hit counter script

Cisco ASR 907 Hardware Installation Manual page 72

Hide thumbs Also See for ASR 907:
Table of Contents

Advertisement

Installing the Chassis Ground Connection
Before making connections to the Cisco ASR 907 Router, ensure that you disconnect the power at the
Caution
circuit breaker. Otherwise, severe injury to you or damage to the router may occur.
This equipment must be grounded. Never defeat the ground conductor or operate the equipment in the
Warning
absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority
or an electrician if you are uncertain that suitable grounding is available. Statement 1024
Warning
Use copper conductors only. Statement 1025
When installing the unit, the ground connection must always be made first and disconnected last. Statement
Warning
42
This unit is to be installed in a restrictive access location and must be permanently grounded to minimum 6
AWG copper ground wire.
Perform the following procedure to ground the Cisco ASR 907 Router using a 2-hole lug and the corresponding
mounting point. Most carriers require a minimum 6 AWG ground connection. Verify your carrier's requirements
for the ground connection.
Step 1
If your ground wire is insulated, use a wire-stripping tool to strip the ground wire to 0.5 inch ± 0.02 inch (12.7 mm ±0.5
mm) As shown in the figure below.
Figure 22: Stripping a Ground Wire
Cisco ASR 907 Router Hardware Installation Guide
60
Installing the Cisco ASR 907 Router

Advertisement

Table of Contents
loading

Table of Contents