameters, and click on NEXT. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
2. Adjust parameter values in the parameter value field then Enter. The status fields read Changed. 3. Open the Device menu, click on Download to device, then use File - Save to save settings offline. The status fields are cleared. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Echo profile utilities (Page 67) Maintenance (Page 72) Wear (Page 74) Select analog output (Page 73) Self test (Page 73) Loop test (Page 73) Configuration flag reset (Page 74) Master reset (Page 74) HART Communication (Page 74) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 68
● Change the position of the cursor on the TVT using the Point+ and Point– buttons: raise and lower the TVT using Offset+ and Offset-. ● Alternatively, enter values for Point and Offset directly into the dialog boxes. ● Click on Transfer to Device. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 69
● It is recommended to use the Detailed resolution view of the echo profile for troubleshooting. For faster and more coarse views, the Standard resolution may be used. ● Click Save and in the new window enter a name and click OK. ● Click OK to exit. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 70
See Auto False Echo Suppression (Page 127) for a more detailed explanation. The learned TVT will be applied over a specified range. The default TVT is applied over the remainder of the measurement range. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 71
TVT will be used. 8. To turn Auto False Echo Suppression off or on, reopen the Auto False Echo Suppression window, change the Auto False Echo Suppression to Off or On, click on Transfer to Device. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 72
Default TVT Material level ③ False echo After Auto False Echo Suppression ① ④ False echo Material level ② ⑤ Learned TVT Default TVT ③ ⑥ Auto False Echo Suppression Range Echo marker SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 73
2. Modify desired values, and if desired, set reminders for either or both of Reminder 1 before Lifetime (Required)/Reminder 2 before Lifetime (Demanded). 3. Click Write. 4. Click Read, to see the effects of your modification. 5. Click Snooze to add a year to the Total Expected Device Life. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 74
Click on OK. The Loop Test window remains open. 3. When you are ready to end simulation, select End and click on OK to return the device to the actual output value. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 75
The preamble consists of three or more hexadecimal FF characters (all 1s). This allows the receiving modem to get its frequency-detection circuits synchronized to the signal after any pause in transmission. We recommend you do not change the default value (5). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 76
To compare outputs in real time open the menu View – Process Variables and click on Overview to see reading (level, space, distance); analog output; device status; and current electronics temperature. To see highest and lowest electronics temperatures, navigate to Level Meter > Maintenance and Diagnostics > Electronics Temperature. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 77
Open the menu Diagnostics – Device Diagnostics to view Diagnostics, Device Status, Hardware/Firmware (HW/FW) Status, and Maintenance status. In the Diagnostics window, click on Update diagnostics to update diagnostic information and refresh linked icons. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
EDD is independent of the operating system. SITRANS DTM ● SITRANS DTM is an EDDL interpreter developed by Siemens to interpret the EDD for that device. ● To use SITRANS DTM to connect to an instrument, you must first install SITRANS DTM on your system and then install the instrument EDD written for SITRANS DTM.
Electronic Device Description (EDD) SITRANS LR560 requires the EDD for AMS Device Manager version 9.0. You can locate the EDD in Device Catalog, under Sensors/Level/Echo/Siemens Milltronics/SITRANS LR560. Check the product page of our website (www.siemens.com/LR560), under Support >...
