[3] Interlocking Setting that is Made on the MA Remote Controller ..66 [4] Switching to the built-in Thermo on the remote controller ..67 5 Electrical Wiring Diagram ............68 [1] PURY-P200, P250, P300, P350, P400YGM-A ...... 68 [2] PURY-P450, P500, P550, P600, P650YGM-A ...... 69 [3] CMB-P104V-G ................ 70 [4] CMB-P105, 106V-G ..............
Page 3
8 Test Run ..................108 [1] Check Items before Test Run..........108 [2] Test Run Method ..............108 [3] Operating Characteristics and Refrigerant Amount....109 [4] Adjustment and Judgment of Refrigerant Amount ....109 [5] Refrigerant Volume Adjustment Mode Operation ....111 [6] Symptoms that do not Signify Problems ........
Safety Precautions Before installing the unit, be sure to carefully read all of the following safety precautions. These precautions provide important information regarding safety. Be sure to follow them to ensure safety. Symbols used in the text Warning: Failure to follow all instructions may result in serious personal injury or death. Caution: Failure to follow all instructions may result in personal injury or damage to the unit.
Page 5
Warning : Carefully read the labels affixed to the main unit. When installing the unit in a small room, safeguard Do not touch the fins on the heat exchanger with against hypoxia that results from leaked refrigerant bare hands: they are sharp and dangerous. reaching the threshold level.
Caution Store the piping to be used during installation Do not use a charging cylinder. indoors, and keep both ends of the piping sealed • The use of charging cylinder will change the until immediately before brazing. (Keep elbows and composition of the refrigerant and lead to power other joints wrapped in plastic.) loss.
Page 7
Before Installing (Relocating) the Unit or Performing Electric Work Caution Ground the unit. Use breakers and fuses (electrical current breaker, remote switch <switch + Type-B fuse>, molded • Do not connect the grounding on the unit to gas case circuit breaker) with a proper current pipes, water pipes, lightning rods, or the grounding capacity.
Page 8
Before the Test Run Caution Turn on the unit at least 12 hours before the test Do not turn off the power immediately after run. stopping the unit. • Keep the unit on throughout the season. • Allow for at least five minutes before turning off the Turning the unit off during the season may cause unit;...
¡ ¡ Read Before Servicing [1] Items to Be Checked 1. Verify the type of refrigerant used by the unit to be serviced. Refrigerant Type : R410A 2. Check the symptom exhibited by the unit to be serviced. Look in this service handbook for symptoms relating to the refrigerant cycle. 3.
[2] Necessary Tools and Materials Prepare the following tools and materials necessary for installing and servicing the unit. [Necessary tools for use with R410A (Adaptability of tools that are for use with R22 and R407C)] 1. To be used exclusively with R410A (not to be used if used with R22 or R407C) Tools/Materials Notes Gauge Manifold...
[3] Piping Materials Do not use the existing piping! New Piping Existing Piping <Types of copper pipe> Type-O pipes Soft copper pipes (annealed copper pipes) They can be bent easily with hands. Type-1/2H pipes Hard copper pipes (straight pipes) Stronger than type-O pipes of the same radial thickness. •...
Page 12
<Indication of the radial thickness and refrigerant type on the piping materials> “Radial thickness” and “Refrigerant Types” are indicated on the insulation material on the piping materials for the new refrigerant. Indication of the radial thickness (mm) Indication of the refrigerant type Radial thickness Symbols Refrigerant type...
[4] Storage of Piping Material 1. Storage location Store the pipes to be used indoors. (Warehouse at site or owner’s warehouse) Storing them outdoors may cause dirt, waste, or water to infiltrate. 2. Pipe sealing before storage Both ends of the pipes should be sealed until immediately before brazing. Wrap elbows and T’s in plastic bags for storage.
[5] Piping Machining Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections. Reason : 1. The refrigerator oil used for the equipment is highly hygroscopic and may introduce water inside. Notes : •...
[6] Brazing No changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt, etc.) does not enter the refrigerant circuit. Example : Inner state of brazed section When non-oxide brazing was not used When non-oxide brazing was used Items to be strictly observed : 1.
[7] Airtightness Test No changes from the conventional method. Note that a refrigerant leakage detector for R22 or R407C cannot detect R410A leakage. Halide torch R22 or R407C leakage detector Items to be strictly observed : 1. Pressurize the equipment with nitrogen up to the design pressure and then judge the equipment’s airtightness, taking temperature variations into account.
Vacuum Drying Photo 1 15010H Photo 2 14010 Recommended vacuum gauge : ROBINAIR 14010 Thermistor Vacuum Gauge 1. Vacuum pump with reverse-flow check valve (Photo 1) To prevent vacuum pump oil from flowing back into the refrigerant circuit upon turning off the vacuum pump’s power source, use a vacuum pump equipped with a reverse flow check valve.
[10] Changing Refrigerant R410A must be in a liquid state when charging. For a cylinder with a syphon attached For a cylinder without a syphon attached Cylin- Cylin- Cylinder color identification R407C-Gray Charged with liquid refrigerant R410A-Pink Valve Valve Liquid Liquid Reasons : R410A is a pseudo-azeotropic refrigerant (boiling point R32 = -52˚C, R125 = -49˚C) and can roughly be handled...
[12] Characteristics of the Conventional and the New Refrigerants 1. Chemical property As with R22, the new refrigerant (R410A) is low in toxicity and a chemically stable non-flammable refrigerant. However, because the specific gravity of steam is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia.
[13] Notes on Refrigerating Machine Oil 1. Refrigerating Machine Oil in the HFC Refrigerant System HFC type refrigerants use a refrigerating machine oil different from that used in the R22 refrigerant system. Please note that the ester oil sealed in the unit is not the same as commercially available ester oil. Refrigerant Refrigerating machine oil Mineral oil...
™ ™ Restrictions [1] Electrical Work & M-NET control 1. Attention ➀ Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations, and guidance of each electric power company. ➁ Wiring for control (hereinafter referred to as transmission line) shall be (5cm or more) apart from power source wiring so that it is not influenced by electric noise from power source wiring.
[2] Types of Switch Setting and Address Setting 1. Switch setting Type and method of switch setting Switch setting vary depending on the system configuration. Make sure to read “[3] Examples of system connection” before conducting electrical work. Turn off the power before setting the switch. Operating the switch while the unit is being powered will not change the setting, and the unit will not properly function.
