hit counter script
Siemens SITRANS LR560 Operating Instructions Manual
Siemens SITRANS LR560 Operating Instructions Manual

Siemens SITRANS LR560 Operating Instructions Manual

Foundation fieldbus radar level transmitter
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Radar Transmitters
SITRANS LR560 (Foundation Fieldbus)
Operating Instructions 10/2010
SITRANS

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS LR560

  • Page 1 Radar Transmitters SITRANS LR560 (Foundation Fieldbus) Operating Instructions 10/2010 SITRANS...
  • Page 2 The user is responsible for all changes and repairs made to the device by the user or the user’s agent. • All new components are to be provided by Siemens Milltronics Process Instruments. • Restrict repair to faulty components only.
  • Page 3: Table Of Contents

    CE Electromagnetic Compatibility (EMC) Conformity ..............2 Industry Canada ............................2 The Manual ...............................3 Application Example ........................3 Technical Support ............................4 Abbreviations and Identifications .....................4 SITRANS LR560 Overview ....................6 Programming ............................6 Local Display Interface (LDI) ......................7 Versions ..............................7 Applications ..............................7 Approvals and Certificates ........................7 Specifications ........................
  • Page 4 Level application example ........................40 Operating via AMS Device Manager ................41 Functions in AMS Device Manager ....................41 Key Features of AMS Device Manager version 9.0............42 Block location of features ......................42 Programming via AMS Device Manager ..................43 Navigating through the parameters ..................43 Pull-down menu access ......................43 Changing parameter settings ....................43 Adding a new device ..........................44...
  • Page 5 Trend ..........................109 Electronics Temperature .................... 109 Peak Values ........................109 Service............................110 Master Reset......................... 110 Remaining Device Lifetime ..................111 Remaining Sensor Lifetime ..................113 Service Schedule ......................115 Calibration Schedule ....................117 Powered Hours......................119 Power-on Resets......................119 Menu Timeout .......................
  • Page 6 Loss of Echo (LOE) Timer (2.3.4.) ....................145 Temperature derating curves ......................145 Appendix E: Communications ..................147 Foundation Fieldbus (FF) Protocol ..................147 Field Communicator 375 (FC375) ....................147 Appendix F: Firmware Revision History ..............148 Glossary ..........................149 Index ..........................153 LCD menu structure ....................... 155...
  • Page 7: Safety Notes

    FCC Conformity US Installations only: Federal Communications Commission (FCC) rules WARNING: Changes or modifications not expressly approved by Siemens Milltronics could void the user’s authority to operate the equipment. Notes: • This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
  • Page 8: Ce Electromagnetic Compatibility (Emc) Conformity

    On the other hand, level probing devices found to interfere with primary licensing operations will be required to be removed at the user’s expense. Page 2 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
  • Page 9: The Manual

    • Please follow the installation and operating procedures for a quick, trouble-free installation and to ensure the maximum accuracy and reliability of your SITRANS LR560. ™ • This manual applies to the SITRANS LR560 (FOUNDATION Fieldbus) only.
  • Page 10: Technical Support

    Technical Support Support is available 24 hours a day. To find your local Siemens Automation Office address, phone number and fax number go www.siemens.com/automation/partner • Click on the tab Contact, select Service, then click Service again to find your product group (+Automation Technology > +Sensor Systems >+Process Instrumentation >...
  • Page 11 PID FB Derivative Function Block parts per million Primary Value measured value Resource Block SELV Safety extra low voltage Secondary Value equivalent value Time Varying Threshold sensitivity threshold Input voltage Output voltage 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 5...
  • Page 12: Sitrans Lr560 Overview

    FF (H1) Link Master. Programming SITRANS LR560 is very easy to install and configure via an optional graphical local display interface (LDI). You can modify the built-in parameters either locally, using the control buttons or the infrared handheld programmer, or from a remote location using one of the following options: •...
  • Page 13: Local Display Interface (Ldi)

    Applications • cement powder, plastic powder/pellets, grain, flour, coal, and other applications • solids bulk storage vessels Approvals and Certificates SITRANS LR560 is available with General Purpose or Hazardous approvals. For details Approvals on page 10. Application LR560 Approval Rating...
  • Page 14: Specifications

    Specifications Notes: • Siemens Milltronics makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. Power Bus powered 9 to 32 V DC, per IEC 61158-2 (Foundation Fieldbus) Current consumed 13.5 mA...
  • Page 15 Display quality will be degraded in temperatures below –20 °C (–4 °F) and above +65°C (+149 °F). Universal flange mates with EN 1092-1 (PN16)/ASME B16.5 (150 lb)/JIS 2220 (10K) bolt hole pattern. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 9...
  • Page 16 R&TTE (Europe), FCC, Industry Canada, C-TICK Maximum and minimum process temperatures are dependent on the process con- nection, O-ring materials, and vessel pressure. Use of the Easy Aimer limits maximum temperature. Page 10 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
  • Page 17 • To estimate the lifetime expectancy, check the nameplate on the back for the serial number. The first six numbers show the production date (mmddyy), for example, serial number 032608101V. Siemens Milltronics Infrared IS (Intrinsically Safe) Hand Programmer for hazardous and all other locations (battery is non-replaceable) • approval FM/CSA Class I, II, III, Div.
  • Page 18: Dimensions

