The user is responsible for all changes and repairs made to the device by the user or the user’s agent. • All new components are to be provided by Siemens Milltronics Process Instruments. • Restrict repair to faulty components only.
CE Electromagnetic Compatibility (EMC) Conformity ..............2 Industry Canada ............................2 The Manual ...............................3 Application Example ........................3 Technical Support ............................4 Abbreviations and Identifications .....................4 SITRANS LR560 Overview ....................6 Programming ............................6 Local Display Interface (LDI) ......................7 Versions ..............................7 Applications ..............................7 Approvals and Certificates ........................7 Specifications ........................
Page 4
Level application example ........................40 Operating via AMS Device Manager ................41 Functions in AMS Device Manager ....................41 Key Features of AMS Device Manager version 9.0............42 Block location of features ......................42 Programming via AMS Device Manager ..................43 Navigating through the parameters ..................43 Pull-down menu access ......................43 Changing parameter settings ....................43 Adding a new device ..........................44...
FCC Conformity US Installations only: Federal Communications Commission (FCC) rules WARNING: Changes or modifications not expressly approved by Siemens Milltronics could void the user’s authority to operate the equipment. Notes: • This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
On the other hand, level probing devices found to interfere with primary licensing operations will be required to be removed at the user’s expense. Page 2 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
• Please follow the installation and operating procedures for a quick, trouble-free installation and to ensure the maximum accuracy and reliability of your SITRANS LR560. ™ • This manual applies to the SITRANS LR560 (FOUNDATION Fieldbus) only.
Technical Support Support is available 24 hours a day. To find your local Siemens Automation Office address, phone number and fax number go www.siemens.com/automation/partner • Click on the tab Contact, select Service, then click Service again to find your product group (+Automation Technology > +Sensor Systems >+Process Instrumentation >...
Page 11
PID FB Derivative Function Block parts per million Primary Value measured value Resource Block SELV Safety extra low voltage Secondary Value equivalent value Time Varying Threshold sensitivity threshold Input voltage Output voltage 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 5...
FF (H1) Link Master. Programming SITRANS LR560 is very easy to install and configure via an optional graphical local display interface (LDI). You can modify the built-in parameters either locally, using the control buttons or the infrared handheld programmer, or from a remote location using one of the following options: •...
Applications • cement powder, plastic powder/pellets, grain, flour, coal, and other applications • solids bulk storage vessels Approvals and Certificates SITRANS LR560 is available with General Purpose or Hazardous approvals. For details Approvals on page 10. Application LR560 Approval Rating...
Specifications Notes: • Siemens Milltronics makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. Power Bus powered 9 to 32 V DC, per IEC 61158-2 (Foundation Fieldbus) Current consumed 13.5 mA...
Page 15
Display quality will be degraded in temperatures below –20 °C (–4 °F) and above +65°C (+149 °F). Universal flange mates with EN 1092-1 (PN16)/ASME B16.5 (150 lb)/JIS 2220 (10K) bolt hole pattern. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 9...
Page 16
R&TTE (Europe), FCC, Industry Canada, C-TICK Maximum and minimum process temperatures are dependent on the process con- nection, O-ring materials, and vessel pressure. Use of the Easy Aimer limits maximum temperature. Page 10 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
Page 17
• To estimate the lifetime expectancy, check the nameplate on the back for the serial number. The first six numbers show the production date (mmddyy), for example, serial number 032608101V. Siemens Milltronics Infrared IS (Intrinsically Safe) Hand Programmer for hazardous and all other locations (battery is non-replaceable) • approval FM/CSA Class I, II, III, Div.
• Process temperature and pressure capabilities are dependent upon information displayed on the process device markings. Universal Slotted Flange • Refer to on page 16 for bolt hole pattern and dimensions. SITRANS LR560 with stainless steel universal flat flange lid lock device label cable gland 176 mm (6.93")
Page 19
SITRANS LR560 with 3" Aimer Flange Notes: • Process temperature and pressure capabilities are dependent upon information displayed on the process device markings. Universal Slotted Flange • Refer to on page 16 for bolt hole pattern and dimensions. lid lock...
Page 20
SITRANS LR560 with 4" and 6" Aimer Flange Notes: • Process temperature and pressure capabilities are dependent upon information displayed on the process device markings. Universal Slotted Flange • Refer to on page 16 for bolt hole pattern and dimensions.