Page 23
Setting the power supply selecting connector for the outdoor unit (Factory setting: CN41 is connected.) System Connection with Power supply unit Grouping operation The setting of the power supply Configuration the system for the of different selecting connector controller transmission lines refrigerant systems Single refrigerant system...
Examples of system connection 1. System using MA remote controller (1) In the case of single refrigerant system (Automatic address set-up) Control wiring example Interlocking with ventilation Group Group ✻ 1 TB02 TB15 TB15 M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 A1 B2 A1 B2 A1 B2...
Page 25
Wiring method Address setting method • a. Indoor/outdoor transmission line Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor unit (OC), M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the heat exchanger unit (OS), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor unit.
Page 26
1. System using MA remote controller (2) In the case of single refrigerant system connecting 2 or more LOSSNAY units (Manual address set-up) Control wiring example Interlocking with ventilation Group Group ✻ 1 TB02 TB15 TB15 M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 A1 B2...
Page 27
Wiring method Address setting method • a. Indoor/outdoor transmission line The same as 1. (1) Connection of shielded wire: The same as 1. (1) b. Centralized control transmission line No connection is required. The same as 1. (1) c. MA remote controller wiring For 2-remote controller operation: The same as 1.
Page 28
1. System using MA remote controller (3) In the case of different refrigerant grouping operation Control wiring example Interlocking with ventilation CN41→CN40 Replace Group Group ✻ 1 TB02 TB15 TB15 M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 Connect A1 B2 A1 B2 M1M2 TB02 ✻...
Page 29
Wiring method Address setting method • a. Indoor/outdoor transmission line Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor unit (OC), M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the heat exchanger unit (OS), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor unit.
Page 30
1. System using MA remote controller (4) In the case of connecting system controller to centralized control transmission line Control wiring example Interlocking with ventilation CN41→CN40 Replace SW2-1 OFF→ON Note 1 Group Group ✻ 1 TB02 TB15 TB15 M1M2 M1M2 M1M2 M1M2 M1M2...
Page 31
Wiring method Address setting method • a. Indoor/outdoor transmission line The same as 1. (3) Connection of shielded wire: The same as 1. (1) b. Centralized control transmission line Apply jumper wiring between M1, M2 terminals of centralized control transmission line terminal blocks (TB7) on each OC.
Page 32
1. System using MA remote controller (5) Connecting (multiple) BC controllers in R2 systems (with the system controller connected to the transmission lines for centralized control Control wiring example Numbers in the squares indicate pipe-end connection number. Connection to the BC controller CN41→CN40 Replace SW2-1 OFF→ON Note 1...
Page 33
Wiring method Address setting method • a. Indoor/outdoor transmission line Connect terminals M1 and M2 of the indoor-outdoor transmission line terminal block (TB3) on the outdoor unit (OC) to the terminals M1 and M2 of the indoor-outdoor transmission terminal block (TB02) of the main BC controller (BC) and the sub BC controller (BS) and terminals M1 and M2 of the indoor-outdoor transmission terminal block (TB5) on each indoor unit (IC).
Page 34
1. System using MA remote controller (6) In the case of connecting system controller to indoor/outdoor transmission line (excluding LM adaptor) Control wiring example Interlocking with ventilation CN41→CN40 Replace SW2-1 OFF→ON Group Group ✻ 1 TB02 TB15 TB15 M1M2 M1M2 M1M2 M1M2 M1M2...
Page 35
Wiring method Address setting method • a. Indoor/outdoor transmission line Daisy-chain the M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the outdoor unit (OC), M1 and M2 terminals of the indoor-outdoor transmission terminal block (TB3) on the heat exchanger unit (OS), M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB02) on the BC controller (BC), and M1 and M2 terminals of the indoor-outdoor transmission line terminal block (TB5) on each indoor unit.
Page 36
2. System Using the M-NET Remote Controller (1) System with the system controller connected to the transmission lines for centralized control Control wiring example Interlocking with ventilation CN41→CN40 Replace SW2-1 OFF→ON Group Group Note1 ✻ 1 TB02 TB15 TB15 M1M2 M1M2 M1M2 M1M2...
Page 37
Wiring method Address setting method • The same as 1. (3) a. Indoor/outdoor transmission line Connection of shielded wire: The same as 1. (1) The same as 1. (4) b. Centralized control transmission line The same as 1. (4) Connection of shielded wire: c.
Page 38
3. System where MA remote controller and M-NET remote controller coexist Control wiring example CN41→CN40 Replace SW2-1 OFF→ON Note1 Group Group ✻2 TB15 TB15 TB15 TB02 M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 Connect A1 B2 A1 B2 M1M2 TB02 ✻2 Leave CN41 as it is.
Page 39
Wiring method Address setting method • a. Indoor/outdoor transmission line The same as 1. (3) Connection of shielded wire: The same as 1. (1) b. Centralized control transmission line The same as 1. (4) Connection of shielded wire: The same as 1. (4) c-1.
Restrictions on Refrigerant Piping Length For the piping connection, the end branching system is applied where the end of refrigerant piping from the outdoor unit is branched and connected to each indoor unit. As the piping connection method, the indoor unit is applied with flare connec- tion, outdoor unit gas piping is flange connection, and liquid piping is flare connection.
Page 41
1. Line-branch method [16 branches or less (the use of only the main BC controller or standard BC controller)] Outdoor unit 110 m or less BC controller 40 m or less Branch pipe (for Y-series) CMY-Y102S-G Junction Indoor unit pipe (option) Indoor unit Indoor unit...
Page 42
[Systems that requires more than 16 pipe-end connections or with multiple BC controllers (with a use of both main and sub controllers)] Outdoor unit <With more than 16 branching> Indoor unit Indoor unit BC controller 110 m or less (sub) Note 6 BC controller (main) 40 m or less...
Page 43
2. Refrigerant piping size Between outdoor unit and BC controller (Part A) Outdoor unit PURY-P200 PURY-P250 PURY-P300 PURY-P350 PURY-P400 Item YGM-A YGM-A YGM-A YGM-A YGM-A High pressure ø 15.88 ø 19.05 ø 22.2 pipe Refrigerant piping size Low pressure ø...