    • Process temperature and pressure capabilities are dependent upon information displayed on the process device markings. Universal Slotted Flange • Refer to on page 16 for bolt hole pattern and dimensions. SITRANS LR560 with stainless steel universal flat flange lid lock device label cable gland 176 mm (6.93")
  • Page 19 SITRANS LR560 with 3" Aimer Flange Notes: • Process temperature and pressure capabilities are dependent upon information displayed on the process device markings. Universal Slotted Flange • Refer to on page 16 for bolt hole pattern and dimensions. lid lock...
  • Page 20 SITRANS LR560 with 4" and 6" Aimer Flange Notes: • Process temperature and pressure capabilities are dependent upon information displayed on the process device markings. Universal Slotted Flange • Refer to on page 16 for bolt hole pattern and dimensions.
  • Page 21 Date of Pressure Test (Year/Month/Day) PROCESS SERIES 25785 Pressure Tag Family Series WETTED NON-METALLIC PEI Sensor Lens Material WETTED METALLICS 304L Process Connection Material(s) WETTED SEALS FKM / VQM Seal Material(s) 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 15...
  • Page 22: Universal Slotted Flange

    0.38" 9.53" 9.45" 0.45" 150 mm (285 mm) (9.65 mm) (242 mm) (240 mm) (11.5 mm) Universal flange mates with EN 1092-1 (PN16)/ASME B16.5 (150 lb)/JIS 2220 (10K) bolt hole pattern. Page 16 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
  • Page 23: Installation

    • Installation shall be performed only by qualified personnel and in accordance with local governing regulations. • SITRANS LR560 is to be used only in the manner outlined in this manual, otherwise protection provided by the device may be impaired.
  • Page 24: Mounting Location

    Use a sunshield if the process temperature instrument will be –40 to +100 °C (–40 to +212 °F) or mounted in direct –40 to +200 °C (–40 to +392 °F) sunlight. (version dependent) Page 18 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML1998KL01...
  • Page 25: Aimer Adjustment

    The LR560 display can be protected by an optional sunshield if the instrument will be mounted in direct sunlight. Aimer Adjustment Note: Aiming will assist in measuring material in the cone. 3" flange 4 and 6" flange 5° 10° 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 19...
  • Page 26: Air Purging System

    LR560 drops down slightly. The enclosure can then be turned freely. Direct SITRANS LR560 so the antenna is pointed at an angle perpendicular to the material surface, if possible. When the desired position is reached, re-tighten the locking ring using the C spanner, and tighten set screws.
  • Page 27: Purge Connection

    The air purge system can clean both dust and moisture off the lens. • It can be used for periodic cleaning. angled holes direct air flow Air pressure in vessel can affect purge operation. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 21...
  • Page 28: Removable Display

    Connecting SITRANS LR560 apart (see on page 23 for instructions). Copy • It can also be used to transfer parameters from one device to another (see Parameters to Display1.3. on page 88.) Page 22 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML1998KL01...
  • Page 29: Wiring

    70 mm (2.75") from the end of the shielded fieldbus cable, and thread the wires through the gland If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 23...
  • Page 30 Connect the wires to the terminals as shown (SITRANS LR560 FF is not polarity- 1) 2) sensitive). cable shield cable gland (or NPT cable entry) instrument shield connection Ground the instrument according to local regulations. Tighten the gland to form a good seal.
  • Page 31: Basic Configuration With Foundation Fieldbus (H1)

    3420 HSE/H1 Gateway FF (H1) FC375 FC375 LR560 FF LR560 FF Configuration via NI-FBUS Linking Device Configurator FF (HSE) PC/laptop controller HSE/H1 Linking Device FF (H1) FC375 FC375 LR560 FF LR560 FF 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 25...
  • Page 32: Wiring Setups For Hazardous Area Installations

    In all cases, check the nameplate on your instrument, and confirm the approval rating. Configuration with Foundation Fieldbus for hazardous areas Configuration via DeltaV Gateway and/or FF (HSE) PC/laptop controller HSE/H1 Gateway Non-hazardous Area FF (H1) Hazardous Area FC375 FC375 LR560 FF LR560 FF Page 26 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 33 Hazardous Area FC375 FC375 LR560 FF LR560 FF Configuration via PCI/PCMCIA Card NI-FBUS Configurator PCI/PCMCIA bus PC/laptop H1 Interface Non-hazardous Area FF (H1) Hazardous Area FC375 FC375 LR560 FF LR560 FF 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 27...
  • Page 34 2. Non-incendive and Dust Ignition Proof wiring (US/ Canada) Device label (FM/CSA) FM/CSA Class 1, Div 2 installation drawing number A5E02795836. can be downloaded from the product page of our website at: www.siemens.com/LR560 under Support. Temperature De-Rating • For power demands see on page 146.
  • Page 35: Instructions Specific To Hazardous Area Installations

    ‘e’ or flameproof ‘d’ . • The supply to the equipment shall be rated for a prospective short-circuit current of not more than 10 kA and shall be protected by a suitably-rated fuse 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 29...
  • Page 36: Local Operation

    • To toggle between Measurement and Program Mode using the handheld programmer, press Mode Power up the device. At initial startup, SITRANS LR560 will not begin measurements and all blocks will be Out of Service until the instrument has been configured .
  • Page 37: The Lcd Display

    Press UP or DOWN arrow to switch. Key functions in Measurement In response to a key press request. For details, see mode on page 32. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 31...
  • Page 38: Handheld Programmer