Page 21
Date of Pressure Test (Year/Month/Day) PROCESS SERIES 25785 Pressure Tag Family Series WETTED NON-METALLIC PEI Sensor Lens Material WETTED METALLICS 304L Process Connection Material(s) WETTED SEALS FKM / VQM Seal Material(s) 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 15...
• Installation shall be performed only by qualified personnel and in accordance with local governing regulations. • SITRANS LR560 is to be used only in the manner outlined in this manual, otherwise protection provided by the device may be impaired.
Use a sunshield if the process temperature instrument will be –40 to +100 °C (–40 to +212 °F) or mounted in direct –40 to +200 °C (–40 to +392 °F) sunlight. (version dependent) Page 18 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML1998KL01...
The LR560 display can be protected by an optional sunshield if the instrument will be mounted in direct sunlight. Aimer Adjustment Note: Aiming will assist in measuring material in the cone. 3" flange 4 and 6" flange 5° 10° 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 19...
LR560 drops down slightly. The enclosure can then be turned freely. Direct SITRANS LR560 so the antenna is pointed at an angle perpendicular to the material surface, if possible. When the desired position is reached, re-tighten the locking ring using the C spanner, and tighten set screws.
The air purge system can clean both dust and moisture off the lens. • It can be used for periodic cleaning. angled holes direct air flow Air pressure in vessel can affect purge operation. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 21...
Connecting SITRANS LR560 apart (see on page 23 for instructions). Copy • It can also be used to transfer parameters from one device to another (see Parameters to Display1.3. on page 88.) Page 22 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML1998KL01...
70 mm (2.75") from the end of the shielded fieldbus cable, and thread the wires through the gland If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 23...
Page 30
Connect the wires to the terminals as shown (SITRANS LR560 FF is not polarity- 1) 2) sensitive). cable shield cable gland (or NPT cable entry) instrument shield connection Ground the instrument according to local regulations. Tighten the gland to form a good seal.
In all cases, check the nameplate on your instrument, and confirm the approval rating. Configuration with Foundation Fieldbus for hazardous areas Configuration via DeltaV Gateway and/or FF (HSE) PC/laptop controller HSE/H1 Gateway Non-hazardous Area FF (H1) Hazardous Area FC375 FC375 LR560 FF LR560 FF Page 26 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 33
Hazardous Area FC375 FC375 LR560 FF LR560 FF Configuration via PCI/PCMCIA Card NI-FBUS Configurator PCI/PCMCIA bus PC/laptop H1 Interface Non-hazardous Area FF (H1) Hazardous Area FC375 FC375 LR560 FF LR560 FF 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 27...
Page 34
2. Non-incendive and Dust Ignition Proof wiring (US/ Canada) Device label (FM/CSA) FM/CSA Class 1, Div 2 installation drawing number A5E02795836. can be downloaded from the product page of our website at: www.siemens.com/LR560 under Support. Temperature De-Rating • For power demands see on page 146.
‘e’ or flameproof ‘d’ . • The supply to the equipment shall be rated for a prospective short-circuit current of not more than 10 kA and shall be protected by a suitably-rated fuse 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 29...
• To toggle between Measurement and Program Mode using the handheld programmer, press Mode Power up the device. At initial startup, SITRANS LR560 will not begin measurements and all blocks will be Out of Service until the instrument has been configured .
Press UP or DOWN arrow to switch. Key functions in Measurement In response to a key press request. For details, see mode on page 32. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 31...
• While the device is in PROGRAM mode the output remains active and continues to respond to changes in the device. • SITRANS LR560 automatically returns to Measurement mode after a period of inactivity in PROGRAM mode (between 15 seconds and 10 minutes, depending on the menu level).
Page 39
• For Quick Access to parameters via the handheld programmer, press Home , and then enter the menu number. For example, to access parameter Temperature Units (2.3.3.), press 2 . 3 . 3 . 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 33...
Page 40
Edit current value mode. The current value is highlighted. Key in a new value. Press RIGHT arrow to accept it. The LCD returns to parameter view and displays the new selection. Page 34 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
Configure the device via the Quick Start Wizard. Quick Start Wizard via the LDI push buttons • on page 36 Quick Start Wizard via the handheld programmer • on page 36 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 35...