Page 44
3. Connecting the BC controllers (1) BC controller (standard model) end connection piping size [P200-P350 types] Piping sections High-pressure side Low-pressure side (liquid side) (gas side) Item ø 15.88 ø 19.05 PURY-P200YGM-A (Brazed) (Brazed) End connection: 22.2 ø brazed connection PURY-P250YGM-A Outdoor (Brazed)
Page 45
(2) BC controller (main) end connection piping size End connection: brazed connection To outdoor unit Main BC controller ✻2 Junction pipe kit Branch pipe (Type: CMY-Y102S-G) ✻1 (Type: CMY-R160-J) (For CITY MULTI Y series, option) Reducer (option) (supplied) Indoor unit Indoor unit Indoor unit Indoor unit...
Page 46
(3) BC controller (sub) end connection piping size End connection: brazed connection Main BC controller Sub BC controller ✻2 Junction pipe kit Branch pipe (Type: CMY-Y102S-G) ✻1 (Type: CMY-R160-J) (For CITY MULTI Y series, option) Reducer (option) (supplied) Indoor unit Indoor unit Indoor unit Indoor unit...
£ £ Components of the Outdoor Unit [1] Appearance of the Components and Refrigerant Circuit < P200, P250, P300, P350-Types > [ Front view of the unit ] Fan guard Heat exchanger [ Rear view of the unit ] Fan guard Heat exchanger - 44 -...
Page 48
< P200, P250, P300, P350-Types > [ Front view of the refrigerant circuit ] Pressure switch High-pressure High-pressure check joint pressure sensor Discharge muffler 4-way valve Accumulator Inverter compressor Drier Check valve block Ball valve on low-pressure side Ball valve on high-pressure side [ Rear view of the refrigerant circuit ] 4-way valve Accumulator...
Page 49
< P400-type > Fan guard [ Front view of the unit ] Heat exchanger [ Rear view of the unit ] Fan guard Heat exchanger - 46 -...
Page 50
< P400-type > [ Front view of the refrigerant circuit ] High-pressure check joint Pressure switch 4-way valve Low-pressure sensor High-pressure pressure sensor Discharge muffler Accumulator Drier Inverter compressor Ball valve on low-pressure side Ball valve on Check joint on Low-pressure sensor high-pressure side low-pressure side...
Page 51
< P450, P500, P550, P600, P650-Types > [ Front view of the unit ] Fan guard Heat exchanger [ Rear view of the unit ] Fan guard Heat exchanger - 48 -...
Page 52
< P450, P500, P550, P600, P650-Types > [ Front view of the refrigerant circuit ] Oil separator (No.1) Oil separator (No.2) Pressure switch Accumulator Inverter compressor (No.1) Oil balancer tube Commercial power supply compressor (No.2) [ Rear view of the refrigerant circuit ] High-pressure High-pressure pressure sensor...
[4] BC controller (inside the panel) < CMB-P V-G(A) > [ Front (CMB-P1016V-G(A) is shown in the picture) ] Gas pipe (indoor unit side) Liquid pipe (indoor unit side) TH11 LEV1 LEV2 TH16 TH12 SVM2 SVM1 LEV2 TH15 TH11 LEV3 SVM1 LEV1 LEV3...
Page 62
< CMB-P V-GB> [ Front view (CMB-P104V-GB is shown in the picture) ] [ Rear view (CMB-P104V-GB is shown in the picture) ] TH22 LEV3a TH25 - 59 -...
[5] BC control box [ BC controller control box (CMB-P1016V-GA is shown in the picture) ] Relay board Transformer Terminal block for power supply Terminal block for transmission BC controller board [6] BC controller board [ BC controller board ] - 60 -...
¢ ¢ Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers There are two types of remote controllers: M-NET (ME) remote controller, which is connected on the indoor/outdoor transmission line, and MA remote controller, which is connected to each indoor unit.
[2] Group Setting and Interlocking Settings that are Made on an ME Remote Controller 1. Group setting/interlocking setting This operation should be performed to set a group of indoor units between different refrigerant systems and to manually raise the indoor/outdoor unit addresses.
Page 67
Repeat steps 7 and 8 above to interlock all the indoor units in a group with the LOSSNAY. (C) Returning to the normal state When all the group registration and interlock registration operations To return to the normal state, To confirm the addresses, go are completed, return to the normal state as described below.
Page 68
(A) Deleting group registration information (B) When deleting interlocked registration <When completed normally> When deletion was completed normally, “ ” is displayed at the unit type display. If a deletion error occurred, (Alternate display) “ ” is displayed at the room temperature display. “...
[PROCEDURE] 1. Set the air conditioner to the off state with the remote controller [ON/OFF] button. The remote controller display shifts to the OFF window display shown at the left. 2. When the [CHECK] and [Mode selection] buttons 1 are pressed and held down at the same time for two seconds, the remote controller switches to the remote controller function selection mode and the “OPERATION MODE DISPLAY SELECTION MODE”...
3 Registration confirmation result - The indoor unit address and registered LOSSNAY address are displayed alternately. FUNCTION FUNCTION <Indoor unit address and indoor unit display> <LOSSNAY address display and LOSSNAY display> - When LOSSNAY are not registered FUNCTION 4 If registration is unnecessary, end registration by pressing and holding down the B [FILTER] and c [Louver] buttons at the same time for two seconds.
Functions of Principal Parts 1. Outdoor Unit Symbol Name Notes Function Specification Check method (function) Compres- Adjusts the volume of circulating re- (P200-type) frigerant by controlling the operating High-pressure shell scroll type frequency with the operating pres- Winding resistance sure. 20˚C : 0.72Ω...
Page 86
Symbol Name Notes Function Specification Check method (function) 1 High/low pressure bypass at Solenoid AC220~240V Continuity check valve Discharge- starting and stopping, and capacity Open when energized with a tester suction bypass control during low-load operation Closed when not energized 2 High-pressure rise suppression Low-pressure down suppression Discharge-...
¶ ¶ Control [1] Dip Switch Functions and Their Factory Settings 1. Outdoor unit (1) Main board Function according to switch setting Switch setting timing Switch Function Unit address setting Set to 00 or 51-100 with the dial switch Before power on SW1 1~10 For self-diagnosis/operation Refer to the LED monitor display on the outdoor unit board Anytime after power on...
Page 90
DipSW5-1 DipSW3-9 Standard specification Standard specification High-static pressure High-static pressure (60Pa) specification (30Pa) specification (2) INV board Function according to switch setting Switch setting timing Switch Function Enabling/disabling the following error Error detection enabled Error detection disabled Anytime after power on detection functions: ACCT, DCCT sensor circuit error (530X Detail No.