    • While the device is in PROGRAM mode the output remains active and continues to respond to changes in the device. • SITRANS LR560 automatically returns to Measurement mode after a period of inactivity in PROGRAM mode (between 15 seconds and 10 minutes, depending on the menu level).
  • Page 39 • For Quick Access to parameters via the handheld programmer, press Home , and then enter the menu number. For example, to access parameter Temperature Units (2.3.3.), press 2 . 3 . 3 . 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 33...
  • Page 40 Edit current value mode. The current value is highlighted. Key in a new value. Press RIGHT arrow to accept it. The LCD returns to parameter view and displays the new selection. Page 34 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
  • Page 41: To Configure A Device Via The Local User Interface

    Configure the device via the Quick Start Wizard. Quick Start Wizard via the LDI push buttons • on page 36 Quick Start Wizard via the handheld programmer • on page 36 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 35...
  • Page 42: Quick Start Wizard Via The Ldi Push Buttons

    FINISH in Wizard Complete. • Do not use the Quick Start wizard to modify individual parameters: see instead Parameter Reference on page 86. (Perform customization only after the Quick Start has been completed.) Page 36 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
  • Page 43 Fill Rate/Min (2.3.6.2.)/Empty rate/Min (2.3.6.3.) SLOW 0. 1 m/min (0.32 ft/min) 1.0 m/min (3.28 ft/min) FAST 10.0 m/min (32.8 ft/min) Use a setting just faster than the maximum filling or emptying rate (whichever is greater). 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 37...
  • Page 44 Quick Start is successfully completed.) To transfer Quick Start values to the device and return to Program menu, press DOWN arrow (Finish). Then press LEFT arrow to return to Measurement mode. Page 38 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
  • Page 45: Requesting An Echo Profile

    Read only. The unique address of the device on the network. • In PROGRAM mode, navigate to: Level Meter > Communication (5.) > Device Address (5.2.) to view the device address. • Press Mode to return to Measurement mode. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 39...
  • Page 46: Level Application Example

    Resets Fill Rate and Empty Rate to 0.1 m/minute. Units Low Calibration Point 15.5 Process empty level. High Calibration Point Process full level. Wizard Complete FINISH Save new settings and exit Wizard Page 40 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
  • Page 47: Operating Via Ams Device Manager

    Within each function group, parameters are associated with a particular Function Block. parameter dialog active parameter tab window active function group (highlighted) active function block (LTB) button access to function groups 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 41...
  • Page 48: Key Features Of Ams Device Manager Version 9.0

    Maintenance & Diagnostics (LTB) Maintenance & Diagnostics (RESOURCE) RESOURCE Security (RESOURCE) RESOURCE Alarms & Errors (LTB) Device Diagnostics Alarms & Errors (RESOURCE) RESOURCE Process Variables (Level Transducer Block - LTB) Process Variables Page 42 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 49: Programming Via Ams Device Manager

    The parameter field will display in yellow until the value has been written to the device. Click OK if you wish to update all parameters and exit to Device Connection View. Click CANCEL to exit without saving changes. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 43...
  • Page 50: Adding A New Device

    Note: Check the product page of our website at: www.siemens.com/LR560, under Support > Software Downloads, for the latest version of EDD: SITRANS LR560 FF - Foundation Fieldbus - AMS V9.0. Check that you have the latest version of the EDD for AMS Device Manager that matches the firmware revision of your device.
  • Page 51 AMS. From the menu bar, open the pull-down menu Actions – Scan Device. If you are adding a new device, configure the device via the Quick Start wizard. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 45...
  • Page 52: Configuring A New Device

    Quick Start step. • If you modify a parameter in any step, the Apply button is activated. Click Apply to write changes to the device. Changes to parameters that affect the block output. Page 46 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 53 Click Step 2 - Application. If you wish to accept the default values, go directly to Step 3. Or select a different vessel type (steel or concrete). [This changes the setting for Position Detect (2.4.5.2.) to Rising Edge.] Then click Apply. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 47...
  • Page 54 Click Step 4 - Summary. Check parameter settings. Return to individual steps if further changes are necessary. The Quick Start is now complete. Put Resource Block into Automatic Mode (see Changing Block Modes on page 49.) Page 48 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 55: Changing Block Modes

    Navigate to Configure/Setup > LTB and click Identification to open the dialog window for access to: Identification: • Read only. Description for the associated block: device tag prefixed by block type. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 49...
  • Page 56 Defines the modes that are allowed. The permitted mode is configured based on application requirements. • Normal Mode This is the mode that the block should be set to during normal operating conditions. Page 50 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 57: Level Transducer Block Parameters