FINISH in Wizard Complete. • Do not use the Quick Start wizard to modify individual parameters: see instead Parameter Reference on page 86. (Perform customization only after the Quick Start has been completed.) Page 36 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
Page 43
Fill Rate/Min (2.3.6.2.)/Empty rate/Min (2.3.6.3.) SLOW 0. 1 m/min (0.32 ft/min) 1.0 m/min (3.28 ft/min) FAST 10.0 m/min (32.8 ft/min) Use a setting just faster than the maximum filling or emptying rate (whichever is greater). 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 37...
Page 44
Quick Start is successfully completed.) To transfer Quick Start values to the device and return to Program menu, press DOWN arrow (Finish). Then press LEFT arrow to return to Measurement mode. Page 38 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
Read only. The unique address of the device on the network. • In PROGRAM mode, navigate to: Level Meter > Communication (5.) > Device Address (5.2.) to view the device address. • Press Mode to return to Measurement mode. 7ML19985LY01 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS Page 39...
Resets Fill Rate and Empty Rate to 0.1 m/minute. Units Low Calibration Point 15.5 Process empty level. High Calibration Point Process full level. Wizard Complete FINISH Save new settings and exit Wizard Page 40 SITRANS LR560 (FF) – OPERATING INSTRUCTIONS 7ML19985LY01...
Within each function group, parameters are associated with a particular Function Block. parameter dialog active parameter tab window active function group (highlighted) active function block (LTB) button access to function groups 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 41...
The parameter field will display in yellow until the value has been written to the device. Click OK if you wish to update all parameters and exit to Device Connection View. Click CANCEL to exit without saving changes. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 43...
Note: Check the product page of our website at: www.siemens.com/LR560, under Support > Software Downloads, for the latest version of EDD: SITRANS LR560 FF - Foundation Fieldbus - AMS V9.0. Check that you have the latest version of the EDD for AMS Device Manager that matches the firmware revision of your device.
Page 51
AMS. From the menu bar, open the pull-down menu Actions – Scan Device. If you are adding a new device, configure the device via the Quick Start wizard. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 45...
Quick Start step. • If you modify a parameter in any step, the Apply button is activated. Click Apply to write changes to the device. Changes to parameters that affect the block output. Page 46 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 53
Click Step 2 - Application. If you wish to accept the default values, go directly to Step 3. Or select a different vessel type (steel or concrete). [This changes the setting for Position Detect (2.4.5.2.) to Rising Edge.] Then click Apply. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 47...
Page 54
Click Step 4 - Summary. Check parameter settings. Return to individual steps if further changes are necessary. The Quick Start is now complete. Put Resource Block into Automatic Mode (see Changing Block Modes on page 49.) Page 48 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Navigate to Configure/Setup > LTB and click Identification to open the dialog window for access to: Identification: • Read only. Description for the associated block: device tag prefixed by block type. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 49...
Page 56
Defines the modes that are allowed. The permitted mode is configured based on application requirements. • Normal Mode This is the mode that the block should be set to during normal operating conditions. Page 50 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
2) If you select Fixed value, enter a Simulation Value and click Apply. 3) Or select Ramp, enter the RAMP start, end, number of steps, and step length, and click Apply. 4) After simulation is complete, set Simulation to OFF and click Apply. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 51...
Page 58
High Level Point • Level Offset Rate Average amount (2.8.3.) Note: Selecting SLOW Response Rate changes setting for 0.9. • Response Rate • Fill Rate per Minute • Empty Rate per Minute Page 52 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 60
Allows you to modify breakpoints under the TVT Shaper tabs, and view Manual TVT-Curve. Turn Shaper Mode On and turn Auto False Echo Suppression Off. Click the appropriate TVT Shaper tab and modify breakpoints as desired. Click Apply. Page 54 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 61
Note: Put LTB Block into OOS Mode before changing settings, then back into AUTO mode to display TVT. Displays the effects of the TVT shaper modifications. (Shaper Mode must be On.) Navigate to Configure/Setup > LTB > Setup > Signal Processing > Manual TVT-Curve. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 55...
Page 62
Click Sensor Lifetime tab for access to: • Lifetime (Expected) • Time in Operation • Remaining Lifetime • Activation of Reminders • Reminder 1 before Lifetime (Required) • Reminder 2 before Lifetime (Demanded) Page 56 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 63
Reminder 1 before Lifetime (Required) • Reminder 2 before Lifetime (Demanded) • Click on Service Performed to reset Time Since Last Service to 0 hours. • Click Apply to write changes to the device. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 57...
