Safety Precautions Before installing the unit, thoroughly read the following safety precautions. Observe these safety precautions for your safety. WARNING This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid the risk of serious injury or death.
Page 3
WARNING Securely attach the terminal block cover (panel) to the After completing the service work, check for a gas unit. leak. If the terminal block cover (panel) is not installed properly, If leaked refrigerant is exposed to a heat source, such as a dust and/or water may infiltrate and pose a risk of electric fan heater, stove, or electric grill, poisonous gases may be shock, smoke, and/or fire.
Page 4
Precautions for handling units for use with R410A CAUTION Do not use the existing refrigerant piping. Use a vacuum pump with a reverse-flow check valve. A large amount of chlorine that is contained in the residual If a vacuum pump that is not equipped with a reverse-flow refrigerant and refrigerator oil in the existing piping may check valve is used, the vacuum pump oil may flow into the cause the refrigerator oil in the new unit to deteriorate.
Before installing the unit WARNING Do not install the unit where a gas leak may occur. When installing the unit in a hospital, take appropriate measures to reduce noise interference. If gaseous refrigerant leaks and piles up around the unit, it may be ignited.
Page 6
Before installing the unit (moving and reinstalling the unit) and performing electrical work CAUTION Properly ground the unit. Periodically check the installation base for damage. Do not connect the grounding wire to a gas pipe, water pipe, If the unit is left on a damaged platform, it may fall and lightning rod, or grounding wire from a telephone pole.
Page 7
Before the test run CAUTION Turn on the unit at least 12 hours before the test run. Do not operate the unit without panels and safety guards. Keep the unit turned on throughout the season. If the unit is turned off in the middle of a season, it may result in malfunc- Rotating, high-temperature, or high-voltage parts on the unit tions.
CONTENTS I Read Before Servicing [1] Read Before Servicing......................3 [2] Necessary Tools and Materials ....................4 [3] Piping Materials ........................5 [4] Storage of Piping ........................7 [5] Pipe Processing........................7 [6] Brazing............................8 [7] Air Tightness Test........................9 [8] Vacuum Drying (Evacuation) ....................
Page 9
CONTENTS [7] Servicing the BC controller ....................350 [8] Troubleshooting Using the Outdoor Unit LED Error Display..........353 X LED Monitor Display on the Outdoor Unit Board [1] How to Read the LED on the Service Monitor ..............357 HWE0913A...
Page 10
I Read Before Servicing [1] Read Before Servicing ....................... 3 [2] Necessary Tools and Materials..................4 [3] Piping Materials ......................... 5 [4] Storage of Piping ....................... 7 [5] Pipe Processing ......................... 7 [6] Brazing..........................8 [7] Air Tightness Test ......................9 [8] Vacuum Drying (Evacuation) ...................
[ I Read Before Servicing ] I Read Before Servicing [1] Read Before Servicing 1. Check the type of refrigerant used in the system to be serviced. Refrigerant Type Multi air conditioner for building application CITY MULTI R2 TJMU-A, YJMU-A series R410A 2.
[ I Read Before Servicing ] [2] Necessary Tools and Materials Prepare the following tools and materials necessary for installing and servicing the unit. Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C) 1.
[ I Read Before Servicing ] [3] Piping Materials Do not use the existing piping! 1. Copper pipe materials O-material (Annealed) Soft copper pipes (annealed copper pipes). They can easily be bent with hands. 1/2H-material (Drawn) Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed) at the same radial thickness.
Page 15
[ I Read Before Servicing ] 4. Thickness and refrigerant type indicated on the piping materials Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant. 5. Flare processing (O-material (Annealed) and OL-material only) The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system. Flare processing dimensions (mm[in.]) A dimension (mm) Pipe size (mm[in.])
[ I Read Before Servicing ] [4] Storage of Piping 1. Storage location Store the pipes to be used indoors. (Warehouse at site or owner's warehouse) If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe. 2.
[ I Read Before Servicing ] [6] Brazing No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide scale, water, and dust) out of the refrigerant system. Example: Inside the brazed connection Use of no inert gas during brazing Use of inert gas during brazing 1.
[ I Read Before Servicing ] [7] Air Tightness Test No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak. Halide torch R22 leakage detector 1. Items to be strictly observed Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight- ness, taking temperature variations into account.
[ I Read Before Servicing ] [8] Vacuum Drying (Evacuation) (Photo1) 15010H (Photo2) 14010 Recommended vacuum gauge: ROBINAIR 14010 Thermistor Vacuum Gauge 1. Vacuum pump with a reverse-flow check valve (Photo1) To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum pump with a reverse-flow check valve.
Page 20
[ I Read Before Servicing ] 7. Notes To evacuate air from the entire system Applying a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) is not enough to attain the desired vacuum pressure. Be sure to apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) and also through the check joints on the high and low pressure sides (CJ1 and 2).
[ I Read Before Servicing ] [9] Refrigerant Charging Cylinder with a siphon Cylinder without a siphon Cylin- Cylin- Cylinder color R410A is pink. Refrigerant charging in the liquid state Valve Valve liquid liquid 1. Reasons R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled the same way as a single refrigerant, such as R22.
[ I Read Before Servicing ] [11] Characteristics of the Conventional and the New Refrigerants 1. Chemical property As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant. However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia.
[ I Read Before Servicing ] [12] Notes on Refrigerating Machine Oil 1. Refrigerating machine oil in the HFC refrigerant system HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system. Note that the ester oil used in the system has properties that are different from commercially available ester oil. Refrigerant Refrigerating machine oil Mineral oil...
II Restrictions [1] System configuration ....................... 17 [2] Types and Maximum allowable Length of Cables ............18 [3] Switch Settings and Address Settings ................19 [4] Sample System Connection..................... 26 [5] An Example of a System to which an MA Remote Controller is connected..... 28 [6] An Example of a System to which an ME Remote Controller is connected.....
[ II Restrictions ] II Restrictions [1] System configuration 1. Table of compatible indoor units The table below summarizes the types of indoor units that are compatible with different types of outdoor units. Outdoor Composing units Maximum total capacity Maximum number Types of connectable in- units of connectable indoor...
[ II Restrictions ] [2] Types and Maximum allowable Length of Cables 1. Wiring work (1) Notes 1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man- ual. 2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference. (Do not put the control cable and power supply cable in the same conduit tube.) 3) Provide grounding for the outdoor unit as required.
[ II Restrictions ] 2) Remote controller wiring MA remote controller ME remote controller Type VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT Shielded cable MVVS Number of 2-core cable 2-core cable cores Cable type 2 *2 2 *2 0.3 to 1.25mm 0.3 to 1.25mm [AWG22 to 16] [AWG22 to 16]...
Page 29
[ II Restrictions ] 2. M-NET Address settings (1) Address settings table The need for address settings and the range of address setting depend on the configuration of the system. Unit or controller Sym- Address Setting method Factory setting address range setting CITY MULTI...
Page 30
[ II Restrictions ] Unit or controller Sym- Address Setting method Factory setting address range setting System Group remote con- 201 to Assign an address that equals the sum of the smallest controller troller group number of the group to be controlled and 200. System remote con- Assign an arbitrary but unique address within the range troller...
Page 31
[ II Restrictions ] (2) Power supply switch connector connection on the outdoor unit (Factory setting: The male power supply switch connector is connected to CN41.) There are limitations on the total number of units that are connectable to each refrigerant system. Refer to the System Design Manual for details.
Page 32
[ II Restrictions ] (5) Various start-stop controls (Indoor unit settings) Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10. *4 *5 Setting (SW1) Operation of the indoor unit when the operation is resumed after the unit Function was stopped Power ON/OFF by the...
Page 33
[ II Restrictions ] CAUTION 1) Wiring should be covered by insulation tube with supplementary insulation. 2) Use relays or switches with IEC or equivalent standard. 3) The electric strength between accessible parts and control circuit should have 2750V or more. Example of wiring connection (1) CN51 (2) CN3S...
Page 34
[ II Restrictions ] (8) Demand control 1) General outline of control Demand control is performed by using the external signal input to the 1-2 and 1-3 pins of CN3D on the outdoor units (OC and OS). Between 2 and 8 steps of demand control is possible by setting Dip SW4-4 on the outdoor units (OC and OS). DipSW4-4 Demand control switch Input to CN3D*...