    2) If you select Fixed value, enter a Simulation Value and click Apply. 3) Or select Ramp, enter the RAMP start, end, number of steps, and step length, and click Apply. 4) After simulation is complete, set Simulation to OFF and click Apply. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 51...
  • Page 58 High Level Point • Level Offset Rate Average amount (2.8.3.) Note: Selecting SLOW Response Rate changes setting for 0.9. • Response Rate • Fill Rate per Minute • Empty Rate per Minute Page 52 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 59 Echo Marker Sampling • Echo Lock • Sampling Up • Sampling Down • Echo Lock Window Echo Quality • Confidence • Echo Strength Filtering • Narrow Echo Filter • Reform Echo 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 53...
  • Page 60 Allows you to modify breakpoints under the TVT Shaper tabs, and view Manual TVT-Curve. Turn Shaper Mode On and turn Auto False Echo Suppression Off. Click the appropriate TVT Shaper tab and modify breakpoints as desired. Click Apply. Page 54 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 61 Note: Put LTB Block into OOS Mode before changing settings, then back into AUTO mode to display TVT. Displays the effects of the TVT shaper modifications. (Shaper Mode must be On.) Navigate to Configure/Setup > LTB > Setup > Signal Processing > Manual TVT-Curve. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 55...
  • Page 62 Click Sensor Lifetime tab for access to: • Lifetime (Expected) • Time in Operation • Remaining Lifetime • Activation of Reminders • Reminder 1 before Lifetime (Required) • Reminder 2 before Lifetime (Demanded) Page 56 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 63 Reminder 1 before Lifetime (Required) • Reminder 2 before Lifetime (Demanded) • Click on Service Performed to reset Time Since Last Service to 0 hours. • Click Apply to write changes to the device. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 57...
  • Page 64 Minimum Value • Maximum Value Communication (LTB) Navigate to Configure/Setup > LTB > Communication for access to: Communication: • Static Revision No. [see Static Revision Number (2.5. 1 .) on page 103] Page 58 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 65: Configure/Setup (Liquid Crystal Display Block-Lcd)

    Select Target Mode Out of Service and deselect Automatic. Click Apply. Setup (LCD) Navigate to Configure/Setup > LCD > Setup for access to: Local Display • Language • LCD Contrast • LCD Backlight (continued on next page) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 59...
  • Page 66 Communication (LCD) Navigate to Configure/Setup > LCD > Communication for access to: Communication: • Static Revision No. [see Static Revision Number (2.5. 1 .) on page 103] Page 60 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 67: Configure/Setup (Diagnostic Transducer Block-Diag)

    The user entered date on which the device was installed in the system. • Strategy Used to identify grouping of blocks. • Plant Unit The identification number of the plant unit. For example, can be used in the host for sorting alarms. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 61...
  • Page 68 Quick Start Wizard via AMS Device Manager on page 46 Start steps (see Operation (RESOURCE) Navigate to Configure/Setup > RESOURCE > Operation. Click on Block Modes to open the dialog window for access to: Block Modes Page 62 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 69 . This could cause a temporary loss of communications. (continued on next page) FF Object Dictionary reset completes with an automatic power cycle. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 63...
  • Page 70 Functional reset does not reset these parameters. FF Object Dictionary reset completes with an automatic power cycle. Foundation Fieldbus for Level instruments (7ML19985MP01) See the manual Data Transmission, for more details. Page 64 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 71 Open the window Remaining Device Lifetime After modifying values/units as required, click Apply to accept the change. Click on Snooze for 1 Year to add a year to the Total Expected Device Life 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 65...
  • Page 72 Reminder 2 before Calibration (Demanded) Click on Calibration Performed to reset Time Since Last Calibration to 0 hours. Click Apply to accept the change. Wear (read only) • Powered Days (read only) • Power-on resets Page 66 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 73 Security (RESOURCE) Navigate to Configure/Setup > RESOURCE > Security to access: Security • Write Protection Security (continued) [see on page 68] Password Protection See also on page 74. (continued on next page) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 67...
  • Page 74: Device Diagnostics (Level Transducer Block - Ltb)

    Device Fault State • Block Configuration • Link Configuration • Other Maintenance • Maintenance Required • Maintenance Demanded Information • Simulation Active • Local Override • Power Up • Out of Service Page 68 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 75 AMS. The maintenance alarm will cause an FF block alert, and the block alert can only be acknowledged via a remote host such as NI-FBUS-Configurator or AMS Device Manager (as in step 3 above). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 69...
  • Page 76: Device Diagnostics (Level Control Device Block - Lcd)

    Alarms & Errors (RESOURCE) Navigate to Device Diagnostics > RESOURCE > Alarms & Errors. Block Error Click Block Error tab to read: Failures • Input Failure • Output Failure • Memory Failure Failures Page 70 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 77 Discrete Alarm • Block Alarm Unacknowledged • Discrete Alarm Unacknowledged • Block Alarm Unacknowledged Unreported • Discrete Alarm Unreported • Block Alarm Unreported Disabled • Write Alarm Disabled • Block Alarm Disabled 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 71...
  • Page 78 • Device Lifetime Reminder 2 • Memory RAM • Calibration Schedule Reminder 1 • Memory EEPROM • Calibration Schedule Reminder 2 • Memory EEPROM Flags • Internal Error • Memory Flash • Invalid Loader Page 72 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 79 Configure/Setup > LTB > Setup > Sensor. Trend View Click Trend View tab to view: • Trend Values • Trend View The primary variable and the channel 1 output from the transducer block. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 73...
  • Page 80: Password Protection

    The Add User Wizard dialog allows you to: • select a user type, Standard User (AMS Device Manager) or Window User • enter the username and password, and set permissions • edit existing users Page 74 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 81: Ams Menu Structure