2. Indoor unit DIP SW1, 3 Function according to switch operation Switch set timing Switch Function Remarks Room temp. sensor position Indoor unit inlet Built in remote controller Clogged filter detect. None Provided Filter duration 100h 2500h Always ineffective for PKFY-P.VAM OA intake Ineffective Effective...
Page 92
Setting of DIP SW5 220V 240V ON : 220V 230V OFF : 240V (PLFY-P·VLMD-E) Switch Function Operation by switch Switch set timing (PCFY-P-VGM-E) Ceiling height Ceiling height Always after powering 3.5m setting 2.8m 2.3m (PDFY-P20 ~ 80VM-E, PEFY-P20 ~ 80VMM-E) 100Pa 50Pa External static...
Page 93
3. BC controller (main board) Function according to the switch setting Switch Function Switch setting timing R410A – Model type setting Always leave it to OFF – – – – – – – – Model type setting Refer to the “Model type setting” below Before powering Model type setting Refer to the “Model type setting”...
(2) ME remote controller (PAR-F27MEA) Set the address of the remote controller with the rotary switch. Rotary switch 10 digits 1 digit (left) (right) Remote controller unit Example: In case of address 108 Address setting range Setting method Main remote controller 101 ~ 150 Set to the lowest indoor main unit address + 100.
Page 95
3. Bypass control Bypass solenoid valves (P200-P400: SV1, SV2, P450-P650: SV1, SV2, SV3), which bypass the high- and low- pressure sides, operate in the following manner. (1) Bypass solenoid valve (SV1) (ON = Open) Operation Timing ON (Open) OFF (Close) At No.
Page 96
4. Frequency control • Depending on the capacity required, the frequency of the compressor is controlled to keep constant the evap- oration temperature (0˚C = 0.71MPa) during cooling operation and condensing temperature (49˚C = 2.88MPa) during heating operation. • The capacity of the P200-P400 is controlled solely by the inverter-driven compressor, and the capacity of P450-P650 is controlled by No.1 and No.2 compressors.
Page 97
5. Defrost operation control (1) Starting the defrost operation • Defrost operation is started when the pipe temperature (TH5) of -10˚C or below (-8˚C or below for P400- type and above) has continuously been detected for 3 minutes after the integrated compressor operation time of 50 minutes have passed.
Page 98
6. Refrigerant recovery control Refrigerant is recovered at each pipe-end connection of the BC controller to prevent the refrigerant from accu- mulating in the indoor units in heating operation, stopping mode (fan mode), cooling mode and heating mode with thermo off. Refrigerant recovery is also performed during cooling operation to prevent an excessive accumulation of refriger- ant in the outdoor heat exchanger (P200-P400 types only).
Page 99
(3) Patterns of outdoor unit heat exchanger capacity control [P200-P400types] [P450-P650types] Solenoid valve Solenoid valve Operation Operation Operation Operation mode pattern mode pattern SV4a SV4b SV4c SV4d SV4a SV4b SV4c SV4d SV5a SV5b Cooling Cooling only only Cooling Cooling main main Heating only Heating only...
Page 100
< Initial start-up control of P450-P650 type units: Time chart > [Example1] Completion of initial start up operation 40 minutes 5 minutes No.1 compressor ON/OFF No.2 compressor ON/OFF Step 1 Step 3 <Restrictions under heating initial start-up mode> When the compressor discharge (SH) is low, or the discharge pressure is low under heating-only, heating-main, and cooling-main modes, the capacity total of indoor units which can be operated will be restricted.
Page 101
10. Cooling/heating circuit control and an overview of the functions of system equipment Operation 2 phase Simplified diagram of refrigerant circuit Refrigerant cycle-simplified diagram status Liquid Reverse-flow 4-way valve check valve Switch valve Low- Pressure pressure Low-pressure 2 phase pipe Low-pressure Liquid Cooling...
Page 102
11. Operation mode (1) Indoor unit operation modes An operation mode can be selected from the following 5 modes on the remote controller. Cooling mode Heating mode Dry mode Fan mode Stopping mode (2) Outdoor unit operation modes Five operation modes of the outdoor units Cooling only All indoor units in are in cooling mode.
Page 103
12. BC controller control (CMB-P G, CMB-P GA, CMB-P (1) SV A, SV B, SV C control A, SV B, SV C comes on and off depending on the mode at the pipe end connection. Mode Pipe Cooling Heating Stop Defrost end connection (2) SVM1 control...
Page 104
13. Demand control Cooling/heating operation can be prohibited (thermo OFF) by an external input to the indoor units. Note : When DIPSW4-7 are on, STEP DEMAND are possible. NIGHT MODE will become unavailable however. SW4-7 : OFF (Compressor ON/OFF and NIGHT MODE) CN3D 1-3P CN3D 1-2P Compressor ON/OFF...
[3] Operation Flow Chart 1. Flow to determine the mode (1) Indoor unit (cooling, heating, dry, fan mode) Normal operation Trouble observed Start Stop Breaker turned on From outdoor uni t Operation SW turned on 1. Protection function self-holding Note: ❉1 cancelled.
Page 106
(2) Outdoor unit (Cooling only, heating only, cooling main, heating main operations) Normal operation Start Trouble observed Stop Breaker turned on Note: ❉1 “HO” blinks on the remote controller Set indoor address No. to remote controller From outdoor unit Operation command 1.
Page 107
(3) BC controller (Cooling only, heating only, cooling main, heating main operations) Normal operation Start Trouble observed Stop Breaker turned on Operatio command 1. Judgment of operation mode Cancellation of the self- (Cooling only, heating only, combination of cooling/heating) holding of protection function 2.
Page 108
2. Operation under each mode (1) Cooling operation Normal operation Cooling operation Trouble observed Stop 4-way valve OFF Indoor unit fan Note: ❉1 operations Test run start Thermostat 3-minute restart preven- tion 1. Inverter output 0Hz 1. Inverter frequency control 2.
Page 109
(2) Heating operation Normal operation Trouble observed Stop Test run Heating operation Note: ❉1, 2 Defrost operation 4-way valve OFF 4-way valve OFF 1. Indoor unit fan stop 2. Inverter defrost frequency Test run start control 3. Indoor unit LEV fully closed 4.
Page 110
(3) Dry operation Normal operation Dry operations Trouble observed Stop 4-way valve OFF Test run start Note: ❉2 Thermostat ON Inlet temp. ≥ 18°C Note: ❉1 1. Outdoor unit (Compressor) 1. Indoor unit fan stop intermittent operations 2. Inverter output 0Hz 2.