Page 64
Minimum Value • Maximum Value Communication (LTB) Navigate to Configure/Setup > LTB > Communication for access to: Communication: • Static Revision No. [see Static Revision Number (2.5. 1 .) on page 103] Page 58 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Select Target Mode Out of Service and deselect Automatic. Click Apply. Setup (LCD) Navigate to Configure/Setup > LCD > Setup for access to: Local Display • Language • LCD Contrast • LCD Backlight (continued on next page) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 59...
Page 66
Communication (LCD) Navigate to Configure/Setup > LCD > Communication for access to: Communication: • Static Revision No. [see Static Revision Number (2.5. 1 .) on page 103] Page 60 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
The user entered date on which the device was installed in the system. • Strategy Used to identify grouping of blocks. • Plant Unit The identification number of the plant unit. For example, can be used in the host for sorting alarms. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 61...
Page 68
Quick Start Wizard via AMS Device Manager on page 46 Start steps (see Operation (RESOURCE) Navigate to Configure/Setup > RESOURCE > Operation. Click on Block Modes to open the dialog window for access to: Block Modes Page 62 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 69
. This could cause a temporary loss of communications. (continued on next page) FF Object Dictionary reset completes with an automatic power cycle. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 63...
Page 70
Functional reset does not reset these parameters. FF Object Dictionary reset completes with an automatic power cycle. Foundation Fieldbus for Level instruments (7ML19985MP01) See the manual Data Transmission, for more details. Page 64 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 71
Open the window Remaining Device Lifetime After modifying values/units as required, click Apply to accept the change. Click on Snooze for 1 Year to add a year to the Total Expected Device Life 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 65...
Page 72
Reminder 2 before Calibration (Demanded) Click on Calibration Performed to reset Time Since Last Calibration to 0 hours. Click Apply to accept the change. Wear (read only) • Powered Days (read only) • Power-on resets Page 66 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 73
Security (RESOURCE) Navigate to Configure/Setup > RESOURCE > Security to access: Security • Write Protection Security (continued) [see on page 68] Password Protection See also on page 74. (continued on next page) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 67...
Device Fault State • Block Configuration • Link Configuration • Other Maintenance • Maintenance Required • Maintenance Demanded Information • Simulation Active • Local Override • Power Up • Out of Service Page 68 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 75
AMS. The maintenance alarm will cause an FF block alert, and the block alert can only be acknowledged via a remote host such as NI-FBUS-Configurator or AMS Device Manager (as in step 3 above). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 69...
The Add User Wizard dialog allows you to: • select a user type, Standard User (AMS Device Manager) or Window User • enter the username and password, and set permissions • edit existing users Page 74 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Sensor Sensor (tab) General Unit 2.3.1 Level Units 2.3.2 Temperature Unit 2.3.3 Loss of Echo Timer 2.3.4 Calibration 2.3.5 Low Cal. Point 2.3.5. 1 High Cal. Point 2.3.5.2 Sensor Offset 2.3.5.3 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 75...
Page 83
Reminder 1 before Service (Required) 4.4.5 Reminder 2 before Service (Demanded) 4.4.6 Electronics Temperature Electronics Temperature (tab) Electronics Temperature Minimum Value 3.4.1 Maximum Value 3.4.2 OMMUNICATION Communication Communication (tab) Static Revision No. 2.5.1 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 77...
Page 86
Wear (tab) Powered Days Poweron Resets OMMUNICATION Communication Communication (tab) Manufacturer Device Type Device Revision DD Revision ITK Version Static Revision No. 2.5.1 ECURITY Security Security (tab) Write Protection Write Protection 6.2.1 Page 80 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 87
Extended Diagnostics (tab) Detailed Error Info Loss of Echo No Tech Power Sensor Lifetime Reminder 1 Sensor Lifetime Reminder 2 Service Schedule Reminder 1 Service Schedule Reminder 2 LTB Scale Internal Temp Sensor 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 81...
Page 88
Block Configuration Link Configuration Other Maintenance Maintenance Required Maintenance Demanded Information Simulation Active Local Override Power Up Out Of Service XD Error Transducer Error Block Alarm Block Alarm (tab) Unacknowledged Alarm State Page 82 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 89
Out Of Service XD Error Transducer Error Block Alarm Block Alarm (tab) Unacknowledged Alarm State Subcode Value ESOURCE LOCK & E LARMS RRORS Block Error Block Error (tab) Failures Input Failure Output Failure 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 83...