    Sensor Sensor (tab) General Unit 2.3.1 Level Units 2.3.2 Temperature Unit 2.3.3 Loss of Echo Timer 2.3.4 Calibration 2.3.5 Low Cal. Point 2.3.5. 1 High Cal. Point 2.3.5.2 Sensor Offset 2.3.5.3 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 75...
  • Page 82 Auto False Echo Suppression 2.4.8. 1 Auto False Echo Suppression 2.4.8.2 Range Hover Level 2.4.8.3 Shaper Mode 2.4.8.4 TVT Shaper 1 (tab) 2.4.9 Breakpoints 1-40 TVT Shaper 2 (tab) Breakpoints 41 - 80 Page 76 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 83 Reminder 1 before Service (Required) 4.4.5 Reminder 2 before Service (Demanded) 4.4.6 Electronics Temperature Electronics Temperature (tab) Electronics Temperature Minimum Value 3.4.1 Maximum Value 3.4.2 OMMUNICATION Communication Communication (tab) Static Revision No. 2.5.1 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 77...
  • Page 84 Static Revision No. 2.5.1 IAGNOSTIC RANSDUCER LOCK DENTIFICATION Identification Identification (tab) Descriptor 2.1.2 Transducer Block Type Strategy Plant Unit PERATION Block Modes Block Modes (tab) Actual Mode Target Mode Permitted Mode Page 78 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 85 Quick Start Step 1 - Identification Step 2 - Application Step 3 - Ranges Step 4 - Summary PERATION Block Modes Block Modes (tab) Actual Mode Target Mode Permitted Mode Normal Mode 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 79...
  • Page 86 Wear (tab) Powered Days Poweron Resets OMMUNICATION Communication Communication (tab) Manufacturer Device Type Device Revision DD Revision ITK Version Static Revision No. 2.5.1 ECURITY Security Security (tab) Write Protection Write Protection 6.2.1 Page 80 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 87 Extended Diagnostics (tab) Detailed Error Info Loss of Echo No Tech Power Sensor Lifetime Reminder 1 Sensor Lifetime Reminder 2 Service Schedule Reminder 1 Service Schedule Reminder 2 LTB Scale Internal Temp Sensor 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 81...
  • Page 88 Block Configuration Link Configuration Other Maintenance Maintenance Required Maintenance Demanded Information Simulation Active Local Override Power Up Out Of Service XD Error Transducer Error Block Alarm Block Alarm (tab) Unacknowledged Alarm State Page 82 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 89 Out Of Service XD Error Transducer Error Block Alarm Block Alarm (tab) Unacknowledged Alarm State Subcode Value ESOURCE LOCK & E LARMS RRORS Block Error Block Error (tab) Failures Input Failure Output Failure 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 83...
  • Page 90 Write Alarm (tab) Unacknowledged Alarm State Subcode Value Alarm Summary Alarm Summary (tab) Current Discrete Alarm Block Alarm Unacknowledged Discrete Alarm Unacknowledged Block Alarm Unacknowledged Unreported Discrete Alarm Unreported Block Alarm Unreported Page 84 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 91 Process Variables (tab) Primary Variable 2.7.1 Value Trend View (tab) Trend Values Value Echo Profile Echo Profile (tab) Echo Profile Parameters Level Measurement 2.7.2 Distance 2.7.3 Measurement Confidence 2.4.7.1 Near Range 2.4.1 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 85...
  • Page 92: Parameter Reference

    Quick Start Wizard via the LDI push buttons on page 36 • Quick Start Wizard via the handheld programmer on page 36 • Quick Start Wizard via AMS Device Manager on page 46 • Page 86 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 93: Afes (Auto False Echo Suppression) Wizard

    If you have a vessel with known obstructions, we recommend using AFES to prevent false echo detection. This feature can also be used if SITRANS LR560 displays a false high level, or the reading is fluctuating between the correct level and a false high level.
  • Page 94: Copy Parameters To Display

    Transfers firmware from a device to the local display interface. Press RIGHT arrow to Edit. Press DOWN arrow to select Start and RIGHT arrow to begin the transfer. SW UPLOAD is displayed, then the device returns to Measurement mode. Page 88 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 95: Copy Firmware From Display

    SW DOWNLOAD is displayed at the beginning of the transfer. This is followed first by a blank screen (for approximately 2 minutes), then by a progress indicator, and then by the Siemens logo with the LOE icon. When the transfer is complete,the device returns to Measurement mode.
  • Page 96: Device

    LR560. 2.2.3. Loader Revision Read only. Revision corresponding to the software used to update the LR560. 2.2.4. Manufacture Date Read only. The date of manufacture of the SITRANS LR560. (Local display format: YY-MM-DD hh:mm:ss) 2.3. Sensor 2.3.1. Unit Sensor measurement unit.
  • Page 97 The point on the sensor from which measurements are referenced (see LR560 with stainless steel universal flat flange SITRANS LR560 with on page 12 and 3" Aimer Flange on page 13). See Minimum Sensor Value (2.4.3.) for an illustration. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 91...
  • Page 98 Empty rate/Min (2.3.6.3.) slow 0.1 m/min (0.32 ft/min) medium 1.0 m/min (3.28 ft/min) fast 10.0 m/min (32.8 ft/min) Use a setting just faster than the maximum filling or emptying rate (whichever is faster). Page 92 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 99 Defines the maximum rate at which the reported sensor value is allowed to increase. Allows you to adjust the SITRANS LR560 response to increases in the actual material level. Fill Rate is automatically updated whenever Response Rate (2.3.6.1.) is altered.
  • Page 100: Signal Processing