Page 80
PDM, DTM, FC375) but is reset to 0 if the reset command is sent via LUI. ● Navigate to Configure/Setup > Operation ● In the General field click on Master Reset and accept the option Factory Defaults. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 81
• Scan Device uploads parameters from the device (synchronizes parameters). Device configuration 1. Navigate to Configure/Setup > Operation and click to open the dialog window. 2. In the General field, click on Master Reset and perform a reset to Factory Defaults. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 82
• Click on OK only if you wish to update all parameters to the device and close AMS. A Wizard provides an easy step-by-step Quick Start procedure that configures the device for a simple application. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 83
1. Navigate to Configure/Setup > Wizard > Quick Start. 2. Click on Step 1. 3. You can accept the default values without modification. (Description, Message, and Installation Date fields can be left blank.) If desired, make changes then click on Apply. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 84
Rising Edge and for ALGORITHM (2.7.3.1) (Page 122) to ALF 1. Click on Step 2. 2. Select the application type (Steel or Concrete) and the operation (Level, Space, or Distance). 3. Click on Apply. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 85
(Page 126) to 0.9. 1. Click on Step 3. 2. Change units if desired (in meters by default). 3. Set High and Low Calibration points. 4. Set Response Rate. 5. Click on Apply. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 86
Apply to write the new values to the device. The parameter field will display in yellow until the value has been written to the device. 2. Click OK only if you wish to update all parameters and exit AMS. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 87
● Master Reset, see Master reset (Page 79) Simulation/Test ● Self Test, see Self test (Page 73) ● Loop Test, see Loop test (Page 73) Setup Note For more detailed explanations of the parameters listed below see the pages referenced. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 88
● High Calibration Point ● Sensor Offset RATE (2.4.) (Page 114) ● Response Rate ● Fill Rate per Minute ● Empty Rate per Minute FAIL-SAFE (2.5.) (Page 116) ● Material level ● Timer ● Level SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 89
Navigate to Configure/Setup > Setup and click on Analog Output Scaling for access to: Analog Output Scaling, see ANALOG OUTPUT SCALING (2.6.) (Page 117) ● Current Output Function ● 4 mA Setpoint ● 20 mA Setpoint ● Minimum mA Limit ● Maximum mA Limit Signal Processing SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 91
● Navigate to Configure/Setup > Setup > Signal Processing and click on Echo Profile. ● To view a previous profile, click the drop-down arrow on the Time field and select the desired profile (note: available only using AMS version 10.1 or later). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
1. Open the window remaining device lifetime. 2. After modifying values/units as required, click on Apply to accept the change. 3. Click on Snooze for 1 Year to add a year to the Total expected device life. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 93
2. After modifying values/units as required, click on Apply to accept the change. 3. Click on Sensor replaced to reset Remaining lifetime to 0 hours. 4. Click on Snooze for 1 Year to add a year to the Total expected sensor life. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
● Time in operation (Reset to 0 after clicking Sensor Replaced) ● Poweron resets 7.1.3.3 Communication Navigate to Communication to read the following: Tag; Manufacturer’s ID; Device ID; Product ID; Device Revision; EDD Revision; Universal Command Revision SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Local access ● Local Operation Enable See also Password protection (Page 96) 7.1.3.5 Device Diagnostics Click on the Device Diagnostics bar at the bottom of the navigation window for access to Device Status. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 96
● Navigate to Process Variables>Echo Profile. ● To view a previous profile, click the drop-down arrow on the Time field and select the desired profile (note: available only using AMS version 10.1 or later). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 97
The Add User Wizard dialog allows you to: ● select a user type, standard (AMS Device Manager) or Window user. ● enter the username and password, and set permissions ● edit existing users SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Step 2 of 4: Application (tab) Application Type Operation Step 3 of 4: Ranges (tab) Unit Low Calibration Point (X) High Calibration Point (Y) Response Rate Step 4 of 4: Summary (tab) Long Tag SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 99
Damping Filter Low Calibration Point (X) High Calibration Point (Y) Sensor Offset Response Rate Fill Rate per Minute Empty Rate per Minute Material Level Timer Level Analog Output Scaling Analog Output Scaling (tab) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 102
Electronics Temperature Electronics Temperature Long Tag Electronics Temperature Lowest Value Highest Value Wear Wear (tab) Long Tag Time in Operation Poweron Resets POWERON RESETS (4.4.) (Page 139) COMMUNICATION Communication Communication (tab) Long Tag SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 103
Secondary Variable Analog Output (tab) Long Tag Distance Range (%) Analog Output (PV)= Trend View (tab) Long Tag Primary Variable Secondary Variable Echo Profile Echo Profile (tab) Long Tag Echo Profile/TVT Curve Distance Measurement SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 104
COMPARE Compare Identification (tab) Descriptor Message Date Manufacturer Product Name Universal Command Revision Device Revision Device ID Final Assembly Number Hardware Revision Software Revision Distributor Order Number Setup (tab) Long Tag Status Listing SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
8.1.1 QUICK START (1.) Wizards provide step-by-step procedures to configure the device, filter out false echoes, and upload and download parameters and firmware to the optional display for easy configuration of multiple LR560s. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
If you have a vessel with known obstructions, we recommend using AFES to prevent false echo detection. This feature can also be used if SITRANS LR560 displays a false high level, or the reading is fluctuating between the correct level and a false high level.