[ II Restrictions ] [4] Sample System Connection Examples of typical system connection are shown on pages [5] to [7]. Refer to the Installation Manual that came with each device or controller for details. (1) An example of a system to which an MA remote controller is connected System Address start up for in- Connection to the system controller...
[ II Restrictions ] [5] An Example of a System to which an MA Remote Controller is connected 1. System with one outdoor unit (automatic address setup for both indoor and outdoor units) (1) Sample control wiring Interlock operation with the ventilation unit Leave the male Leave the male...
Page 38
[ II Restrictions ] Set one of the MA remote controllers as a sub controller. (4) Wiring method (Refer to the Instruction Manual for the MA remote con- 1) Indoor/outdoor transmission line troller for the setting method.) Daisy-chain terminals M1 and M2 of the terminal block Group operation of indoor units for indoor-outdoor transmission line (TB3) on the outdoor To perform a group operation of indoor units (IC), daisy-...
Page 39
[ II Restrictions ] 2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address setup for both indoor and outdoor units) (1) Sample control wiring Interlock operation with the ventilation unit Leave the male Leave the male Group...
Page 40
[ II Restrictions ] 2) Transmission line for centralized control (4) Wiring method No connection is required. 1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 of the terminal block 3) MA remote controller wiring for indoor-outdoor transmission line (TB3) on the outdoor Same as [5] 1.
Page 41
[ II Restrictions ] 3. Group operation of units in a system with multiple outdoor units (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male from CN41 to CN40. Group Group Group connector on SW2-1 OFF CN41 as it is.
Page 42
[ II Restrictions ] (4) Wiring method problem with the outdoor unit whose power jumper was moved from CN41 to CN40, central control is not possible, 1) Indoor/outdoor transmission line even if TB7's are daisy-chained.) Only use shielded cables. Same as [5] 2. Shielded cable connection Shielded cable connection Same as [5] 2.
Page 43
[ II Restrictions ] 4. A system in which a system controller is connected to the transmission line for centralized control and which is pow- ered from an outdoor unit (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector from CN41 to CN40.
Page 44
[ II Restrictions ] problem with the outdoor unit whose power jumper was (4) Wiring method moved from CN41 to CN40, central control is not possible, 1) Indoor/outdoor transmission line even if TB7's are daisy-chained.) Only use shielded cables. Same as [5] 2. Only use shielded cables.
Page 45
[ II Restrictions ] 5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except LM adapter) (1) Sample control wiring Interlock operation with the ventilation unit CN41 CN40 Replace Leave the male SW2-1 OFF ON connector on CN41 as it is.
Page 46
[ II Restrictions ] daisy-chained, connect the transmission line for the central control (4) Wiring method system to TB7 of the OC. (Note a).To maintain the central control even during an OC failure or a power failure, connect TB7 on OC 1) Indoor/outdoor transmission line and OS together.
Page 47
[ II Restrictions ] 6. A system with multiple BC controller connections (with a system controller connected to the centralized control line) (1) Sample control wiring Leave the male Move the male connector connector on from CN41 to CN40 CN41 as it is. SW2-1 OFF ON Group Group...
Page 48
[ II Restrictions ] (4) Wiring method b) If TB7's on the outdoor units in the same refrigerant cir- 1) Indoor/outdoor transmission line cuit are not daisy-chained, connect the transmission line Daisy-chain terminals M1 and M2 of the terminal block for the central control system to TB7 of the OC.
Page 49
[ II Restrictions ] (5) Address setting method Pro- Fac- Address tory Unit or controller setting Setting method Notes set- range ting Assign the smallest address to the main unit in the Port number setting is re- Indoor Main unit IC 01 to 50 group.
[ II Restrictions ] [6] An Example of a System to which an ME Remote Controller is connected (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male from CN41 to CN40. connector on SW2-1 OFF ON CN41 as it is.
Page 52
[ II Restrictions ] When 2 remote controllers are connected to the sys- (4) Wiring method 1) Indoor/outdoor transmission line Refer to the section on Switch Setting. Same as [5] 2. Performing a group operation (including the group Shielded cable connection operation of units in different refrigerant circuits).
[ II Restrictions ] [7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected (1) Sample control wiring Move the male connector Leave the male from CN41 to CN40. Group Group connector on SW2-1 OFF ON CN41 as it is.
Page 54
[ II Restrictions ] Group operation of indoor units) (4) Wiring method Same as [5] 1. 1) Indoor/outdoor transmission line 4) ME remote controller wiring Same as [5] 2. (When 2 remote controllers are connected to the sys- Shielded cable connection Same as [5] 2.
Page 55
[ II Restrictions ] (5) Address setting method Pro- dress Facto- Unit or controller set- Setting method Notes ry set- dure ting ting range Assign the smallest address to Assign an address smaller than that of Opera- Main 01 to the main unit in the group.
[ II Restrictions ] [8] Restrictions on Pipe Length (1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con- troller> Outdoor unit *Use a main BC controller when connecting the outdoor units of P144 model or above.
Page 57
[ II Restrictions ] Restrictions on pipe length [PURY-P72, P96TJMU-A, PURY-P72, P96YJMU-A] The height difference and the pipe length between BC controller and indoor units 1000 [229] [3280] [2952] [196] [2624] [164] [2296] [131] [1968] [98] [1640] [64] [1312] [32] [984] [656] 90 100 110...
Page 58
[ II Restrictions ] (2) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P144 model or below.> Outdoor unit Branch joint Indoor (CMY-Y202-G2) (CMY-Y102L-G2) (CMY-Y102S-G2) BC controller (sub) BC controller (main) Branch joint (CMY-Y102S-G2) BC controller (sub) Reducer (P06 - P18 models)
Page 59
[ II Restrictions ] 1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel.
Page 60
[ II Restrictions ] (3) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P168 model or above.> Branch joint (CMY-R100VBK) Outdoor unit The distributor on the low-pressure side must be placed in the outdoor unit that has a larger capacity Outdoor unit index of the two, regardless of the relative positions of the outdoor units or their addresses.
Page 61
[ II Restrictions ] 1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers. 2) When connecting two sub BC controllers, observe the maximum allowable length in the table above. 3) When connecting two sub BC controllers, install them in parallel.
Page 62
[ II Restrictions ] 1. Refrigerant pipe size (1) Between outdoor unit and the first twinning pipe (Part A) Unit : mm [inch] Refrigerant pipe size Connection to outdoor unit and BC controller Outdoor units Low-pressure pipe High-pressure pipe Low-pressure pipe High-pressure pipe ø19.05 [3/4"] ø15.88 [5/8"]...
Page 63
[ II Restrictions ] 2. Connecting the BC controller (1) Size of the pipe that fits the standard BC controller ports P72 - P120 models Connection: Brazed connection To outdoor unit BC controller Reducer Branch joint (Model name:CMY-Y102S-G2) Junction pipe kit (Standard (Optional accessory) (Model name:...
Page 64
[ II Restrictions ] 1) To connect P06 - P18 models of indoor units use 2) To connect P72 - P96 models of indoor units (or when the the reducer that is supplied with the BC controller. total capacity of indoor units exceeds P55), use a junction pipe kit and merge the two nozzles.
Page 65
[ II Restrictions ] (2) Size of the pipe that fits the main BC controller ports P72 - P288 models Branch joint (Model name:CMY-Y102S-G2) (Optional accessory) Connection: Brazed connection To outdoor unit BC controller (main) Reducer (Standard supplied parts) Junction pipe kit (Model name:CMY-R160-J) (Optional accessory) Indoor...
Page 66
[ II Restrictions ] (3) Size of the pipe that fits the sub BC controller ports Branch joint (Model name:CMY-Y102S-G2) Connection: Brazed connection (Optional accessory) To Main BC controller Junction pipe kit BC controller (sub) (Model name: CMY-R160-J) (Optional accessory) Reducer (Standard supplied parts) Indoor...
III Outdoor Unit Components [1] Outdoor Unit Components and Refrigerant Circuit ............61 [2] Control Box of the Outdoor Unit..................66 [3] Outdoor Unit Circuit Board....................70 [4] BC Controller Components ....................80 [5] Control Box of the BC Controller..................83 [6] BC Controller Circuit Board....................