If you have a vessel with known obstructions, we recommend using AFES to prevent false echo detection. This feature can also be used if SITRANS LR560 displays a false high level, or the reading is fluctuating between the correct level and a false high level.
Transfers firmware from a device to the local display interface. Press RIGHT arrow to Edit. Press DOWN arrow to select Start and RIGHT arrow to begin the transfer. SW UPLOAD is displayed, then the device returns to Measurement mode. Page 88 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
SW DOWNLOAD is displayed at the beginning of the transfer. This is followed first by a blank screen (for approximately 2 minutes), then by a progress indicator, and then by the Siemens logo with the LOE icon. When the transfer is complete,the device returns to Measurement mode.
LR560. 2.2.3. Loader Revision Read only. Revision corresponding to the software used to update the LR560. 2.2.4. Manufacture Date Read only. The date of manufacture of the SITRANS LR560. (Local display format: YY-MM-DD hh:mm:ss) 2.3. Sensor 2.3.1. Unit Sensor measurement unit.
Page 97
The point on the sensor from which measurements are referenced (see LR560 with stainless steel universal flat flange SITRANS LR560 with on page 12 and 3" Aimer Flange on page 13). See Minimum Sensor Value (2.4.3.) for an illustration. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 91...
Page 98
Empty rate/Min (2.3.6.3.) slow 0.1 m/min (0.32 ft/min) medium 1.0 m/min (3.28 ft/min) fast 10.0 m/min (32.8 ft/min) Use a setting just faster than the maximum filling or emptying rate (whichever is faster). Page 92 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 99
Defines the maximum rate at which the reported sensor value is allowed to increase. Allows you to adjust the SITRANS LR560 response to increases in the actual material level. Fill Rate is automatically updated whenever Response Rate (2.3.6.1.) is altered.
Use this feature if the measured surface can drop below the Low Cal. Point in Far Range (2.4.2.) normal operation. For more detail see on page 143. SITRANS LR560 with stainless steel universal flat flange on page 12. Page 94 SITRANS LR560 (FF) – INSTRUCTION MANUAL...
Page 101
Selects the algorithm to be applied to the echo profile to extract the true echo. Area Largest First Echo Area Largest Echo First Echo Area Largest Area First Options Largest First Best of First or Largest echo Best Largest Best First LAST True First 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 95...
Page 102
Range: 0 to 99 Values Default: 5 Loss of Echo (LOE) Timer (2.3.4.) Related Parameters Use this feature when an incorrect material level is reported. Page 96 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 103
Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo. This value is preset to 70%. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 97...
Page 104
Range: 1 to 50 Values Default: 2 Echo Lock (2.4.6.1.) If Echo Lock set to any value Related other than its default (2), then Down Sampling parameters default = 5. Page 98 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 105
Displays the absolute strength (in dB above 1 μV rms) of the echo selected as the measurement echo. –20 to 99 Values (view only) See Echo Lock (2.4.6.1.) on page 118 for more detail. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 99...
Page 106
Subtract 0.5 m (20") from this distance, and enter the resulting value in Auto False Echo Suppression Range. Before Auto False Echo Suppression TVT Hover false echo Level material level default TVT echo marker Page 100 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 107
Range: 0 to 100% Values Default: 40% When SITRANS LR560 is located in the center of the vessel, the TVT hover level may be lowered to increase the confidence level of the largest echo. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL...
Note: Ensure that Mode is returned to AUTO when simulation or maintenance are completed. Used to request an operating mode from the Analog Input Function Block. It allows you to put SITRANS LR560 into Manual mode (used in conjunction with Simulation) or Out-of-Service mode for maintenance purposes. Setting...
Page 110
Value Scale) in Level Units. Process Value Scale normalizes the input value to a customer-defined range. Range: -999999 to 999999 Values Default: 100 % Provides Output values (Out) to AIFB 1 or AIFB 2 Output Scale Page 104 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 111
Engineering unit to be displayed with the output value m, cm, mm, ft, in, %, Not Used, Unknown, Special Options 2.5.5.4. Decimal Point Read only. The number of digits to display after the decimal point (fixed to two). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 105...