Page 108
Wizard Complete. 7. Press DOWN (Finish) to save AFES parameter changes and return to Program menu. 8. Press LEFT twice to return to Measurement mode. ① false echo ② true echo SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
8.1 WIZARDS (1.) 8.1.4 COPY PARAMETERS TO DISPLAY (1.3.) Transfers parameter settings from a device to the local display interface. See Connecting SITRANS LR560 (Page 37) for instructions on removing the local display interface. 1. Press RIGHT to edit. 2. Press DOWN to select Start and RIGHT to begin the transfer.
Start and RIGHT to begin the transfer. SW DOWNLOAD is displayed, then the device returns to Measurement mode. SETUP (2.) Note Handheld programmer Values shown in the following tables can be entered via handheld programmer. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Read only. Corresponds to the electronics hardware of the device. 8.2.1.7 FIRMWARE REVISION (2.1.7.) Read only. Corresponds to the firmware that is embedded in the device. 8.2.1.8 LOADER REVISION (2.1.8.) Read only. Corresponds to the software used to update the device. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
(see Damping (Page 187) for more detail). 8.2.2.4 TEMPERATURE UNITS (2.2.4.) Factory setting: Degrees C Setting range: Degrees C, F, R, or K Purpose: Selects the engineering unit to be displayed with the value representing temperature. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Any change to High Calibration Point will cause the mA setpoints to be updated. Related parameters: UNITS (2.2.1.) (Page 111) FAR RANGE (2.7.2.) (Page 121) The point from which level measurement is referenced. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
It may be necessary to reduce this further for FAST applications. ● Use a setting just faster than the maximum filling or emptying rate (whichever is faster). ● For the measurement value update time, see "Update time" in Performance (Page 163). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Defines the maximum rate at which the reported sensor value is allowed to increase. Allows you to adjust the SITRANS LR560 response to increas- es in the actual material level. Fill Rate is automatically updated whenever Response Rate is altered.
When a loss of echo occurs, MATERIAL LEVEL (2.5.1.) (Page 116) determines the material level to be reported when the fail-safe timer expires. Factory setting: 100 s Setting range: 0.00 to 7200 seconds Purpose: Sets the reaction speed of the device to measurement changes. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
• Use caution when changing Current Output Function while the device is connected to a HART network. Current Output Function controls the primary value and the loop current for the device. • Current Output Function also affects the secondary, tertiary and quaternary variables in a HART network. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 119
LOW CALIBRATION POINT (2.3.1.) (Page 113) HIGH CALIBRATION POINT (2.3.2.) (Page 113) Level Space Distance ① ② sensor reference point high calibration point ③ ④ 20 mA, 100% 4 mA, 0% ⑤ low calibration point SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Factory setting: 3.8 mA Setting range: 3.56 to 22.6 mA Purpose: Prevents the mA output from dropping below this minimum level for a measurement value. This does not restrict the Fail-safe or Manual settings. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
After completing the test, remember to reset mA Output mode (2.6.6.) • to the previous setting. Via SIMATIC PDM: Open the menu Device > Loop Test. • Related parameters: mA OUTPUT MODE (2.6.6.) (Page 120) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Loss of Echo (LOE) state, see SENSOR MODE (2.2.2.) (Page 111). Description: Use this feature if the measured surface can drop below the Low Cal. Point in normal operation. Related parameters: UNITS (2.2.1.) (Page 111) CLEF RANGE (2.7.3.4) (Page 123) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Selecting Steel or Concrete vessel type in the Quick Start wizard changes the setting for Position Detect to Rising Edge. Factory setting: RISING Setting range: RISING (yields highest stability on sloped targets) CENTER (yields higher accuracy on flat, non-sloped targets) HYBRID (CENTER and CLEF) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 124
CLEF Range (see illustration below). Above that point, the Center algo- rithm is used. Related parameters: POSITION DETECT (2.7.3.3) (Page 122) FAR RANGE (2.7.2.) (Page 121) ① ② CLEF Range Low calibration point ③ ④ Sensor reference point Far range SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
8.2.7.7 DOWN SAMPLING (2.7.4.3.) Factory setting: Setting range: 1 to 50 Purpose: Specifies the number of consecutive echoes that must appear below the echo currently selected, before the measurement is accepted as valid. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
TVT SETUP (2.8.) 8.2.8.1 AUTO FALSE ECHO SUPPRESSION (2.8.1) Note AFES wizard We recommend setting Auto False Echo Suppression either via SIMATIC PDM or via local operation using the Auto False Echo Suppression wizard. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