[ III Outdoor Unit Components ] III Outdoor Unit Components [1] Outdoor Unit Components and Refrigerant Circuit 1. Front view of a outdoor unit (1) PURY-P72, P96TJMU-A PURY-P72, P96YJMU-A Fan guard Control Heat exchanger Front panel Fin guard HWE0913A - 61 -...
Page 71
[ III Outdoor Unit Components ] (2) PURY-P120, P144TJMU-A PURY-P120, P144YJMU-A Fan guard Control Contactor Contactor Heat exchanger Heat exchanger Transformer box Transformer box (YJMU-A only) (YJMU-A only) Front panel Fin guard HWE0913A - 62 -...
[ III Outdoor Unit Components ] [2] Control Box of the Outdoor Unit <HIGH VOLTAGE WARNING> Control box houses high-voltage parts. When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
Page 76
[ III Outdoor Unit Components ] 2. PURY-P96, P120, P144TJMU-A Note.2 Fan board INV board Control board DC reactor (DCL) Electromagnetic relay (72C) Diode stack Noise filter Current sensor (ACCT3) M-NET board Current sensor (DCCT1) Terminal block for power supply (TB1) Current sensor Ground terminal...
Page 77
[ III Outdoor Unit Components ] 3. PURY-P72, P96, P120, P144YJMU-A Capacitor(C100) Rush current protection resistor (R1,R5) Note.2 Electromagnetic relay(72C) Fan board Control board DC reactor (DCL) Noise filter M-NET board Terminal block for power supply (TB1) Fuse(F4) Terminal block for transmission line Ground Fuse(F5) (TB3, TB7)
[ III Outdoor Unit Components ] [3] Outdoor Unit Circuit Board 1. Outdoor unit control board CN332 CNDC Serial communication signal input CN801 Output 18VDC Bus voltage input GND INV board Pressure switch Output 17VDC connection (Fan board) Serial communication signal output CNAC2 CN505 72C driving output...
Page 80
[ III Outdoor Unit Components ] 2. M-NET board CNIT CNS2 CN04 CN102 Input 12VDC Transmission line Bus voltage input Power supply output for centralized CN03(TJMU only) input/output for (YJMU only) control system (30VDC) (TJMU only) Input 5VDC Bus voltage input centralized control Bus voltage output Indoor/outdoor transmission line...
Page 81
[ III Outdoor Unit Components ] 3. INV board (1) PURY-P72TJMU-A Open: No-load operation setting CN5V Short-circuited: Normal setting SC-P1 Rectifier diode output (P) Output 5VDC LED1 Lit: Inverter in normal operation Blink: Inverter error IGBT (Rear) GND(Fan Board) Serial communication signal output C30,31,32 Smoothing capacitor CNDC...
Page 82
[ III Outdoor Unit Components ] (2) PURY-P96, P120, P144TJMU-A CNCT3 CNTH AC sensor input Thermistor input (ACCT3) CNTYP (THHS) Function setting CNCT2 connector input LED4 (Z26) AC sensor input LED1 Lit during normal CPU operation ACCT1 ON:No-load operation setting Inverter operation (Lit)/error (Blinking) OFF:Normal setting ACCT2...
Page 83
[ III Outdoor Unit Components ] (3) PURY-P72, P96, P120, P144YJMU-A SC-P1 Rectifier diode output (P) Open: No-load operation setting CN5V RSH1 SC-P2 Short-circuited: Normal setting LED1 Overcurrent detection Bus voltage Input(P) Lit: Inverter in normal operation 5VDC output resistor Blink: Inverter error GND(Fan Board) Serial communication...
Page 84
[ III Outdoor Unit Components ] 4. Fan board (1) PURY-P72, P96, P120, P144TJMU-A GND CNVDC Serial communication signal output Bus voltage input CN18V LED3 N GND (Control board) Fuse Input 18VDC Lit during normal P Serial communication signal output 250VAC 15A GND CPU operation...
Page 85
[ III Outdoor Unit Components ] (2) PURY-P72, P96, P120, P144YJMU-A LED3 CN18V Lit during normal Input 18VDC CPU operation Serial communication signal output GND(Control board) Serial communication signal output CN21 Serial communication signal output GND(INV board) CNVDC Input 17VDC Bus voltage input CN22 GND(INV board)
[ III Outdoor Unit Components ] [5] Control Box of the BC Controller 1. CMB-P1016NU-G, GA, HA Transformer Terminal block for power supply Terminal block for transmission line Relay board BC controller board HWE0913A - 83 -...
IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers ........89 [2] Group Settings and Interlock Settings via the ME Remote Controller ......90 [3] Interlock Settings via the MA Remote Controller ............. 94 [4] Using the built-in Temperature Sensor on the Remote Controller ........95 HWE0913A - 87 -...
[ IV Remote Controller ] IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers There are two types of remote controllers: ME remote controller, which is connected on the indoor-outdoor transmission line, and MA remote controller, which is connected to each indoor unit. 1.
[ IV Remote Controller ] [2] Group Settings and Interlock Settings via the ME Remote Controller 1. Group settings/interlock settings Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the indoor/outdoor unit address.
Page 100
[ IV Remote Controller ] Repeat steps in the previous page to interlock all the indoor units in a group with the LOSSNAY unit. (C) To return to the normal display When all the group settings and interlock settings are made, take the To go back to the normal display, To search for an address, following step to go back to the normal display.
Page 101
[ IV Remote Controller ] (A) To delete group settings (B) To delete interlock settings <Successful completion of deletion> If deletion is successfully completed, will appear in the unit type display window. If the deletion fails, will (Displayed alternately) will be displayed in the room temperature display window. appear in the unit type display - If a transmission error occurs, the selected setting will not be window.
Page 102
[ IV Remote Controller ] [Operation Procedures] 1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal display). 2. Press buttons [CHECK] and [MODE] simultaneously for 2 seconds to go into the operation mode display selection mode under the remote controller function selection mode.
[ IV Remote Controller ] [3] Interlock Settings via the MA Remote Controller 1. LOSSNAY interlock setting (Make this setting only when necessary.) (1) MA Remote Controller (PAR-21MAA) * When the upper controller is connected, make the setting using the upper controller. NOTE: When using LOSSNAY units in conjunction, interlock the addresses of all indoor units within the group and address of LOSSNAY units.
[ IV Remote Controller ] < 2. Search Procedures > To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is connected to it. <Indoor unit address>...
V Electrical Wiring Diagram [1] Electrical Wiring Diagram of the Outdoor Unit ..............99 [2] Electrical Wiring Diagram of the BC Controller .............. 104 [3] Electrical Wiring Diagram of Transmission Booster............114 HWE0913A - 97 -...
[ V Electrical Wiring Diagram ] [3] Electrical Wiring Diagram of Transmission Booster Terminal block for power supply (TB1) 250V 2A Red Red Red Black White White Green/Yellow AC208V/230V Varistor Noise filter Black White White White White Varistor Green Black Stabilized power supply Blue Black...
VI Refrigerant Circuit [1] Refrigerant Circuit Diagram ................... 117 [2] Principal Parts and Functions ..................126 HWE0913A - 115 -...
[ VI Refrigerant Circuit ] [2] Principal Parts and Functions 1. Outdoor unit Part Symbols Notes Usage Specifications Check method name (functions) Com- Adjusts the amount of circulating P72 model pressor (Comp1) refrigerant by adjusting the operat- Low-pressure shell scroll ing frequency based on the oper- compressor ating pressure data...
Page 137
[ VI Refrigerant Circuit ] Part Symbols Notes Usage Specifications Check method name (functions) Heater CH11 Heats the refrigerant in the com- Belt heater Resistance pressor P72 model check 1511 ohm 35W P96, P120, P144 models 1280 ohm 45W 4-way 21S4a Changeover between heating and AC208-230V...
Page 138
[ VI Refrigerant Circuit ] 2. Indoor Unit Part Symbol Notes Usage Specification Check method Name (functions) Linear 1) Adjusts superheat at the DC12V Refer to the section expan- Opening of stepping motor "Continuity Test with a indoor heat exchanger sion valve driving valve 0-(1400) puls- Tester".