Page 112
Range: 0 to 50% Options Default: 0.50% Enter a value for the hysteresis here, to be used for all warnings and alarms. The units are always %. Page 106 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
For example, to filter out a spike with 500 mm width, enter 6 or 7 (the closest integer product of 500 x 0.013). When a value is keyed in, the nearest acceptable value is entered. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 107...
To request a profile via the handheld programmer or local control buttons: Requesting an Echo Profile In PROGRAM mode, navigate to Echo Profile (3.1.). (See on page 39 for more details.) Page 108 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
3.5.1. Minimum Measured Value The minimum recorded Sensor value, reported in units defined in Unit (2.3.1.). 3.5.2. Maximum Measured Value The maximum recorded Sensor value, reported in units defined in Unit (2.3.1.). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 109...
After a master reset is performed, the device will stop measuring, the Resource and Level Transducer Blocks will go to Out of Service, and the LCD will display the Quick Start Wizard until the device is configured. Page 110 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Default: 10.00 years 4.2.2. Time in Operation Read only. The amount of time the device has been operating. 4.2.3. Remaining Lifetime Read only. Lifetime Expected (4.2.1.) less Time in Operation (4.2.2.). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 111...
Page 118
To display the level of maintenance reminder that is active in AMS Device Device Manager see Extended Diagnostics (RESOURCE) on page 72 under Diagnostics (Resource Block - RESOURCE) 4.2.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 112 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
The amount of time the sensor has been operating. Can be reset to zero after performing a service or replacing the sensor. To reset to zero: • Via the handheld programmer, manually reset Time in Operation (4.3.2.) to zero. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 113...
To display the level of maintenance reminder in AMS Device Manager see Device Diagnostics (Level Extended Diagnostics (LTB) on page 70 under Transducer Block - LTB) 4.3.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 114 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Time elapsed since last service. Can be reset to zero after performing a service. To reset to zero: • Via the handheld programmer, manually reset Time Last Serviced (4.4.2.) to zero. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 115...
Page 122
To display the level of maintenance reminder in AMS Device Manager see Device Diagnostics (Level Extended Diagnostics (LTB) on page 70 under Transducer Block - LTB) 4.4.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 116 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
To reset to zero: • Via the handheld programmer, manually reset Time Last Calibrated (4.5.2.) to zero. 4.5.3. Time Next Calibrated Read only. Calibration Interval (4.5.1.) less Time Last Calibrated (4.5.2.). 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 117...
Page 124
To display the level of maintenance reminder that is active in AMS Device Device Manager see Extended Diagnostics (RESOURCE) on page 72 under Diagnostics (Resource Block - RESOURCE) 4.5.8. Acknowledge Status Indicates which level of maintenance reminder has been acknowledged. Page 118 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Values Default: 8 temperature. Adjust the value to improve visibility in different temperatures and light conditions. Change the value in small steps to ensure you can continue to read the display. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 119...
5.1. Tag The user-defined description for the device. To access this parameter via AMS Device Manager see Identification under Identification (RESOURCE) on page 61. Parameter view Program mode on page 31, under Page 120 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
16-247 5.3. Manufacturer Device manufacturer: Siemens. 5.4. Device Type Identification Hexadecimal integer defined by Siemens to uniquely identify each product with manufacturer’s Id. (LR560 FF device= 00D7.) 5.5. Device Revision Manufacturer’s revision number associated with this device.
7. Language Selects the language to be used on the LCD. * ENGLISH DEUTSCH FRANÇAIS Options ESPAÑOL 简体中文 Local Display To access this parameter via AMS Device Manager, see on page 59. Page 122 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
• Check the network to ensure the controller is com- municating with the LR560. Only the AIFB 1 and AIFB 2 • Ensure Local Operation (6.2.2.) on page 122 is enabled parameters are displayed via Page 128 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
• Ensure block is set to Out of Service (O/S) ters, such as low calibration point If you continue to experience problems, go to our website at: http://www.siemens.com/LR560, and check the FAQs for SITRANS LR560, or contact your Siemens Milltronics representative. Device Status Icons Priority...