    Use this feature if the measured surface can drop below the Low Cal. Point in Far Range (2.4.2.) normal operation. For more detail see on page 143. SITRANS LR560 with stainless steel universal flat flange on page 12. Page 94 SITRANS LR560 (FF) – INSTRUCTION MANUAL...
  • Page 101 Selects the algorithm to be applied to the echo profile to extract the true echo. Area Largest First Echo Area Largest Echo First Echo Area Largest Area First Options Largest First Best of First or Largest echo Best Largest Best First LAST True First 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 95...
  • Page 102 Range: 0 to 99 Values Default: 5 Loss of Echo (LOE) Timer (2.3.4.) Related Parameters Use this feature when an incorrect material level is reported. Page 96 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 103 Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo. This value is preset to 70%. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 97...
  • Page 104 Range: 1 to 50 Values Default: 2 Echo Lock (2.4.6.1.) If Echo Lock set to any value Related other than its default (2), then Down Sampling parameters default = 5. Page 98 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 105 Displays the absolute strength (in dB above 1 μV rms) of the echo selected as the measurement echo. –20 to 99 Values (view only) See Echo Lock (2.4.6.1.) on page 118 for more detail. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 99...
  • Page 106 Subtract 0.5 m (20") from this distance, and enter the resulting value in Auto False Echo Suppression Range. Before Auto False Echo Suppression TVT Hover false echo Level material level default TVT echo marker Page 100 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 107 Range: 0 to 100% Values Default: 40% When SITRANS LR560 is located in the center of the vessel, the TVT hover level may be lowered to increase the confidence level of the largest echo. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL...
  • Page 108 2.4.9.4. Shaper 28-36 2.4.9.5. Shaper 37-45 2.4.9.6. Shaper 46-54 2.4.9.7. Shaper 55-63 2.4.9.8. Shaper 64-72 2.4.9.9. Shaper 73-81 2.4.9.10. Shaper 82-90 2.4.9.11. Shaper 91-99 2.4.9.12. Shaper 100-108 2.4.9.13. Shaper 109-117 2.4.9.14. Shaper 118-120 Page 102 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 109: Aifb 1

    Note: Ensure that Mode is returned to AUTO when simulation or maintenance are completed. Used to request an operating mode from the Analog Input Function Block. It allows you to put SITRANS LR560 into Manual mode (used in conjunction with Simulation) or Out-of-Service mode for maintenance purposes. Setting...
  • Page 110 Value Scale) in Level Units. Process Value Scale normalizes the input value to a customer-defined range. Range: -999999 to 999999 Values Default: 100 % Provides Output values (Out) to AIFB 1 or AIFB 2 Output Scale Page 104 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 111 Engineering unit to be displayed with the output value m, cm, mm, ft, in, %, Not Used, Unknown, Special Options 2.5.5.4. Decimal Point Read only. The number of digits to display after the decimal point (fixed to two). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 105...
  • Page 112 Range: 0 to 50% Options Default: 0.50% Enter a value for the hysteresis here, to be used for all warnings and alarms. The units are always %. Page 106 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 113: Aifb 2

    For example, to filter out a spike with 500 mm width, enter 6 or 7 (the closest integer product of 500 x 0.013). When a value is keyed in, the nearest acceptable value is entered. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 107...
  • Page 114: Diagnostics

    To request a profile via the handheld programmer or local control buttons: Requesting an Echo Profile In PROGRAM mode, navigate to Echo Profile (3.1.). (See on page 39 for more details.) Page 108 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 115: Fault Reset

    3.5.1. Minimum Measured Value The minimum recorded Sensor value, reported in units defined in Unit (2.3.1.). 3.5.2. Maximum Measured Value The maximum recorded Sensor value, reported in units defined in Unit (2.3.1.). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 109...
  • Page 116: Service

    After a master reset is performed, the device will stop measuring, the Resource and Level Transducer Blocks will go to Out of Service, and the LCD will display the Quick Start Wizard until the device is configured. Page 110 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 117: Remaining Device Lifetime

    Default: 10.00 years 4.2.2. Time in Operation Read only. The amount of time the device has been operating. 4.2.3. Remaining Lifetime Read only. Lifetime Expected (4.2.1.) less Time in Operation (4.2.2.). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 111...
  • Page 118 To display the level of maintenance reminder that is active in AMS Device Device Manager see Extended Diagnostics (RESOURCE) on page 72 under Diagnostics (Resource Block - RESOURCE) 4.2.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 112 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 119: Remaining Sensor Lifetime

    The amount of time the sensor has been operating. Can be reset to zero after performing a service or replacing the sensor. To reset to zero: • Via the handheld programmer, manually reset Time in Operation (4.3.2.) to zero. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 113...
  • Page 120: Remaining Lifetime

    To display the level of maintenance reminder in AMS Device Manager see Device Diagnostics (Level Extended Diagnostics (LTB) on page 70 under Transducer Block - LTB) 4.3.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 114 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 121: Service Schedule

    Time elapsed since last service. Can be reset to zero after performing a service. To reset to zero: • Via the handheld programmer, manually reset Time Last Serviced (4.4.2.) to zero. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 115...
  • Page 122 To display the level of maintenance reminder in AMS Device Manager see Device Diagnostics (Level Extended Diagnostics (LTB) on page 70 under Transducer Block - LTB) 4.4.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 116 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 123: Calibration Schedule