Page 139
[ VI Refrigerant Circuit ] 3. BC controller (1) G type Symbols Part Part name Usage Specifications Check method (functions) code Pressure 1) Detects high pressure Pressure sensor (High pres- 2) LEV control 0~4.15 MPa [601psi] Vout 0.5~3.5V sure side) 1 2 3 0.071V/0.098 MPa [14psi] Pressure [MPa]...
Page 140
[ VI Refrigerant Circuit ] (2) GA type Symbols Part Part name Usage Specifications Check method (functions) code Pressure 1) Detects high pressure Pressure sensor (High pres- 2) LEV control 0~4.15 MPa [601psi] Vout 0.5~3.5V sure side) 1 2 3 0.071V/0.098 MPa [14psi] Pressure [MPa] Con-...
Page 141
[ VI Refrigerant Circuit ] (3) GB type Symbols Part Part name Usage Specifications Check method (functions) code Thermistor TH12 LEV control (Superheat) (Bypass = 15k outlet tem- = 3460 0/80 perature) R = 15 3460 TH15 LEV control (Superheat) 0°C[32°F] : 15kohm (Bypass in- 10°C[50°F] :9.7kohm...
Page 142
[ VI Refrigerant Circuit ] (4) HA type Symbols Part Part name Usage Specifications Check method (functions) code Pressure 1) Detects high pressure Pressure sensor (High pres- 2) LEV control 0~4.15 MPa [601psi] Vout 0.5~3.5V sure side) 1 2 3 0.071V/0.098 MPa [14psi] Pressure [MPa] Con-...
Page 143
[ VI Refrigerant Circuit ] (5) HB type Symbols Part Part name Usage Specifications Check method (functions) code Thermistor TH12 LEV control (Superheat) (Bypass = 15k outlet tem- = 3460 0/80 perature) R = 15 3460 TH15 LEV control (Superheat) 0°C[32°F] : 15kohm (Bypass in- 10°C[50°F] :9.7kohm...
VII Control [1] Functions and Factory Settings of the Dipswitches ............137 [2] Controlling the Outdoor Unit ..................144 [3] Controlling BC Controller ....................159 [4] Operation Flow Chart..................... 160 HWE0913A - 135 -...
[ VII Control ] VII Control [1] Functions and Factory Settings of the Dipswitches 1. Outdoor unit (1) Control board Units that re- quire switch Function according to switch setting Switch setting timing setting Switch Function Note.2 Unit address setting Set to 00 or 51-100 with the dial switch Before power on For self-diagnosis/...
Page 147
[ VII Control ] Units that re- quire switch Function according to switch setting Switch setting timing setting Switch Function Note.2 Test run mode: en- SW3-2 disabled SW3-2 enabled Anytime after power on abled/disabled Test run mode: ON/ Sends a test-run Stops all ICs Anytime after power on signal to all IC...
Page 148
[ VII Control ] Units that re- quire switch Function according to switch setting Switch setting timing setting Switch Function Note.2 To be set at the factory. Low-noise mode Capacity priority Low-noise mode Before being energized selection mode(Note 3) To be set at the factory. Backup heating Disabled Enabled...
Page 149
[ VII Control ] 2) PURY-P96, P120, P144TJMU-A Function according to switch Switch setting timing setting Switch Function Anytime after power on Enabling/disabling the following error Error detec- Error detec- detection functions; tion enabled tion disable ACCT/DCCT sensor failure (No load op- (5301 Detail No.
Page 150
[ VII Control ] 2. Function of the switch (Indoor unit) (1) Dipswitches 1) SW1,3 Function according to switch setting Switch setting timing Switch Function Notes Set to ON (built-in sensor on the remote controller) Room temperature Built-in sensor on Indoor unit inlet on All Fresh (PEFY-VMH-F) model units detection position...
Page 151
[ VII Control ] (2) Address switch Actual indoor unit address setting varies in different systems. Refer to the installation manual for the outdoor unit for details on how to make the address setting. Each address is set with a combination of the settings for the 10's digit and 1's digit. (Example) When setting the address to "3", set the 1's digit to 3, and the 10's digit to 0.
Page 152
[ VII Control ] (2) ME remote controller (PAR-F27MEA-US) Set the address of the remote controller with the rotary switch. Rotary switch 10's digit 1's digit (left) (right) Remote controller unit Example: In case of address 108 Address setting range Setting method Main remote controller 101-150...
[ VII Control ] [2] Controlling the Outdoor Unit -1- Outline of Control Method The outdoor units are designated as OC and OS in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large). The setting of outdoor unit can be verified by using the self-diagnosis switch (SW1).
Page 154
[ VII Control ] -5- Bypass Control Bypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the following functions. (1) Bypass solenoid valve (SV1a) (ON = Open) SV1a Operation When each indoor unit compressor startup ON for 4 minutes. After the restoration of thermo or 3 minutes ON for 4 minutes.
Page 155
[ VII Control ] (5) Bypass solenoid valve (SV5b) (ON = Open) SV5c Operation While the unit is stopped Always ON Cooling mode When one or more of the following When the condition on the left is not valves is turned OFF: SV4a through SV4c.
Page 156
[ VII Control ] -7- Defrost Operation Control (1) Starting the defrost operation The defrost cycle will start when all of the three conditions (outside temperature, cumulative compressor operation time, and pipe temperature) under <Condition 1>, <Condition 2>, or <Condition 3> are met. Condition 1 Condition 2 Condition 3...
Page 157
[ VII Control ] (2) Defrost operation Outdoou unit Compressor frequency Model Compressor frequency P72 model 60 Hz P96 model 65 Hz P120, P144 models 65 Hz Outdoor unit fan Stopped SV1a ON (open) P72, P96 models ON (open) P120, P144 models SV5b ON (open) SV5c...
Page 158
[ VII Control ] -8- Refrigerant Recovery Control Refrigerant recovery is performed for each BC port during heating operation to prevent the refrigerant from accumulating in- side the units that are stopped (in the fan mode), in the cooling mode, or in the heating Thermo-OFF mode. It is also performed during cooling operation to prevent an excessive amount of refrigerant from accumulating in the outdoor heat exchanger.
Page 159
[ VII Control ] -9- Capacity Control of Outdoor Fan and Heat Exchanger (1) Control method Depending on the capacity required, the rotation speed of the outdoor unit fan is controlled by the inverter to keep a constant condensing temperature of (outside temperature +10°C [50°F]) during cooling operation and a constant evaporation temper- ature of (0°C [32°F] =0.71 <Pa [103psi]) during heating operation.
Page 160
[ VII Control ] -10- Control at Initial Start-up When started up for the first time before 12 hours have elapsed after power on, the unit goes into the initial startup mode. At the completion of the initial operation mode on the OC and OS, they will go into the normal control mode. 1.
Page 161
[ VII Control ] (2) P168, P192, P216, P240, P264, P288 models Initial startup mode starts. The compressor on the OC starts up. 60Hz The total operating load of the indoor unit after 5 minutes of operation is P96 or above. (*1 Qj The compressor on the OC starts up.
Page 162
[ VII Control ] -11- Emergency Operation Mode 1. Problems with the outdoor unit The P168 through P240 models of unit have a mode that allows the outdoor unit to perform an emergency operation when the other outdoor unit in the system malfunctions. This mode can be started by performing an error reset via the remote controller.
Page 163
[ VII Control ] 2. Communication circuit failure or when some of the outdoor units are turned off This is a temporary operation mode in which the outdoor unit that is not in trouble operates when communication circuit failure occurs or when some of the outdoor units are turned off. (1) Starting the emergency operation (When the OC is in trouble) 1) When an error occurs, the error source and the error code appear on the display on the remote controller.
Page 164
[ VII Control ] -12- Control Method The control system configuration for the PURY models is shown in the chart below. Daisy-chained Non-polar 2-wire Data signal exchange non-polar 2-wire serial communication between system equipment method transmission line 16-bit CPU Calculation, processing microcomputer operation processing System control...
Page 165
[ VII Control ] -13- Cooling/heating Circuit Control and General Function of System Equipment Operation Schematic diagram of refrigerant circuit Schematic diagram of refrigerating cycle Two-phase status Liquid 4-way valve Check valve Selector valve Low- Pressure pressure Low-pressure two-phase pipe Low-pressure Liquid Cooling...
Page 166
[ VII Control ] -14- Operation Mode (1) Indoor unit operation mode The operation mode can be selected from the following 6 modes using the remote controller. Cooling mode Heating mode Dry mode Automatic cooling/heating mode Fan mode Stopping mode (2) Outdoor unit operation mode Cooling only mode All indoor units in operation are in cooling mode.