• If fault persists, contact your local Siemens representative. S: 2 Unable to collect profile because of a Repair required. Contact your local power condition that is outside the Siemens representative. operating range of the device. Page 130 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
Page 137
(2.3.5.1.) and High Calibration Point • Ensure settings for High Calibration (2.3.5.2.) are the same. Point and Low Calibration Point are different. S: 11 Internal temperature sensor failure. Repair required: contact your local Siemens representative. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 131...
Page 138
Repair required: contact your local memory error. Siemens representative. S: 29 EEPROM damaged. Repair required: contact your local Siemens representative. S: 30 EEPROM corrupt. Reset power. If fault persists, contact your local Siemens representative. Page 132 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
Page 139
NOTE: Fault text and icon appear only Siemens representative. on LCD. S:66 to Device error. Repair required. Contact your local S:83 NOTE: Fault text and icons appear only Siemens representative. on LCD. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 133...
• ensure Auto Suppression Range is set correctly Display shows Antenna malfunction: • check temperature in Maximum • temperature too high Value (3.4.2.) S: 0 LOE • physical damage • relocate Page 134 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
Page 141
• ensure Algorithm (2.4.5. 1 .) is set to tF (trueFirst echo) • vessel near empty and • set Position Detect (2.4.5.2.) to Hybrid low dK material • check the setting for CLEF Range (2.4.5.4.) 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 135...
Appendix C: Maintenance SITRANS LR560 requires no maintenance or cleaning under normal operating conditions. Under severe operating conditions, the antenna may require periodic cleaning. If cleaning becomes necessary: • Note the antenna material and the process medium, and select a cleaning solution that will not react adversely with either.
Reference on page 86 for a complete list of parameters. Principles of Operation SITRANS LR560 is a 2-wire 78 GHz FMCW radar level transmitter for continuous monitoring of solids in vessels . Radar level measurement uses the time of flight principle to determine distance to a material surface.
Echo Processing Process Intelligence The signal processing technology embedded in Siemens radar level devices is known as Process Intelligence. Process intelligence provides high measurement reliability regardless of the dynamically changing conditions within the vessel being monitored. The embedded Process Intelligence dynamically adjusts to the constantly changing material surfaces within these vessels.
Page 145
The CLEF algorithm enables the device to report the level correctly. Example: CLEF off: Position set to Hybrid on page 140 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 139...
Page 146
Example: CLEF enabled Vessel height: 5 m; Far Range 5.5 m; CLEF range set to 1 m default TVT vessel material bottom echo echo selected echo marker Page 140 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
Page 147
In radar applications, two measurement verification options are used: Lock Off SITRANS LR560 responds immediately to a new selected echo (within the restrictions set by the Maximum Fill / Empty Rate), but measurement reliability is affected. Material Agitator A new measurement outside the Echo Lock Window must meet the sampling criteria before the window will move to include it.
Page 148
Example before Auto False Echo Suppression sensor reference point High Cal. Pt. obstruction at 1.9 m default false material level at echo 3.9 m material echo Page 142 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
Measurement Range Near Range (2.4.1.) Near Range programs SITRANS LR560 to ignore the zone in front of the antenna. The default blanking distance is 27.8 cm (0.91 ft) from the sensor reference point. Near Range allows you to increase the blanking value from its factory default. But Auto False Echo Suppression (2.4.8.1.) is generally recommended in preference to extending...
Confidence (2.4.7.1.) describes the quality of an echo. Higher values represent higher quality. Echo Threshold (2.4.5.3.) defines the minimum confidence value required for an echo to be accepted as valid and evaluated. Page 144 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
–40 °C to 80 °C (–40 °F to 176 °F) process temperature: –40 to +100 °C (–40 to +212 °F) or –40 to +200 °C (–40 to +392 °F) depending on the version 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 145...
Page 152
Temperature De-Rating high temperature standard version version Process Temperature (°C) Page 146 SITRANS LR560 (FF)– INSTRUCTION MANUAL 7ML19985LY01...
Appendix E: Communications Foundation Fieldbus (FF) Protocol SITRANS LR560 (FF) is a class 3IPS, 32L FF (H1) device. It supports publish and subscribe functionality as well as Backup LAS functionality. The full range of SITRANS LR560 functions is available only over an FF network.
Echoes are frequently measured in decibels relative to the directly transmitted signal. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 149...
Page 156
Distance is determined by the return transit time. Page 150 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01...
Page 157
TVT (time varying threshold): a time-varying curve that determines the threshold level above which echoes are determined to be valid. 7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 151...