    To reset to zero: • Via the handheld programmer, manually reset Time Last Calibrated (4.5.2.) to zero. 4.5.3. Time Next Calibrated Read only. Calibration Interval (4.5.1.) less Time Last Calibrated (4.5.2.). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 117...
  • Page 124 To display the level of maintenance reminder that is active in AMS Device Device Manager see Extended Diagnostics (RESOURCE) on page 72 under Diagnostics (Resource Block - RESOURCE) 4.5.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 118 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 125: Powered Hours

    Values Default: 8 temperature. Adjust the value to improve visibility in different temperatures and light conditions. Change the value in small steps to ensure you can continue to read the display. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 119...
  • Page 126: Secondary Value

    5.1. Tag The user-defined description for the device. To access this parameter via AMS Device Manager see Identification under Identification (RESOURCE) on page 61. Parameter view Program mode on page 31, under Page 120 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 127: Device Address

    16-247 5.3. Manufacturer Device manufacturer: Siemens. 5.4. Device Type Identification Hexadecimal integer defined by Siemens to uniquely identify each product with manufacturer’s Id. (LR560 FF device= 00D7.) 5.5. Device Revision Manufacturer’s revision number associated with this device.
  • Page 128: Local Access

    7. Language Selects the language to be used on the LCD. * ENGLISH DEUTSCH FRANÇAIS Options ESPAÑOL 简体中文 Local Display To access this parameter via AMS Device Manager, see on page 59. Page 122 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 129: Appendix A: Alphabetical Parameter List

    Copy Parameters to Display (1.3.) Decimal Point (2.5.4.4.) Decimal Point (2.5.5.4.) Demo Mode (4.13.) Descriptor (2.1.2.) Device (2.2.) Device Address (5.2.) Device Revision (5.5.) Device Type Identification (5.4.) Diagnostics (3.) Display (2.5.7.) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 123...
  • Page 130 Local Operation (6.2.2.) Loss of Echo (LOE) Timer (2.3.4.) Low Calibration Point (2.3.5. 1 .) Low Level Point (2.3.5.4.) Low Limit Alarm (2.5.6.4.) Low Limit Warning (2.5.6.3.) Lower Value (2.5.4.1.) Lower Value (2.5.5.1.) Page 124 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 131 Remaining Lifetime (4.3.3.) Remaining Sensor Lifetime (4.3.) Reminder 1 (Required) (4.2.5.) Reminder 1 (Required) (4.3.5.) Reminder 1 (Required) (4.4.5.) Reminder 1 (Required) (4.5.5.) Reminder 2 (Demanded) (4.2.6.) Reminder 2 (Demanded) (4.3.6.) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 125...
  • Page 132 Shaper 100-108 (2.4.9. 1 2.) Shaper 109-117 (2.4.9.13.) Shaper 118-120 (2.4.9.14.) Shaper Mode (2.4.8.4.) Signal Processing (2.4.) Simulate Enable (4. 1 2.) Static Revision Number (2.5.1.) Tag (2.1.1.) Tag (5.1.) Temperature Units (2.3.3.) Page 126 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 133 Time Next Serviced (4.4.3.) Trend (3.3.) TVT (Auto False Echo Suppression) Setup (2.4.8.) TVT Shaper (2.4.9.) Unit (2.3. 1 .) Unit (2.5.4.3.) Unit (2.5.5.3.) Upper Value (2.5.4.2.) Upper Value (2.5.5.2.) Write Protection (6.2.1.) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 127...
  • Page 134: Appendix B: Troubleshooting

    • Check the network to ensure the controller is com- municating with the LR560. Only the AIFB 1 and AIFB 2 • Ensure Local Operation (6.2.2.) on page 122 is enabled parameters are displayed via Page 128 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 135: Device Status Icons

    • Ensure block is set to Out of Service (O/S) ters, such as low calibration point If you continue to experience problems, go to our website at: http://www.siemens.com/LR560, and check the FAQs for SITRANS LR560, or contact your Siemens Milltronics representative. Device Status Icons Priority...
  • Page 136: General Fault Codes

    • If fault persists, contact your local Siemens representative. S: 2 Unable to collect profile because of a Repair required. Contact your local power condition that is outside the Siemens representative. operating range of the device. Page 130 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 137 (2.3.5.1.) and High Calibration Point • Ensure settings for High Calibration (2.3.5.2.) are the same. Point and Low Calibration Point are different. S: 11 Internal temperature sensor failure. Repair required: contact your local Siemens representative. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 131...
  • Page 138 Repair required: contact your local memory error. Siemens representative. S: 29 EEPROM damaged. Repair required: contact your local Siemens representative. S: 30 EEPROM corrupt. Reset power. If fault persists, contact your local Siemens representative. Page 132 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 139 NOTE: Fault text and icon appear only Siemens representative. on LCD. S:66 to Device error. Repair required. Contact your local S:83 NOTE: Fault text and icons appear only Siemens representative. on LCD. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 133...
  • Page 140: Operation Troubleshooting

    • ensure Auto Suppression Range is set correctly Display shows Antenna malfunction: • check temperature in Maximum • temperature too high Value (3.4.2.) S: 0 LOE • physical damage • relocate Page 134 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 141 • ensure Algorithm (2.4.5. 1 .) is set to tF (trueFirst echo) • vessel near empty and • set Position Detect (2.4.5.2.) to Hybrid low dK material • check the setting for CLEF Range (2.4.5.4.) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 135...
  • Page 142: Appendix C: Maintenance