• • Test Run [1] Check Items before Test Run Check refrigerant leak, loose power source or transmission line if found. Measure resistance between the power source terminal block and ground with a 500V megger to confirm it is exceeding 1.0MΩ. Notes: 1.
[3] Operating Characteristics and Refrigerant Amount Clarify relationship between the refrigerant amount and operating characteristics of CITY MULTI new refrigerant series, and perform service activities such as decision and adjustment of refrigerant amount on the market. 1. Operating characteristics and refrigerant amount The followings are operating characteristics and refrigerant amount which draw special attention.
Page 113
3. Amount of additional refrigerant to be charged The unit is charged with the amount of refrigerant listed in the table below at factory shipment. The refrigerant necessary for extension pipes (on-site piping) is not included and it must be added on site. Outdoor unit model name P200 P250...
[5] Refrigerant Volume Adjustment Mode Operation Since the refrigerant volume adjustment introduced in this chapter is just for emergency need, correct adjustment to meet the rated refrigerant volume is difficult. Please judge for adequate volume by following the flow chart later under normal operation mode.
Page 115
[ Refrigerant Adjustment Method ] Start SW2-4 ON ❉ Refer to the previous page for Notes 1 All indoor units are run in through 4. test cooling mode Has the initial start-up mode been completed? Minimum of 30 minutes continuous operation Add a small amount of refriger- Is TH11...
[6] Symptoms that do not Signify Problems Symptom Remote controller display Cause Indoor unit does not run while oper- "COOL (HEAT)" Unable to execute cooling (heating) operation while ating for cooling (heating). blinking display other indoor unit is under cooling (heating) operation. Auto-vane runs freely.
[2] Responding to Error Display on the Remote Controller 1. Mechanical problems Checking code Meaning, detecting method Cause Checking method & Countermeasure 0403 Serial Serial transmission failure (1) Defective wiring. Check for wiring between the transmission between the main board and the main board connector CNRS3B abnormality INV board, and between the...
Page 129
Checking code Meaning, detecting method Cause Checking method & Countermeasure 1102 Discharge (12) Gas leak between low and Check operation status of temperature high pressures. cooling-only or heating-only. abnormality 4-way valve trouble, compressor (Outdoor unit) trouble, solenoid valve SV1 trouble. (13) Thermistor trouble Check resistance of thermistor.
Page 130
Checking code Meaning, detecting method Cause Checking method & Countermeasure 1302 High pressure (16) Outdoor unit fan block, Check outdoor unit fan abnoramlity 1 motor trouble, poor See Trouble check of outdoor (Outdoor unit) operations of fan controller. unit fan. (8)~(16) : Rise in high pressure caused by lowered condensing capacity in cooling-only and...
Page 131
Checking code Meaning, detecting method Cause Checking method & Countermeasure 2502 Drain pump When drain sensor detects (1) Drain pump malfunction (1) Check the drain pump abnormality flooding during drain pump ON. malfunction 1Check whether there is (This error (2) Clogged drain pump intake occurs only water in the drain pan.
Page 132
Checking code Meaning, detecting method Cause Checking method & Countermeasure 2502 Drain pump When drain sensor detects (1) Drain pump malfunction Refer to the previous page. abnormality flooding during drain pump ON (This error in the stopped indoor unit. (2) Clogged drain pump intake <Error release method>...
Page 133
Checking code Meaning, detecting method Cause Checking method & Countermeasure 4103 Reverse 1. The operation cannot be (1) Faulty wiring · Check whether the phase of phase started because of the the power supply terminal abnormality reserve phase of one of the block (TB1) is normal.
Page 134
Checking code Meaning, detecting method Cause Checking method & Countermeasure 4115 Power supply The frequency cannot be (1) There is an open phase in Check before the breaker, after sync signal determined when the power is the power supply. the breaker or at the power abnormality switched on.
Page 135
Checking code Meaning, detecting method Cause Checking method & Countermeasure 4220 Bus voltage If Vdc 289V is detected during (2) Voltage drop detected. <In the case of 4225> 4225 drop operation. (Software detection) Check the followings 1Check the voltage of CN52C abnormality (Error details on the main board...
Page 136
Checking code Meaning, detecting method Cause Checking method & Countermeasure 4240 Overload When the output current (lac) (1) Air passage short cycle. Ensure that a short cycle has not 4245 abnormality > Imax (Arms) or THHS > 90˚C occurred at the unit fan exhaust. is detected for 10 minutes in a row during the inverter operation.
Page 137
Checking code Meaning, detecting method Cause Checking method & Countermeasure 4250 Refer to 9.[4].7.(2).[2] Load short Shorting at the load <In the case of 4250> 4255 abnormality (compressor) side detected just (1) Shorting of compressor (Error details before starting the inverter. (2) Output wiring 105) (3) Power supply...
Page 138
Checking code Meaning, detecting method Cause Checking method & Countermeasure 5101 Discharge 1. Shorting (high temperature in- (1) Thermistor failure Thermistor resistance check (TH11) take) or open (low temperature Check for lead wire. (TH12) intake) of the thermistor is de- (2) Pinched lead wire tected.
Page 139
Checking code Meaning, detecting method Cause Checking method & Countermeasure High pressure See Troubleshooting of 5201 1. When pressue sensor detects (1) Pressure sensor trouble. pressure sensor. sensor 0.098MPa or less during abnormality operation, outdoor unit once (outdoor unit) stops with 3 minutes (2) Inner pressure drop due to restarting mode, and restarts a leakage.
Page 140
Checking code Meaning, detecting method Cause Checking method & Countermeasure DCCT An abnormal value was (1) Contact is faulty. Check the contacts around the 5301 sensor/circuit detected with the DCCT INV board connector CNCT and 5305 abnormality detection circuit just before the DCCT side connector.
Page 141
Checking Meaning, detecting method Cause Checking method & Countermeasure code Transmission processor hardware 6602 (1) At the collision of mutual transmission data generated during the wiring abnormality work or polarity change of the transmission line of indoor or outdoor unit while turning the power source on, the wave shape is changed and Though transmission processor the error is detected.
Page 142
Checking Meaning, detecting method Cause Checking method & Countermeasure code Communications with transmission Turn off power sources of indoor unit, 6606 (1) Data is not properly processor abnormality and outdoor unit. transmitted due to casual erroneous operation of the When power sources are turned Communication trouble between generating controller.