When the device is located in the center of the vessel, the TVT hover level may be lowered to increase the confidence level of the largest echo. 8.2.8.4 SHAPER MODE (2.8.4) Factory setting: Setting range: ON, OFF Purpose: Enables/disables the TVT shaper. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Demanded). This applies when clearing faults via the handheld programmer or 375 Field Communicator. To clear a fault using the handheld programmer, enter the fault code number then press RIGHT arrow. Internal Temperature High SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
2. Press RIGHT arrow to request a profile, see Requesting an Echo Profile (Page 56) 8.3.3 TREND (3.3.) Shows current trend. Samples are saved every minute up to 3200 samples. Once the maximum number is reached, saved data is overwritten from the beginning. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
MAXIMUM PRIMARY VALUE (3.4.4.) The maximum recorded Primary Value from the Analog Input Function Block 1. 8.3.9 MINIMUM SECONDARY VALUE (3.4.5.) The minimum recorded Secondary Value from the Analog Input Function Block 1. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Read only. Displays (in °C) the current temperature on the circuit board recorded by the internal electronics. For access via SIMATIC PDM open the menu View – Process Variables and check the field Electronics Temperature. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
TIME IN OPERATION (3.6.1.) Read only. The amount of time the device has been operating. 8.3.12.2 REMAINING LIFETIME (3.6.2.) Read only. LIFETIME EXPECTED (3.6.6.) (Page 134) less TIME IN OPERATION (3.6.1.) (Page 133). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Remaining Device Lifetime parameters in SIMATIC PDM. Factory setting: 10.00 years Setting range: 0 to 20 years Purpose: Allows you to override the factory default. Description: Units: hours, days, years, are selectable only via SIMATIC PDM. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
• The device operates in years. To view Remaining Device Lifetime parameters in hours or days (via SIMATIC PDM only) see LIFETIME EXPECTED (3.7.6.) (Page 137). Factory setting: years Setting range hours, days, years SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
If REMAINING LIFETIME (3.7.2.) (Page 136) is equal to or less than this value, the device generates a Maintenance Demanded reminder. Description: 1. Modify values as required. 2. Set REMINDER ACTIVATION (3.7.5.) (Page 137) to the desired option SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
ACKNOWLEDGE STATUS (3.7.8.) Indicates which level of maintenance reminder has been acknowledged. In SIMATIC PDM, open the menu Diagnostics > Device Diagnostics, click on the Maintenance tab, and check the Calibration Schedule Status window. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
• Following a reset to Factory Defaults, the LCD displays the Quick Start wizard. • Following a reset to Factory Defaults, complete reprogramming is required. Factory setting: Factory Defaults Setting range: Factory Defaults, Warm Start SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Contrast setting will depend on ambient temperature. Adjust the value to improve visibility in different temperatures and light conditions. Change the value in small steps to ensure you can continue to read the display. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
● In SIMATIC PDM, open the menu Device – Maintenance, click on the Service Schedule tab, and click on Service Performed to restart the timer and clear any fault messages. ● Via the handheld programmer, manually reset Time since Last Service to zero. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
To acknowledge a reminder via the local control buttons or hand-held program- mer: Press RIGHT arrow twice to open parameter view and activate Edit Mode. • Press RIGHT arrow to acknowledge the reminder. • SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
● Via the handheld programmer, manually reset Time since Last Calibration (4.8.1.) to zero. 8.4.8.2 TIME UNTIL NEXT CALIBRATION (4.8.2.) Read only. CALIBRATION INTERVAL (4.8.6.) (Page 145) less TIME SINCE LAST CALIBRATION (4.8.1.) (Page 143). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Allows you to enable a maintenance reminder. Description: 1. First set the values in REMINDER 1 (REQUIRED) (4.8.3.) (Page 144) REMINDER 2 (DEMANDED) (4.8.4.) (Page 144). 2. Select the desired Reminder Activation option. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Press RIGHT arrow twice to open parameter view and activate Edit Mode. • Press RIGHT arrow to acknowledge the reminder. • 8.4.9 STORED SOFTWARE VERSION (4.9.) Displays the version string of the firmware previously uploaded to the local display (if any). SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Enables/disables the read/write access to parameters via remote commu- nications. If locked via the handheld programmer, it can be unlocked only via the handheld programmer. If locked via AMS, it can be reset via AMS. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
To turn Lock Off, key in the Unlock Value 2457. • LANGUAGE (7.) Factory setting: English Setting range: English, Deutsch, Français, Español, 简体中文 Purpose: Selects the language to be used on the local display. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
● Reliability of power supply, lightning protection, and grounds WARNING Impermissible repair and maintenance of the device • Repair and maintenance must be carried out by Siemens authorized personnel only. WARNING Impermissible repair of explosion protected devices Risk of explosion in hazardous areas •...