Page 167
[ VII Control ] -15- DEMAND Control Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units. When DIP SW4-4 is set to ON, the 4-step DEMAND control is enabled. Eight-step demand control is possible in the system with two outdoor units. Refer to Chapter II [3] 2.
[ VII Control ] [3] Controlling BC Controller 1. Control of SV A, SV B, and SV A, SV B, and SV C turn on or off depending on the operation mode of the branch. Mode Cooling Heating Stopped Defrost SV A Port SV B...
[ VII Control ] [4] Operation Flow Chart 1. Mode determination flowchart (1) Indoor unit (cooling, heating, dry, fan mode) Start Normal operation Error Breaker Stop turned on Operation SW turned on *Note 1 1. Protection function self-holding cancelled. 2. Indoor unit LEV fully closed. *Note 2 Remote controller Error mode...
Page 170
[ VII Control ] (2) Outdoor unit (cooling only, heating only, cooling main and heating main modes) Start Normal operation Error Breaker turned on Unit in the stopped state "HO" / "PLEASE WAIT" blinks on the remote controller *Note 1 Indoor units registered to the remote controller...
Page 171
[ VII Control ] (3) BC controller (cooling only, heating only, cooling main and heating main modes) Start Normal operation Error Breaker turned on Unit in the stopped state Operation command 1. Determination of operation mode Protection function (Cooling only, Heating only, Mixture self-holding cancelled.
Page 172
[ VII Control ] 2. Operations in each mode (1) Cooling operation Cooling operation Normal operation During test run mode 4-way valve OFF Unit in the stopped state Indoor unit fan *Note 1 operation Test run mode Thermostat 3-minute restart prevention 1.
Page 173
[ VII Control ] (2) Heating operation Normal operation Heating operation Defrost operation *Note 1,2 Unit in the stopped state Defrost operation During test run mode 4-way valve ON 4-way valve OFF Test run mode 1. Indoor unit fan stop 2.
Page 174
[ VII Control ] (3) Dry operation Dry operation Normal operation Thermostat ON 4-way valve OFF Unit in the stopped state Test run mode *Note 2 Thermostat ON Suction temperature 18 C[64 F] *Note 1 1. Indoor unit fan stop 1.
VIII Test Run Mode [1] Items to be checked before a Test Run ................. 169 [2] Test Run Method ......................170 [3] Operating Characteristic and Refrigerant Amount ............171 [4] Adjusting the Refrigerant Amount .................. 171 [5] Refrigerant Amount Adjust Mode................... 174 [6] The following symptoms are normal.
[ VIII Test Run Mode ] VIII Test Run Mode [1] Items to be checked before a Test Run (1) Check for refrigerant leak and loose cables and connectors. (2) Measure the insulation resistance between the power supply terminal block and the ground with a 500V megger and make sure it reads at least 1.0Mohm.
[ VIII Test Run Mode ] [2] Test Run Method The figure shows an MA remote controller (PAR-21MAA). ON/OFF button Set Temperature buttons Down Fan Speed button TIME SUN MON TUE WED THU FRI SAT TIMER AFTER AFTER ERROR CODE FUNCTION FILTER WEEKLY...
[ VIII Test Run Mode ] [3] Operating Characteristic and Refrigerant Amount It is important to have a clear understanding of the characteristics of refrigerant and the operating characteristics of air conditioners before attempting to adjust the refrigerant amount in a given system. 1.
Page 181
[ VIII Test Run Mode ] 3. Amount of refrigerant to be added The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units. The amount necessary for extended pipe (field piping) is not included and must be added on site. Outdoor unit model P120 P144...
Page 182
[ VIII Test Run Mode ] (2) Example Outdoor unit 1 Outdoor unit 2 Branch joint kit Indoor Branch joint (CMY-Y202-G2) (CMY-Y102L-G2) BC controller(HB) (CMY-Y102S-G2) BC controller(GA) H H′ Branch joint Reducer BC controller(HB) (CMY-Y102S-G2) (Supplied with the BC Controller) Junction pipe kit (CMY-R160-J) (Optional accessory)
[ VIII Test Run Mode ] [5] Refrigerant Amount Adjust Mode 1. Procedures Follow the procedures below to add or extract refrigerant as necessary depending on the operation mode. When the function switch (SW4-3) on the main board on the outdoor unit (OC only) is turned to ON, the unit goes into the refrigerant amount adjust mode, and the following sequence is followed.
Page 184
[ VIII Test Run Mode ] Start Turn on SW4-3 on the OC. Operation of the Refrigerant Amount Adjust Mode Put all indoor units in the test run mode When the unit is the refrigerant amount adjust mode, the LEV on the and run the units in cooling mode.
[ VIII Test Run Mode ] [6] The following symptoms are normal. Remote controller Symptoms Cause display The indoor unit does not start "Cooling (heating)" The unit cannot perform a heating (cooling) operation when other indoor icon blinks on the units are performing a cooling (heating) operation.
[ VIII Test Run Mode ] [7] Standard Operation Data (Reference Data) 1. Single unit (1) Cooling only operation Outdoor unit model Operation PURY-P72TJMU-A PURY-P96TJMU-A Model name of BC controller CMB-P104NU-G CMB-P104NU-G 26.7°C/19.4°C 26.7°C/19.4°C Indoor Ambient [80 °F/67 °F] [80 °F/67 °F] tempera- DB/WB 35°C/í...
Page 187
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P120TJMU-A PURY-P144TJMU-A Model name of BC controller CMB-P104NU-G CMB-P108NU-GA 26.7°C/19.4°C 26.7°C/19.4°C Indoor Ambient [80 °F/67 °F] [80 °F/67 °F] tempera- DB/WB 35°C/í 35°C/í ture Outdoor [95 °F/í] [95 °F/í] No. of connected units Unit Indoor unit No.
Page 188
[ VIII Test Run Mode ] (2) Heating only operation Outdoor unit model Operation PURY-P72TJMU-A PURY-P96TJMU-A Model name of BC controller CMB-P104NU-G CMB-P104NU-G 21.1°C/í 21.1°C/í Indoor Ambient [70 °F/-] [70 °F/-] tempera- DB/WB 8.3°C/6.1°C 8.3°C/6.1°C ture Outdoor [47 °F/43 °F] [47 °F/43 °F] No.
Page 189
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P120TJMU-A PURY-P144TJMU-A Model name of BC controller CMB-P104NU-G CMB-P108NU-GA 21.1°C/í 21.1°C/í Indoor Ambient [70 °F/í] [70 °F/í] tempera- DB/WB 8.3°C/6.1°C 8.3°C/6.1°C ture Outdoor [47 °F/43 °F] [47 °F/43 °F] No. of connected units Unit Indoor unit No.
Page 190
[ VIII Test Run Mode ] 2. 2-unit combination (1) Cooling only operation Outdoor unit model Operation PURY-P168TSJMU-A PURY-P96TJMU-A PURY-P72TJMU-A Model name of BC controller CMB-P108NU-GA Ambient Indoor 26.7°C/19.4°C [80 °F/67 °F] tempera- DB/WB Outdoor 35°C/í [95 °F/í] ture No. of connected units Unit Indoor unit No.
Page 191
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P192TSJMU-A PURY-P96TJMU-A PURY-P96TJMU-A Model name of BC controller CMB-P108NU-GA Ambient Indoor 26.7°C/19.4°C [80 °F/67 °F] tempera- DB/WB Outdoor 35°C/í [95 °F/í] ture No. of connected units Unit Indoor unit No. of units in operation Model 30/30/30/30/36/36 Operating...
Page 192
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P216TSJMU-A PURY-P120TJMU-A PURY-P96TJMU-A Model name of BC controller CMB-P1013NU-GA Ambient Indoor 26.7°C/19.4°C [80 °F/67 °F] tempera- DB/WB Outdoor 35°C/í [95 °F/í] ture No. of connected units Unit Indoor unit No. of units in operation Model 36/36/36/36/36/36 Operating...