Page 143
Checking Meaning, detecting method code 6607 No ACK abnormality When no ACK signal is detected in 6 continuous times with 30 seconds (continued) interval by transmission side controller, the transmission side detects error. Note : The address/attribute shown on remote controller indicates the controller not providing the answer (ACK).
Page 144
Checking Meaning, detecting method code No ACK abnormality 6607 When no ACK signal is detected in 6 continuous times with 30 seconds (continued) interval by transmission side controller, the transmission side detects error. Note : The address/attribute shown on remote controller indicates the controller not providing the answer (ACK).
Page 145
Checking Meaning, detecting method code No ACK abnormality 6607 When no ACK signal is detected in 6 continuous times with 30 seconds (continued) interval by transmission side controller, the transmission side detects error. Note : The address/attribute shown on remote controller indicates the controller not providing the answer (ACK).
Page 146
Checking Meaning, detecting method code No ACK abnormality 6607 When no ACK signal is detected in 6 continuous times with 30 seconds (continued) interval by transmission side controller, the transmission side detects error. Note : The address/attribute shown on remote controller indicates the controller not providing the answer (ACK).
Page 147
Checking Meaning, detecting method code No ACK abnormality 6607 When no ACK signal is detected in 6 continuous times with 30 seconds (continued) interval by transmission side controller, the transmission side detects error. Note : The address/attribute shown on remote controller indicates the controller not providing the answer (ACK).
Page 148
Checking code Meaning, detecting method Factor Checking method & Remedy (1) Check the transmission lines 6831 1. Communication between the (1) The remote control line of Communication MA remote controller and the the MA remote controller or of the indoor unit and MA no reception indoor unit is not done the indoor unit has a poor...
Page 149
3. System error Checking Meaning, detecting method Cause Checking method & Countermeasure code Total capacity abnormality (a) Check for the model total (capacity 7100 (1) Total capacity of indoor units cord total) of indoor units connected. in the same refrigerant Total capacity of indoor units in the system exceeds the (b) Check whether indoor unit capacity...
Page 150
Checking Meaning, detecting method Cause Checking method & Countermeasure code (1) Total type number of the in- 7107 Branch port setting error Before resetting the branch port set- door unit per each branch ting switch or the type (capacity code) port or per each merge port Branch port No.
Page 151
Checking Meaning, detecting method Cause Checking method & Countermeasure code Check transmission booster and power 7110 Connection number setting (1) Transmission booster is abnormality faulty. supply. (2) Power supply of transmission booster has been cut. 7111 Remote control sensor abnormality (a) Replace the remote controller with (1) The remote controller without the one with built-in temperature...
Page 152
4. Trouble shooting according to the remote controller malfunction and the external input error (1) In the case of MA remote controller Phenomena Factors Checke method & Handling Even if the operation SW on (1) The power for the indoor unit is not (a) Check voltage of the MA remote controller terminal (among 1 to 3).
Page 153
Phenomena Factors Checke method & Handling When turning on the remote (1) The power for the M-NET When the factor (2) and (3) controller operation SW, a transmission line is not supplied apply, self-diagnosis LED works temporary operation display is from the outdoor unit.
Page 154
Phenomena Factors “HO” display on the remote (1) The power for the M-NET transmission line is not controller does not turn off, supplied from the outdoor unit. When the factor and the switch does not work. (2) Short circuit of the transmission line. (2) and (3) apply, self-diagnosis (3) Incorrect wiring of the M-NET transmission line on...
Page 155
<Flow chart> Even if the operation SW on the remote controller is pressed, the indoor and the outdoor units do not start running. - 152 -...
Page 156
(2) In the case of the M-NET remote controller Phenomena Factors Checke method & Handling Even if the operation SW on (a) Check voltage of the M-NET remote (1) The power for the M-NET controller transmission terminal. the remote controller is transmission line is not supplied i) If the voltage is 17V-30V pressed, the display remains...
Page 157
Phenomena Factors “HO” display on remote (Without using MELANS) controller does not disappear (1) Outdoor unit address is set to “00” and ON/OFF switch is (2) Erroneous address. 1 Address setting of indoor unit to be coupled with remote controller incorrect. ineffective.
Page 158
Phenomena Factors Checke method & Handling (a) Confirm the address of unit to be “88” appears on remote (Generates at registration and coupled. controller at registration and confirmation) (b) Check the connection of access remote controller. (1) Erroneous address of unit to be transmission line.
Page 159
(3) Both for MA remote controller and M-NET remote controller Phenomena Factors Checke method & Handling (a) Observe difference between sensor Cooling with normal remote (1) Insufficient frequency rise 1 Faulty detection of pressure controller display but not detected pressure and actual providing capacity.
Page 160
Phenomena Factors Checke method & Handling Cooling with normal remote (7) Clogging by foreign matter Check temperature difference between controller display but not before and after a portion (strainer, providing capacity. distributor) of low pressure piping where foreign matter may likely be clogged.
Page 161
Phenomena Factors Checke method & Handling Heating with normal remote (3) When abnormal temperature of Check piping thermistor. controller display but not indoor unit piping temperature providing capacity. sensor is taken higher, LEV is throttled excessively due to apparent small sub-cooling. (4) Abnormal speed of outdoor unit fan Refer to the page of outdoor unit fan.
[3] Investigation of Transmission Wave Shape/Noise 1. M-NET transmission Control is performed by exchanging signals between outdoor unit, indoor unit and remote controller by M-NET transmission. If noise should enter into the transmission line, the normal transmission will be hindered causing erroneous operation.
Page 163
(3) Checking and measures to be taken (a) Measures against noise Check the items below when noise can be confirmed on wave shape or the error code in the item (1) is generated. Items to be checked Measures to be taken (1) Wiring of transmission and power lines in cross- Isolate transmission line from power line (5cm or more).
Page 164
2. MA remote control transmission The MA remote control and indoor unit communicate with the current tone burst method. (1) Symptoms caused by infiltration of noise on transmission cable If noise, etc., infiltrates the transmission cable and the communication between the MA remote control and indoor unit is cut off for three consecutive minutes, a MA communication error (6831) will occur.
[4] Troubleshooting of Principal Parts 1. Pressure sensor (1) Check for failure by comparing the sensing pressure according to the high pressure/low pressure pressure sensor and the pressure gauge pressure. Set SW1 as shown below to display the high and low pressure sensor data displayed digitally by the light emitting diode LD1.