    Appendix C: Maintenance SITRANS LR560 requires no maintenance or cleaning under normal operating conditions. Under severe operating conditions, the antenna may require periodic cleaning. If cleaning becomes necessary: • Note the antenna material and the process medium, and select a cleaning solution that will not react adversely with either.
  • Page 143: Appendix D: Technical Reference

    Reference on page 86 for a complete list of parameters. Principles of Operation SITRANS LR560 is a 2-wire 78 GHz FMCW radar level transmitter for continuous monitoring of solids in vessels . Radar level measurement uses the time of flight principle to determine distance to a material surface.
  • Page 144: Echo Processing

    Echo Processing Process Intelligence The signal processing technology embedded in Siemens radar level devices is known as Process Intelligence. Process intelligence provides high measurement reliability regardless of the dynamically changing conditions within the vessel being monitored. The embedded Process Intelligence dynamically adjusts to the constantly changing material surfaces within these vessels.
  • Page 145 The CLEF algorithm enables the device to report the level correctly. Example: CLEF off: Position set to Hybrid on page 140 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 139...
  • Page 146 Example: CLEF enabled Vessel height: 5 m; Far Range 5.5 m; CLEF range set to 1 m default TVT vessel material bottom echo echo selected echo marker Page 140 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 147 In radar applications, two measurement verification options are used: Lock Off SITRANS LR560 responds immediately to a new selected echo (within the restrictions set by the Maximum Fill / Empty Rate), but measurement reliability is affected. Material Agitator A new measurement outside the Echo Lock Window must meet the sampling criteria before the window will move to include it.
  • Page 148 Example before Auto False Echo Suppression sensor reference point High Cal. Pt. obstruction at 1.9 m default false material level at echo 3.9 m material echo Page 142 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 149: Measurement Range

    Measurement Range Near Range (2.4.1.) Near Range programs SITRANS LR560 to ignore the zone in front of the antenna. The default blanking distance is 27.8 cm (0.91 ft) from the sensor reference point. Near Range allows you to increase the blanking value from its factory default. But Auto False Echo Suppression (2.4.8.1.) is generally recommended in preference to extending...
  • Page 150: Measurement Response

    Confidence (2.4.7.1.) describes the quality of an echo. Higher values represent higher quality. Echo Threshold (2.4.5.3.) defines the minimum confidence value required for an echo to be accepted as valid and evaluated. Page 144 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 151: Loss Of Echo (Loe) Timer (2.3.4.)

    –40 °C to 80 °C (–40 °F to 176 °F) process temperature: –40 to +100 °C (–40 to +212 °F) or –40 to +200 °C (–40 to +392 °F) depending on the version 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 145...
  • Page 152 Temperature De-Rating high temperature standard version version Process Temperature (°C) Page 146 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
  • Page 153: Appendix E: Communications

    Appendix E: Communications Foundation Fieldbus (FF) Protocol SITRANS LR560 (FF) is a class 3IPS, 32L FF (H1) device. It supports publish and subscribe functionality as well as Backup LAS functionality. The full range of SITRANS LR560 functions is available only over an FF network.
  • Page 154: Appendix F: Firmware Revision History

    Appendix F: Firmware Revision History Firmware Date Changes Rev. Rev. (EDD/MM/YYYY) 1.00.00 1.00.00 21 June, 2010 • Initial release. Page 148 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 155: Glossary

    Echoes are frequently measured in decibels relative to the directly transmitted signal. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 149...
  • Page 156 Distance is determined by the return transit time. Page 150 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 157 TVT (time varying threshold): a time-varying curve that determines the threshold level above which echoes are determined to be valid. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 151...
  • Page 158 Notes Page 152 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 159: Index

    34 nameplate key functions 35 Hazardous (ATEX/IECEx/C-TICK) 28 enable/disable remote operation 121 Hazardous (FM/CSA) 28 Near Range factory defaults 110 explanation 143 Far Range explanation 143 operating principles 137 function keys 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 153...
  • Page 160 4 synchronize parameters scan device via AMS 43 temperature de-Rating curves 145 troubleshooting operation 134 Wear Powered Hours, Power-on Resets 119 wiring cables 23 hazardous areas 26 Write Protection 122 Page 154 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 161: Lcd Menu Structure

    LCD Menu Structure SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 155 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 162 2.5.6.4 LO LIMIT ALARM 2.4.2 FAR RANGE 2.5.6.5 LIMIT HYSTERESI.. 2.4.3 MIN SENSOR VAL 2.5.7 DISPLAY 2.4.4 MAX SENSOR VAL 2.5.7. 1 FILTER TIME CONS.. Page 156 SITRANS LR560 (FF) – INSTRUCTION MANUAL SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 163 7. LANGUAGE 4.2.8 ACK STATUS 4.2.9 ACK 4.3 REMAIN SENS LIFE 4.3. 1 LIFETIME EXPECT.. 4.3.2 TIME IN OPER. 4.3.3 REMAIN. LIFETIM.. 4.3.4 REMINDER ACTIV. SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 157 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 164 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 158 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
  • Page 165 Siemens Milltronics Process Instruments Inc. Subject to change without prior notice Industry Automation (IA) 7ML19985LY01 Rev. 1.0-02 1954 Technology Drive P.O. Box 4225 *7ml19985LY01* © Siemens Milltronics Process Instruments Inc. 2010 Peterborough, ON Canada K9J 7B1 Printed in Canada email: techpubs.smpi@siemens.com www.siemens.com/processautomation...

Table of Contents