The inscriptions could become unreadable. WARNING Electrostatic charge Risk of explosion in hazardous areas if electrostatic charges develop, for example, when cleaning plastic surfaces with a dry cloth. • Prevent electrostatic charging in hazardous areas. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
3. Visually inspect sensor inlet and outlet. Exception: Devices exclusively having the type of protection "Intrinsic safety Ex i" may be opened in an energized state in hazardous areas. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
• Close the device after maintenance work. Refer to Power (Page 163). Return procedure Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
– Number of returned devices/replacement parts – Reason for returning the item(s) ● Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment."...
Page 155
Service and maintenance 9.5 Disposal SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Simulation or substitute value • Communication is good; device is in simulation mode or works with substitute values. • Out of operation • Communication is good; device is out of action. • No data exchange • SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Adjust process conditions to minimize foam or • other adverse conditions. Correct configuration range. • If fault persists, contact your local Siemens rep- • resentative. S: 2 Unable to collect profile because of a power condition Repair required: contact your local Siemens repre- that is outside the operating range of the device.
Page 158
Inspect for heat-related damage and contact • your local Siemens representative if repair is re- quired. Fault code will persist until a manual reset is • performed using SIMATIC PDM or the local dis- play.
Page 159
EEPROM corrupt. Reset power. If fault persists, contact your local Siemens representative. S: 31 Flash error. Repair required: contact your local Siemens repre- sentative. S: 33 Factory calibration for the internal temperature sensor Repair required: contact your local Siemens repre- has been lost.
Page 160
1. Voltage low at the LR560 modify wiring or increase source voltage according- 2. Hardware defect ly, see Typical connection drawing (Page 190). For 2: Repair required: contact your local Siemens representative. S: 95 Device error. Repair required: contact your local Siemens repre- NOTE: Fault text and icons appear only on the local sentative.
CONFIDENCE (2.7.6.1) (Page 126). • Display shows material build-up on antenna Use the air purge feature to clean the antenna • re-locate SITRANS LR560. • Display shows location or aiming: check to ensure nozzle is vertical • poor installation •...
Try pressing Mode to put the device into PROGRAM mode. If you continue to experience problems, go to our website (www.siemens.com/LR560) and check the FAQs for SITRANS LR560, or contact your Siemens representative. SITRANS LR560 (mA/HART)
Page 163
Diagnosing and troubleshooting 10.4 Communication troubleshooting SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Technical data Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. 11.1 Power Nominal 24 V DC at 550 Ohm loop resistance . For other configurations, refer to Loop Power (Page 190).
−40 to +80 °C (−40 to +176 °F) Storage temperature −40 to +80 °C (−40 to +176 °F) Relative humidity suitable for outdoor use Type 4X/NEMA 4X, Type 6/NEMA 6, IP68 enclosure (see note above) Installation category Pollution degree SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Maximum and minimum temperatures are dependent on the process connection, antenna and O-ring materials. Use of the Easy Aimer limits maximum temperature. 11.6 Approvals data Note Approvals The device label lists the approvals that apply to your device. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 167
Groups A, B, C, D, T4 China NEPSI Ex nA II T4 Ex nL IIC T4 DIP A20 TA, T139 ºC CE Electromagnetic Compatibility (EMC) conformity Emission EN 55011 / CISPR-11 Immunity EN/IEC 61326-1 (Industry) NAMUR NE 21 SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Year 2014: Apha code = E Year 2020: Apha code = M Year 2015: Apha code = F Siemens Milltronics Infrared IS (Intrinsically Safe) Handheld Programmer for hazardous and all other locations (battery is non-replaceable). Approvals FM/CSA Class I, II, III, Div. 1, Gr. A to G T6 ATEX II 1GD Ex ia IIC T4 Ga Ex iaD 20 T135 °C...