Page 166
2. Low-pressure pressure sensor (63LS) Conduct the check comparing the pressure that is detected by the low-pressure pressure sensor and the low-pressure gauge pressure. The pressure that is detected by the low-pressure pressure sensor will be displayed on the LED screen, LD1 when setting the digital shift switch (SW1) as shown below.
Page 167
3. Solenoid valve Check if the control board’s output signals and the operation of the solenoid valves match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED’s. Each LED shows whether the relays for the following parts are ON or OFF.
Page 168
(4) In the case of SV4a~4d [P200/P400 type] or SV4a~4d, 5a, 5b [P450-P650 type] (Heat exchanger capacity control) In the case of cooling-only, one or more valves among SV4a~4c, 5a, 5b turn(s) on depending on the condition. Check the operation by LED display and operation sound of the solenoid valve. In the case of heating-only, all of SV4a~4c, 5a, 5b turn on.
Page 170
(6) Check valve block , 7, 8, and 9. Check the LED monitor. Valve plug A, By turning on or off SV3-6, the refrigerant flows through B and C can be removed with 3 kinds of hex wrenches. Hex wrench size is shown below. Refrigerant circuit figure (P200-P400types) Refrigerant flow in the case Refrigerant flow in the case...
Page 172
5. Troubleshooting method of main parts of BC controller (1) Pressure sensor Troubleshooting flow chart for pressure sensor Start Note1 Check whether the pressure sensor or the con- nectors of P1 and P3 are not disconnected, not loose, or not connected wrongly. Fix the fault.
Page 173
Note1 BC controller: Phenomena when the pressure sensor is connected wrongly (reverse connection of P1 and P3) to the board. Phenomena Cooling-only Cooling-main Heating-only Heating-main Normal Non-cooling SC11 large Heating indoor SC11 large Non-cooling SC11 large SC16 small SC small SC16 small Heating indoor SC16 small...
Page 174
Note1 For the connectors on the board, TH11~TH12 is CN10, and TH15 and TH16 is CN11. Disconnect the applied connector, and check every number of the sensor. Note2 and 3 (1) Pull out the sensor connector from the I/O board ······· Do not pull the sensor with holding the lead wire. (2) Measure the resistance with such as a tester.
Page 175
(3) Troubleshooting flow chart for LEV · Solenoid valve 1LEV No cooling capacity No heating capacity Note1 Check whether the electric expansion valve and the solenoid valve connector are not disconnected or not loose. Fault is found Fix the fault. Run the cooling operation or the heating operation in the applied system (only one system).
Page 176
Note1 BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV1 and LEV3) to the board. Phenomena Cooling-only Cooling-main Heating-only Heating-main Non-cooling Non-cooling, non-heating Indoor heating SC small Non-cooling SH12 small, SC11 small SH12 small, SC11 small PHM large Indoor heating SC small SH16 small, branch pipe SH16 large, but branch pipe...
Page 178
<Troubleshooting flow chart for solenoid valve body> Start Check that the connector and the terminal are not disconnected, and check the color of the lead wire visually. Intermediate connector Control board Brown Brown Blue Blue When LEV is fully closed: tick sound Orange Orange When LEV is fully open : no sound...
Page 179
2Solenoid valve (SVA, SVB, SVC) Faulty judgment of solenoid valve Stop the operation of the applied BC remote controller system. (Use the remote controller to turn off.) Stop the Stop the operation. operation. Check whether the wire to the solenoid valve is not connected wrongly, or the connector is not loose.
Page 180
Check whether the BC board output signal and the solenoid valve operation correspond. Note1 SVA, SVB, SVC SVA, SVB and SVC turn on or off according to the indoor unit operation mode. Mode Cooling Heating Stop Defrost Branch end SVM1, SVM2 [P400-P550 types] SVM1,SVM2 turns on or off according to the operation mode.
Page 181
6. LEV (1) Indoor, BC controller LEV The valve opening angle changes in proportion to the number of pulses. (Connections between the indoor unit’s control board and indoor, BC controller LEV.) Indoor control board Wire joining connecter DC12V φ 6 Brown φ...
Page 182
(2) Judgment methods and likely failure mode Caution: The specifications of the outdoor unit (outdoor LEV) and indoor unit (indoor LEV) differ. For this reason, there are cases where the treatment contents differ, so follow the treatment specified for the appropriate LEV as indicated in the right column.
Page 183
7. Inverter and compressor a. Replace only the compressor if only the compressor is found to be defective. (Overcurrent will flow through the inverter if the compressor is damaged, however, the power supply is automatically cut when overcurrent is detected, protecting the inverter from damage.) b.
Page 184
(2) Treatment of inverter output related troubles Check item Phenomena Treatment Perform the following: (1) IPM/overcurrent error. • Replace INV board. Check the INV 1. Disconnect INV board CNDR2. (4250 detailed No. 101, 102, 103, board error After removing, turn on the out- 104, 105, 106, 107) detection circuit.
Page 185
Check item Phenomena Treatment 1. Check to see if the IPM screw (1) Screw terminal is loose. Check all IPM screw terminals and Check the terminal is loose. tighten. inverter circuit trouble. 2. Check the exterior of the IPM. (2) IPM is cracked due to swelling. •...
Page 186
(3) Trouble measures when main power breaker tripped Check item Phenomena Treatment Perform Meg check between the (1) Zero to several ohm, or Meg failure. Check each part in the main inverter circuit. terminals in the power terminal • Refer to "Simple checking Procedure for in- block TB1.
Page 187
(5) Intelligent power module (IPM) Measure resistances between each terminal of IPM with tester, and use the results for troubleshooting Notes on measurement • Make sure the polarity before the measurement. (On the tester, black normally indicates plus.) • Make sure that the resistance is not open (∞Ω) or not shorted (to 0Ω). •...
Page 188
(7) Caution at replacement of inverter parts (1) Fully check wiring for incorrect and loose connection. The incorrect or loose connection of the power circuit part wiring like IPM and diode module causes to damage the IPM. Therefore, check the wiring fully. As the insufficient tightening of screws is difficult to find, tighten them together additionally after finishing other works.
Page 189
8. Control circuit (1) Control power source function block [ P200~P400 types ] Power source system Control system (DC5~30V) Smoothing Compressor Noise filter Rectifier 52C1 capacitor Inverter AC380~415V Terminal block for power source G/A board Fuse (6.3A) Fuse IPM drive circuit (10A) Heat exchanger...