Page 193
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P240TSJMU-A PURY-P120TJMU-A PURY-P120TJMU-A Model name of BC controller CMB-P1013NU-GA Ambient Indoor 26.7°C/19.4°C [80 °F/67 °F] tempera- DB/WB Outdoor 35°C/í [95 °F/í] ture No. of connected units Unit Indoor unit No. of units in operation Model 24/36/36/36/36/36/36 Operating...
Page 194
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P264TSJMU-A PURY-P144TJMU-A PURY-P120TJMU-A Model name of BC controller CMB-P1016NU-HA Ambient Indoor 26.7°C/19.4°C [80 °F/67 °F] tempera- DB/WB Outdoor 35°C/í [95 °F/í] ture No. of connected units Unit Indoor unit No. of units in operation Model 24/24/36/36/36/36/36/36 Operating...
Page 195
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P288TSJMU-A PURY-P144TJMU-A PURY-P144TJMU-A Model name of BC controller CMB-P1016NU-HA Ambient Indoor 26.7°C/19.4°C [80 °F/67 °F] tempera- DB/WB Outdoor 35°C/í [95 °F/í] ture No. of connected units Unit Indoor unit No. of units in operation Model 36/36/36/36/36/36/36/36 Operating...
Page 196
[ VIII Test Run Mode ] (2) Heating only operation Outdoor unit model Operation PURY-P168TSJMU-A PURY-P96TJMU-A PURY-P72TJMU-A Model name of BC controller CMB-P108NU-GA Ambient Indoor 21.1°C/í [70 °F/í] tempera- DB/WB Outdoor 8.3°C/6.1°C [47°F/43°F] ture No. of connected units Unit Indoor unit No.
Page 197
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P192TSJMU-A PURY-P96TJMU-A PURY-P96TJMU-A Model name of BC controller CMB-P108NU-GA Ambient Indoor 21.1°C/í [70 °F/í] tempera- DB/WB Outdoor 8.3°C/6.1°C [47°F/43°F] ture No. of connected units Unit Indoor unit No. of units in operation Model 30/30/30/30/36/36 Operating...
Page 198
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P216TSJMU-A PURY-P120TJMU-A PURY-P96TJMU-A Model name of BC controller CMB-P1013NU-GA Ambient Indoor 21.1°C/í [70 °F/í] tempera- DB/WB Outdoor 8.3°C/6.1°C [47°F/43°F] ture No. of connected units Unit Indoor unit No. of units in operation Model 36/36/36/36/36/36 Operating...
Page 199
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P240TSJMU-A PURY-P120TJMU-A PURY-P120TJMU-A Model name of BC controller CMB-P1013NU-GA Ambient Indoor 21.1°C/í [70 °F/í] tempera- DB/WB Outdoor 8.3°C/6.1°C [47°F/43°F] ture No. of connected units Unit Indoor unit No. of units in operation Model 24/36/36/36/36/36/36 Operating...
Page 200
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P264TSJMU-A PURY-P144TJMU-A PURY-P120TJMU-A Model name of BC controller CMB-P1016NU-HA Ambient Indoor 21.1°C/í [70 °F/í] tempera- DB/WB Outdoor 8.3°C/6.1°C [47°F/43°F] ture No. of connected units Unit Indoor unit No. of units in operation Model 24/24/36/36/36/36/36/36 Operating...
Page 201
[ VIII Test Run Mode ] Outdoor unit model Operation PURY-P288TSJMU-A PURY-P144TJMU-A PURY-P144TJMU-A Model name of BC controller CMB-P1016NU-HA Ambient Indoor 21.1°C/í [70 °F/í] tempera- DB/WB Outdoor 8.3°C/6.1°C [47°F/43°F] ture No. of connected units Unit Indoor unit No. of units in operation Model 36/36/36/36/36/36/36/36 Operating...
IX Troubleshooting [1] Error Code Lists ......................195 [2] Responding to Error Display on the Remote Controller..........199 [3] Investigation of Transmission Wave Shape/Noise............285 [4] Troubleshooting Principal Parts ..................288 [5] Refrigerant Leak ......................333 [6] Compressor Replacement Instructions................335 [7] Servicing the BC controller ....................
[ IX Troubleshooting ] IX Troubleshooting [1] Error Code Lists Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code 4300 Serial communication error/Panel communication 0403 4305 error (Note) 1102 1202 Discharge temperature fault 1301 Low pressure fault 1302...
Page 205
[ IX Troubleshooting ] Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code Indoor unit pipe tempera- ture (TH22) Temperature sensor 5102 1217 fault OA processing unit pipe temperature (TH2) Indoor unit gas-side pipe temperature (TH23) OA processing unit gas- Temperature sensor...
Page 207
[ IX Troubleshooting ] The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to inverter on fan inverter. Example Code 4225 (detail code 108): Bus voltage drop in the fan inverter system Code 4230 : Heatsink overheat protection in the inverter system The last digit Inverter system...
[ IX Troubleshooting ] [2] Responding to Error Display on the Remote Controller 1. Error Code 0403 (TJMU-A) Serial communication error 2. Error definition and error detection method Serial communication error between the control board and the INV board on the compressor, and between the control board and the Fan board Detail code 01: Between the control board and the INV board Detail code 05: Between the control board and the Fan board...
Page 209
[ IX Troubleshooting ] 1. Error Code 0403 (YJMU-A) Serial communication error 2. Error definition and error detection method Serial communication error between the control board and the INV board on the compressor, and between the control board and the Fan board Detail code 01: Between the control board and the INV board Detail code 05: Between the control board and the Fan board 3.
Page 210
[ IX Troubleshooting ] 1. Error Code 1102 Discharge temperature fault 2. Error definition and error detection method 1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
Page 211
[ IX Troubleshooting ] 1. Error Code 1301 Low pressure fault 2. Error definition and error detection method When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before start-up, the operation immediately stops. 3.
Page 212
[ IX Troubleshooting ] 1. Error Code 1302 High pressure fault 1 (Outdoor unit) 2. Error definition and error detection method 1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out- door stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
Page 213
[ IX Troubleshooting ] 1. Error Code 1302 High pressure fault 2 (Outdoor unit) 2. Error definition and error detection method If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an abnormal stop, and error code "1302"...
Page 214
[ IX Troubleshooting ] 1. Error Code 2500 Drain sensor submergence (Models with a drain sensor) 2. Error definition and error detection method 1) If an immersion of the drain sensor in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage.
Page 215
[ IX Troubleshooting ] 1. Error Code 2500 Drain sensor submergence (Models with a float switch) 2. Error definition and error detection method 1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage.
Page 216
[ IX Troubleshooting ] 1. Error Code 2502 Drain pump fault (Models with a drain sensor) 2. Error definition and error detection method 1) Make the drain sensor thermistor self-heat. If the temperature rise is small, it is interpreted that the sensor is immersed in water.
Page 217
[ IX Troubleshooting ] 1. Error Code 2502 Drain pump fault (Models with a float switch) 2. Error definition and error detection method 1) The immersion of sensor tip in water is detected by the ON/OFF signal from the float switch. Submergence of the sensor When it is detected that the float switch has been ON for 15 seconds, it is interpreted that the sensor tip is immersed in water.
Page 218
[ IX Troubleshooting ] 1. Error Code 2503 Drain sensor (Thd) fault 2. Error definition and error detection method If the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary error, and the unit goes into the 3-minute restart delay mode.
Page 219
[ IX Troubleshooting ] 1. Error Code 2600 Water leakage 2. Cause, check method and remedy Check that water does not leak from the pipes in such as the humidifier. 1. Error Code 2601 Water supply cutoff 2. Cause, check method and remedy Cause Check method and remedy The water tank of the humidifier is empty.
Page 220
[ IX Troubleshooting ] 1. Error Code 3121 Out-of-range outside air temperature 2. Error definition and error detection method When the thermistor temperature of -28°C[-18°F] or below has continuously been detected for 3 minutes during heating op- eration (during compressor operation), the unit makes an error stop and "3121" appears on the display. (Use the OC therm- istor temperature to determine when two outdoor units are in operation.) The compressor restarts when the thermistor temperature is -26°C[-15°F] or above (both OC and OS) during error stop.