Dimension drawings 12.2 SITRANS LR560 with 3" aimer flange 12.2 SITRANS LR560 with 3" aimer flange Note Bolt hole patterns and dimensions Refer to Universal slotted flange (Page 174) for bolt hole patterns and dimensions. Dimensions are in mm (inch) ①...
Dimension drawings 12.3 SITRANS LR560 with 4" and 6" aimer flange 12.3 SITRANS LR560 with 4" and 6" aimer flange Note Bolt hole patterns and dimensions Refer to Universal slotted flange (Page 174) for bolt hole patterns and dimensions. Dimensions are in mm (inch) ①...
Page 173
Dimension drawings 12.3 SITRANS LR560 with 4" and 6" aimer flange C Spanner A C spanner, used to loosen the aimer locking ring, is shipped with the device, packed separately. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Dimension drawings 12.4 SITRANS LR560 with stamped flange 12.4 SITRANS LR560 with stamped flange Note Bolt hole patterns and dimensions Refer to Stamped flange (Page 176) for bolt hole patterns and dimensions. Dimensions in mm (inch) ① ⑥ lid lock 110 (4.33)
① ⑤ bolt hole circle max. diameter flange O.D. ② ⑥ number of slotted bolt holes thickness ③ ⑦ bolt hole radius bolt hole circle min. diameter ④ section A-A SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 176
0.37 (9.5) 6 (150) 11.22 (285) 0.38 (9.65) 9.53 (242) 9.45 (240) 0.45 (11.5) Dimensions are in inch (mm) Universal flange mates with EN 1092-1 (PN16)/ASME B16.5 (150 lb)/JIS 2220 (10K) bolt hole pattern. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
TEST DATE 10/01/04 Date of Pressure Test (Year/Month/Day) PROCESS SERIES 25785 Pressure Tag Family Series WETTED NON-METALLIC PEI Sensor Lens Material WETTED METALLICS 304L Process Connection Material(s) WETTED SEALS FKM / VQM Seal Material(s) SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Electromagnetic waves are not attenuated by dust. SITRANS LR560 consists of an enclosed electronic circuit coupled to an antenna and process connection. The electronic circuit generates a radar signal (78 GHz) that is directed to the lens antenna.
Echo processing A.3.1 Process Intelligence The signal processing technology embedded in Siemens radar level devices is known as Process Intelligence. Process intelligence provides high measurement reliability regardless of the dynamically changing conditions within the vessel being monitored. The embedded Process Intelligence dynamically adjusts to the constantly changing material surfaces within these vessels.
Page 182
Center: Uses center of the echo. Hybrid: Uses the Center algorithm for the top part of the vessel, and the CLEF algorithm for the part nearest the vessel bottom, according to the setting for CLEF range. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 183
Example: CLEF off: Position set to Hybrid Vessel height: 1.5 m; CLEF range set to 0 (Center algorithm gives the same result.) ① default TVT ② material echo ③ vessel bottom echo selected ④ echo marker SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
In radar applications, two measurement verification options are used: Lock Off SITRANS LR560 responds immediately to a new selected echo (within the restrictions set by the Maximum Fill / Empty Rate), but measurement reliability is affected. SITRANS LR560 (mA/HART)
Auto False Echo Suppression Range must be set to a distance shorter than the distance to the material level when the environment was learned, to avoid the material echo being screened out. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 186
Example after Auto False Echo Suppression Auto False Echo Suppression Range set to 2 m ① ④ Learned TVT Default TVT ② ⑤ False echo Material echo ③ ⑥ Auto False Echo Suppression Range Echo marker SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Measurement range NEAR RANGE (2.7.1.) (Page 121) Near Range programs SITRANS LR560 to ignore the zone in front of the antenna. The default blanking distance is 27.8 cm (0.91 ft) from the sensor reference point. Near Range allows you to increase the blanking value from its factory default. But SHAPER MODE (2.8.4) (Page 127) is generally recommended in preference to extending the blanking...
4 mA equals 0% and 20 mA equals 100%. While the device is in PROGRAM mode, the output remains active and continues to respond to changes in the device. SITRANS LR560 automatically returns to Measurement mode after a period of inactivity in PROGRAM mode. A.4.1 Sensor Mode This parameter controls the input.