Page 190
[ P450~P650 type ] Power source system Control system (DC5~30V 51C2 Fuse (50A) 52C2 No.2 Compressor Smoothing No.1 capacitor AC380~415V Rectifier 52C1 Inverter Noise filter Compressor Terminal block for power source G/A board Heat Fuse (6.3A) exchanger 52C2 Fuse Relay board IPM drive circuit (10A) Heat...
Page 191
(2) Outdoor unit transmission power source circuit failure judgment Check voltage of indoor/outdoor transmis- sion terminal block (TB3) of outdoor unit. Check and modify transmission line for DC24 ~ 30V disconnection & poor contact Check voltage of TB3 by removing transmission line from TB3.
[5] Refrigerant Leak 1. Leak spot: In the case of extended pipe for indoor unit (Cooling season) 1 Mount a pressure gauge on the check joint (CJ2) for low-pressure service. 2 Stop all the indoor units, and close the liquid ball valve (BV2) inside the outdoor unit while the compressor is being stopped.
Page 193
3. Leak spot: In the case of extended pipe for indoor unit (Heating season) 1 Conduct a test run for all the indoor units under the heating mode. (1) To start a test run for all the indoor units, turn on SW3-2 when SW3-1 on the outdoor unit main board is ON. (2) Change the setting of the remote controller for all the indoor units to the heating mode.
[6] Compressor Replacement Instructions (only P450-P650 types) Follow the instructions below when replacing the compressor. When replacing the compressor No.1 (inverter drive), start replacing after judging whether the compressor is malfunctioning or the inverter is malfunctioning. When only one compressor is malfunctioning, operate the compressor for approximately an hour under emergency operation mode before the replacement, check the items below, and replace the compressor after examining whether the return oil circuit is working properly or not.
(19) Attach the crankcase heater. Note : Attach the appropriate crankcase heater to the appropriate compressor. (20) Attach the soundproof material to the compressor. (21) Attach the discharge tempareture themistor, and attach the insulation cover. (22) Attach the power source wire to the terminal on the compressor. (23) After vacuuming, calculate the amount of added refrigerant at factory shipment and the amount of added refrigerant on site, and charge the system.
[8] BC controller service instruction ✻Special care must be taken when replacing heavy parts. (1) Service panel Work procedure Explanatory figure 1. Remove 2 lock nuts on the control box, loose 2 lock nuts, Ceiling panel Service panel Loose and remove the control box. 2.
Page 197
(4) Pressure sensor Work procedure Explanatory figure 1. Remove the service panel. TH11 TH16 PS3 PS1 LEV3 1 For the pressure sensors PS1 and PS3, refer to LEV1 (1)-1.2. 2. Remove the applied pressure sensor connector from the LEV2 control board, and insulate the connector. 1 Liquid-side pressure sensor (CNP1) 2 Intermediate-part pressure sensor (CNP3) TH12...
Page 198
✻Special care must be taken when replacing heavy parts. (6) Solenoid valve Work procedure Explanatory figure 1. Remove the service panel. (Refer to (1)-1.2.3.) Double pipe heat exchanger 2. Remove the connector of the applied solenoid valve. 3. Remove the solenoid valve coil. 1 For the solenoid valve coil of SVA, SVB and SVM1, 2 service from the inspection door is possible.
LED display [1] LED Monitor Display 1. How to read LED for service monitor By setting of DIP SW1-1 ~ 1-10, the unit operating condition can be observed with the service LED on the control circuit board. (For the relation of each DIP SW to the content, see the table provided.) As shown in the figure below, the LED consist of 7 segments is put in 4 sets side by side for numerical and graphic display.
Page 200
3. Time data storage function ❉ This function is not compatible with some units. The outdoor unit has a simple clock function to receive the time setting from the system controller, such as the G50A, and count the current time with an internal timer. If an error (prediction) occurs, the error history data and the error detection time are saved in the service memory.
Page 201
4. List of code on the LED monitor LED monitor display Item Remarks 1234567890 0000000000 Relay output display 1 Comp Comp 1 Comp 2 Lights for LD8 is a relay output (lighting to display) operation operation operation 52C1 52C2 normal which lights up at all operation times when the...
Page 202
Item Remarks 1234567890 0111100000 Unit No.1 Unit No.2 Unit No.3 Unit No.4 Unit No.5 Unit No.6 Unit No.7 Unit No.8 Indoor unit Lights up when thermostat thermostat is on. Unit No.9 Unit No.10 Unit No.11 Unit No.12 Unit No.13 Unit No.14 Unit No.15 Unit No.16 1111100000 Goes off when thermostat is off.
Page 204
Item Remarks 1234567890 0000 ~ 9999 111 1111011000 COMP1 bus voltage The unit is [ V ]. 112 0000111000 113 1000111000 114 0100111000 115 1100111000 116 0010111000 117 1010111000 Compressor 1 opera- 0000 ~ 9999 The unit is [ h ]. tin time upper 4 digits.
Page 205
Item Remarks 1234567890 150 0110100100 BC (Main,Standard) TH12 -99.9 ~ 999.9 The unit is [ ˚C ]. ↑ BC (Main,Standard) TH15 151 1110100100 ↑ BC (Main,Standard) TH16 152 0001100100 BC (Main,Standard) 63HS1 ↑ 153 1001100100 The unit is [ kgf/cm ↑...
Page 206
Item Remarks 1234567890 Inverter error detail Inverter error detail (0001 ~ 0120) Address and error code 193 1000001100 are reversed and disp- 194 0100001100 0000 ~ 9999 layed. Error history 9 "----" is displayed when there is no error. Inverter error detail Inverter error detail (0001 ~ 0120) 195 1100001100 0000 ~ 9999...
Page 222
Item Remarks 1234567890 1100011011 0010011011 1010011011 0110011011 -99.9 ~ 999.9 1110011011 U phase current The unit is [ A ]. effective value 1 ↑ 0001011011 W phase current effective value 1 ↑ 1001011011 The unit is [ deg ]. Power tactor phase angle 1 (deg) 0101011011 1101011011...
Page 224
Service Handbook PURY-P200, P250, P300, P350, P400YGM-A PURY-P450, P500, P550, P600, P650YGM-A HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Issued in Sep. 2004 HWE04020 New publication effective Sep. 2004. Printed in Japan Specifications subject to change without notice.