Page 221
[ IX Troubleshooting ] 1. Error Code 4102 (TJMU-A) Open phase 2. Error definition and error detection method An open phase of the power supply (L1 phase, L2 phase) was detected at power on. The L3 phase current is outside of the specified range. The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
Page 222
[ IX Troubleshooting ] 1. Error Code 4102 (YJMU-A) Open phase 2. Error definition and error detection method An open phase of the power supply (L1 phase, L2 phase) was detected at power on. The L3 phase current is outside of the specified range. The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
Page 223
[ IX Troubleshooting ] 1. Error Code 4106 <Transmission power supply fault Error detail code FF (Outdoor unit)> 2. Error definition and error detection method Transmission power output failure 3. Cause 1) Wiring failure 2) Transmission power supply cannot output voltage because overcurrent was detected. 3) Voltage cannot be output due to transmission power supply problem.
Page 224
[ IX Troubleshooting ] 1. Error Code 4109 Indoor unit fan operation error 2. Error definition and error detection method 1) During operation, it has been continuously detected for 100 seconds that the auxiliary relay (X13) for fan fault detection is not excited.
Page 225
[ IX Troubleshooting ] 1. Error Code (TJMU-A) 4115 Power supply signal sync error 2. Error definition and error detection method The frequency cannot be determined when the power is switched on. 3. Cause, check method and remedy Cause Check method and remedy Power supply error Check the voltage of the power supply terminal block (TB1).
Page 226
[ IX Troubleshooting ] 1. Error Code 4116 RPM error/Motor error 2. Error definition and error detection method LOSSNAY The motor keep running even if the power is OFF. The thermal overload relay is ON. (Only for the three-phase model) Indoor unit If detected less than 180rpm or more than 2000rpm, the indoor unit will restart and keep running for 3 minutes.If detected again, the display will appear.
Page 227
[ IX Troubleshooting ] 1. Error Code 4220 (TJMU-A) 4225 Abnormal bus voltage drop (Detail code 108) 2. Error definition and error detection method If Vdc 160V or less is detected during Inverter operation. (S/W detection) 3. Cause, check method and remedy (1) Power supply environment Find out if there was a (momentary) power failure.
Page 228
[ IX Troubleshooting ] 1. Error Code 4220 (YJMU-A) 4225 Abnormal bus voltage drop (Detail code 108) 2. Error definition and error detection method If Vdc 289V or less is detected during Inverter operation. (S/W detection) 3. Cause, check method and remedy (1) Power supply environment Find out if there was a (momentary) power failure.
Page 229
[ IX Troubleshooting ] 1. Error Code 4220 (TJMU-A) 4225 Abnormal bus voltage rise (Detail code 109) 2. Error definition and error detection method If Vdc 400V is detected during inverter operation. 3. Cause, check method and remedy (1) Different voltage connection Check the power supply voltage on the power supply terminal block (TB1).
Page 230
[ IX Troubleshooting ] 1. Error Code 4220 (TJMU-A) (P96, P120, P144 models only) 4225 VDC error (Detail code 110) 2. Error definition and error detection method Bus voltage abnormality If Vdc 400V or Vdc 160V is detected. (H/W detection) 3.
Page 231
[ IX Troubleshooting ] 1. Error Code 4220 (TJMU-A) 4225 Logic error (Detail code 111) 2. Error definition and error detection method H/W error If only the H/W error logic circuit operates, and no identifiable error is detected. 3. Cause, Check method and remedy In the case of 4220 Cause Check method and remedy...
Page 232
[ IX Troubleshooting ] 1. Error Code 4220 (YJMU-A) 4225 Logic error (Detail code 111) 2. Error definition and error detection method H/W error If only the H/W error logic circuit operates, and no identifiable error is detected. 3. Cause, Check method and remedy In the case of 4220 Cause Check method and remedy...
Page 233
[ IX Troubleshooting ] 1. Error Code 4230 (TJMU-A) Heatsink overheat protection 2. Error definition and error detection method When the heat sink temperature (THHS) remains at or above TOH is detected. Model P72 model 100°C [212°F] P96, P120, P144 models 90°C [194°F] 3.
Page 234
[ IX Troubleshooting ] 1. Error Code 4230 (YJMU-A) Heatsink overheat protection 2. Error definition and error detection method When the heat sink temperature (THHS) remains at or above 100°C [212°F] is detected. 3. Cause, check method and remedy Cause Check method and remedy Fan board failure Refer to IX [4] -7- (2) [6].(page 323)
Page 235
[ IX Troubleshooting ] 1. Error Code 4240 (TJMU-A) Overload protection 2. Error definition and error detection method If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes or more during inverter operation.
Page 236
[ IX Troubleshooting ] 1. Error Code 4240 (YJMU-A) Overload protection 2. Error definition and error detection method If the output current of "(Iac) >Imax (Arms)" or "THHS > 95°C [203°F] " is continuously detected for 10 minutes or more during inverter operation.
Page 237
[ IX Troubleshooting ] 1. Error Code 4250 (TJMU-A) 4255 IPM error (Detail code 101) 2. Error definition and error detection method In the case of 4250 P72 model Overcurrent is detected by the overcurrent detection resistor (RSH) on the INVboard. P96, P120, P144 models IPM error signal is detected.
Page 238
[ IX Troubleshooting ] 1. Error Code 4250 (YJMU-A) 4255 IPM error (Detail code 101) 2. Error definition and error detection method In the case of 4250 Overcurrent is detected by the overcurrent detection resistor (RSH) on the INV board. In the case of 4255 IPM error signal is detected.
Page 239
[ IX Troubleshooting ] 1. Error Code 4250 (TJMU-A) DCCT overcurrent (H/W detection) (Detail code 103) Instantaneous overcurrent (Detail code 106) Overcurrent (effective value) (Detail code 107) 2. Error definition and error detection method P72 model Overcurrent 88 Apeak or 42 Arms and above is detected by the current sensor. P96, P120, P144 models Overcurrent 128 Apeak or 60 Arms and above is detected by the current sensor.
Page 240
[ IX Troubleshooting ] 1. Error Code 4250 (YJMU-A) Instantaneous overcurrent (Detail code 106) Overcurrent (effective value) (Detail code 107) 2. Error definition and error detection method P72 model Overcurrent 94 Apeak or 22 Arms and above is detected by the current sensor. P96, P120, P144 models Overcurrent 94 Apeak or 35 Arms and above is detected by the current sensor.
Page 241
[ IX Troubleshooting ] 1. Error Code 4250 4255 Overcurrent error due to short-circuited motor (Detail code 105) 2. Error definition and error detection method When a short is detected on the load side just before starting the inverter operation. 3.
Page 242
[ IX Troubleshooting ] 1. Error Code 5101 Return air temperature sensor (TH21) fault (Indoor unit) Return air temperature sensor (TH4) fault (OA processing unit) 5102 Pipe temperature sensor (TH22) fault (Indoor unit) Pipe temperature sensor (TH2) fault (OA processing unit) 5103 Gas-side pipe temperature sensor (TH23) fault (Indoor unit) Gas-side pipe temperature sensor (TH3) fault (OA processing unit)
Page 243
[ IX Troubleshooting ] 1. Error Code 5103 Heat exchanger outlet temperature sensor (TH3) fault (Outdoor unit) 5104 Discharge temperature sensor (TH4) fault (Outdoor unit) 5105 Accumulator inlet temperature sensor (TH5) fault (Outdoor unit) 5106 Heat exchanger inlet temperature sensor (TH6) fault (Outdoor unit) 5107 Outside temperature sensor (TH7) fault (Outdoor unit) 2.
Page 244
[ IX Troubleshooting ] 1. Error Code 5110 (TJMU-A) Heatsink temperature sensor (THHS) fault (Detail code 01) 2. Error definition and error detection method When a short or an open of THHS is detected just before or during the inverter operation. 3.
Page 245
[ IX Troubleshooting ] 1. Error Code 5111 Liquid inlet temperature sensor (TH11) fault (BC controller) 5112 Bypass outlet temperature sensor (TH12) fault (BC controller) 5115 LEV3 outlet temperature sensor (TH15) fault (BC controller) 5116 LEV3 inlet temperature sensor (TH16) fault (BC controller) 2.
Page 246
[ IX Troubleshooting ] 1. Error Code 5201 High-pressure sensor fault (63HS1) 2. Error definition and error detection method If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the outdoor unit stops once, turns to anti- restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more.