Service Required icon, and the text region displays the fault code S: 0 and the text LOE. If two faults are present at the same time, the fault code, error text, and error icon for each fault are displayed alternately. For example, Loss of Echo and Fail-safe. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Upon receiving a reliable echo, the loss of echo condition is aborted, the Service Required icon and error message are cleared, and the reading and mA output return to the current material level. Temperature De-Rating SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Loop voltage is the voltage at the terminals of the power supply (not the voltage at the terminals of the device). ① ④ Loop voltage SITRANS LR560 ② ⑤ Power supply Loop current IL ③ Loop resistance RL SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
A.6.2 Startup behavior ● The device draws less than 3.6 mA at startup. ● Time to first measurement is 60 seconds nominal. A.6.3 Loop voltage versus loop resistance ① Operation - with HART SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
HART Communicator 375 Menu Structure Note HART Communicator 375 is supported by SITRANS LR560 HART. The menu structure is aligned with the menu structure of SIMATIC PDM. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 195
2 Tag 3 Descriptor 4 Message 5 Installation Date 6 Order Number 7 Range Mode 8 Language English German French Spanish Chinese 9 Device Image 2 Step 2 - Application 1 Application Type SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 196
1 Configuration Flag Reset 2 Device Status Icon 3 Operation 1 General 1 Select Analog Output 2 Master Reset 2 Simulation / Test 1 Self Test 2 Loop Test 3 Device Status Icon SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 197
6 Device Status Icon 3 Signal Processing 1 General 1 Range 1 Near Range 2 Far Range 2 Echo Select 1 Algorithm 2 Position Detect 3 Echo Threshold 4 CLEF Range 5 Echo Marker 3 Sampling SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 198
3 Time in Operation 4 Activation of Reminders 5 Reminder 1 before Lifetime (Required) 6 Reminder 2 before Lifetime (Demanded) 7 Snooze for 1 Year 8 Device Status Icon 2 Remaining Sensor Lifetime SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 199
8 Device Status Icon 5 Electronic Temperature 1 Electronics Temperature 2 Lowest Value 3 Highest Value 4 Device Status Icon 6 Wear 1 Time in Operation 2 Poweron Resets 3 Device Status Icon 6 Communication SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 200
3 Secondary 4 SV: Distance 5 Device Status Icon 2 Analog Output 1 Distance Range [%] 2 Analog Output [mA] 3 Device Status Icon 3 Trend View 1 Trend Values 1 Primary 2 Secondary SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
HART Multidrop Mode allows the connection of multiple field devices via HART. Details on the use of Multidrop Mode are outlined in an application guide Working with HART, which can be downloaded from the product page of our website (www.siemens.com/LR560). Go to Support and click on Application Guides.
● Services & Support (http://www.siemens.com/automation/service&support) Personal contact If you have additional questions about the device, please contact your Siemens personal contact ● Partner (http://www.automation.siemens.com/partner) In order to find the contact for your product, select under 'All Products and Branches' the path 'Automation Technology >...
Page 206
3.4. PEAK VALUES 3.4.1. MIN MEAS. VALUE 3.4.2. MAX MEAS. VALUE 3.4.3. MINIMUM PV 3.4.4. MAXIMUM PV 3.4.5. MINIMUM SV 3.4.6. MAXIMUM SV 3.5. ELECT TEMP 3.5.1. MIN. VALUE 3.5.2. MAX. VALUE 3.5.3. INTERN. TEMP SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 207
4.7.2. TIME NEXT SERV. 4.7.3. REMIND. 1 (REQ.) 4.7.4. REMIND. 2 (DEM.) 4.7.5. REMINDER ACTIVATION 4.7.6. SERVICE INTERVAL 4.7.7. MAINT. STAT. 4.7.8. ACK. STATUS 4.7.9. ACK. 4.8. CALIB. SCHEDULE 4.8.1. TIME LAST CALIB. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Process Automation (PROFIBUS) Pressure Equipment Directive safety approval parts per million Primary Variable measured value SELV Safety extra low voltage Secondary Value equivalent value Transducer Block Time Varying Threshold sensitivity threshold Input voltage Output voltage SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 211
List of abbreviations E.1 List of abbreviations SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 213
Echo Confidence describes the quality of an echo. Higher values represent higher quality. Echo Threshold defines the minimum value required for an echo to be accepted as valid and evaluated. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 214
The unit is a Henry. local display interface (LDI) the removable LCD display with push buttons SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...
Page 216
TVT (Time Varying Threshold) a time-varying curve that determines the threshold level above which echoes are determined to be valid. SITRANS LR560 (mA/HART) Operating Instructions, 06/2017, A5E34647946-AD...