Page 247
[ IX Troubleshooting ] 1. Error Code 5201 High-pressure sensor fault (Outdoor unit HPS/BC controller PS1) 5203 Intermediate pressure sensor fault (BC controller PS3) 2. Error definition and error detection method When a pressure sensor reading of 4.06 MPa [589 psi] or above is detected, error codes "5201" and "5203" will appear. The unit will continue its operation by using other sensors as a backup.
Page 248
[ IX Troubleshooting ] 1. Error Code 5301 (TJMU-A) ACCT sensor fault (Detail code 115) 2. Error definition and error detection method When the formula "output current < 2 Arms" remains satisfied for 10 seconds while the inverter is in operation. 3.
Page 249
[ IX Troubleshooting ] 1. Error Code 5301 (YJMU-A) ACCT sensor fault (Detail code 115) 2. Error definition and error detection method When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation. 3.
Page 250
[ IX Troubleshooting ] 1. Error Code 5301 (TJMU-A) (P96, P120, P144 models only) DCCT sensor circuit fault (Detail code118) 2. Error definition and error detection method When an error value is detected with the DCCT detection circuit just before the inverter starts 3.
Page 251
[ IX Troubleshooting ] 1. Error Code 5301 (YJMU-A) Open-circuited IPM/Loose ACCT connector (Detail code 119) 2. Error definition and error detection method Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup. 3. Cause, check method and remedy Cause Check method and remedy Inverter output wiring problem...
Page 252
[ IX Troubleshooting ] 1. Error Code 5301 (YJMU-A) Faulty ACCT wiring (Detail code 120) 2. Error definition and error detection method Presence of target current cannot be detected during the self-diagnostic operation immediately before startup. 3. Cause, check method and remedy Cause Check method and remedy Inverter output wiring problem...
Page 253
[ IX Troubleshooting ] 1. Error Code 5401 Temperature sensor fault 2. Error definition and error detection method A short-circuit or an open-circuit of the humidity sensor is detected during operation. 3. Cause, check method and remedy Cause Check method and remedy Connector contact failure (CN30) (Loose con- Check the connector for proper contact.
Page 254
[ IX Troubleshooting ] 1. Error Code 5701 Loose float switch connector 2. Error definition and error detection method Detection of the disconnected float switch (open-phase condition) during operation 3. Cause, check method and remedy (1) CN4F disconnection or contact failure Check for disconnection of the connector (CN4F) on the indoor unit control board.
Page 255
[ IX Troubleshooting ] 1. Error Code 6600 Address overlaps 2. Error definition and error detection method An error in which signals from more than one indoor units with the same address are received The address and attribute that appear on the remote controller indicate the controller that detected the error. 3.
Page 256
[ IX Troubleshooting ] 1. Error Code 6602 Transmission processor hardware error 2. Error definition and error detection method Although "0" was surely transmitted by the transmission processor, "1" is displayed on the transmission line. The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Page 257
[ IX Troubleshooting ] 1. Error Code 6603 Transmission line bus busy error 2. Error definition and error detection method Generated error when the command cannot be transmitted for 4-10 minutes in a row due to bus-busy Generated error when the command cannot be transmitted to the transmission line for 4-10 minutes in a row due to noise The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Page 258
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 259
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 260
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 261
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 262
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 263
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 264
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 265
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 266
[ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
Page 267
[ IX Troubleshooting ] 1. Error Code 6608 No response error 2. Error definition and error detection method When no response command is returned although acknowledgement (ACK) is received after transmission, an error is detect- When the data is transmitted 10 times in a row with 3 seconds interval, an error is detected on the transmission side. The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
Page 268
[ IX Troubleshooting ] 1. Error Code 6831 MA controller signal reception error (No signal reception) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. No proper data has been received for 3 minutes. 3.
Page 269
[ IX Troubleshooting ] 1. Error Code 6832 MA remote controller signal transmission error (Synchronization error) 2. Error definition and error detection method MA remote controller and the indoor unit is not done properly. Failure to detect opening in the transmission path and unable to send signals Indoor unit : 3 minutes Remote controller : 6 seconds 3.
Page 270
[ IX Troubleshooting ] 1. Error Code 6833 MA remote controller signal transmission error (Hardware error) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. An error occurs when the transmitted data and the received data differ for 30 times in a row. 3.
Page 271
[ IX Troubleshooting ] 1. Error Code 6834 MA controller signal reception error (Start bit detection error) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. No proper data has been received for 2 minutes. 3.
Page 272
[ IX Troubleshooting ] 1. Error Code 7100 Total capacity error 2. Error definition and error detection method The model total of indoor units in the system with one outdoor unit exceeds limitations. 3. Error source, cause, check method and remedy, Error source Cause Check method and remedy...
Page 273
[ IX Troubleshooting ] 1. Error Code 7101 Capacity code setting error 2. Error definition and error detection method Connection of incompatible (wrong capacity code) indoor unit or outdoor unit 3. Error source, cause, check method and remedy Error source Cause Check method and remedy Outdoor unit...
Page 274
[ IX Troubleshooting ] 1. Error Code 7102 Wrong number of connected units 2. Error definition and error detection method The number of connected indoor units is "0" or exceeds the allowable value. 3. Error source, cause, check method and remedy Error source Cause Check method and remedy...
Page 275
[ IX Troubleshooting ] 1. Error Code 7105 Address setting error 2. Error definition and error detection method Erroneous setting of OC unit address Erroneous setting of BC controller address 3. Cause, check method and remedy Error source Cause Check method and remedy Outdoor unit Erroneous setting of OC unit address Check that the outdoor unit and BC controller...
Page 276
[ IX Troubleshooting ] 1. Error Code 7107 Port setting error 2. Error definition and error detection method The port with wrong number is connected to the indoor unit.The model total connected to the port is greater than the specifi- cation.
Page 277
[ IX Troubleshooting ] 1. Error Code 7110 Connection information signal transmission/reception error 2. Error definition and error detection method The given indoor unit is inoperable because it is not properly connected to the outdoor unit in the same system. 3.
Page 278
[ IX Troubleshooting ] 1. Error Code 7113 Function setting error (incorrect resistor connection) 2. Error source, cause, check method and remedy Error source Cause Check method and remedy Outdoor unit Wiring fault (Detail code 15) Loose connectors, short-circuit, con- Check the connector CNTYP5 on the control board for tact failure proper connection.
Page 279
[ IX Troubleshooting ] 1. Error Code 7117 Model setting error 2. Error source, cause, check method and remedy Error source Cause Check method and remedy Outdoor unit Wiring fault (Detail code 15) Loose connectors, short-circuit, con- Check the connector CNTYP5 on the control board for tact failure proper connection.
Page 280
[ IX Troubleshooting ] 1. Error Code 7130 Incompatible unit combination 2. Error definition and error detection method The check code will appear when the indoor units for use with a different type of refrigerant or incompatible units are connect- 3.
Page 281
[ IX Troubleshooting ] -1- Troubleshooting according to the remote controller malfunction or the external input error In the case of MA remote controller 1. Phenomena Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start run- ning.(Power indicator does not appear on the screen.) (1) Cause...
Page 282
[ IX Troubleshooting ] In the case of MA remote controller 2. Phenomena When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off, and the display lights out immediately, and the unit stops. (1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit.
Page 283
[ IX Troubleshooting ] In the case of MA remote controller 3. Phenomena "HO" or "PLEASE WAIT" display on the remote controller does not disappear, and no operation is performed even if the button is pressed. ("HO" or "PLEASE WAIT" display will normally turn off 5 minutes later after the power on.) (1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit.
Page 284
[ IX Troubleshooting ] Flow chart Even if the operation button on the remote controller is pressed, the indoor and the outdoor units do not start running. HWE0913A - 275 -...
Page 285
[ IX Troubleshooting ] In case of ME remote controller 1. Phenomena Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start running. (Power indicator does not appear on the screen.) (1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit.
Page 286
[ IX Troubleshooting ] In case of ME remote controller 2. Phenomena When the remote controller operation SW is turned on, a temporary operation display is indicated, and the display lights out immediately. (1) Cause 1) The power is not supplied to the indoor unit. The main power of the indoor unit (AC208/230V) is not on.
Page 287
[ IX Troubleshooting ] In case of ME remote controller 3. Phenomena "HO" display on the remote controller does not disappear, and no operation is performed even if the button is pressed. (1) Cause Without using MELANS 1) Outdoor unit address is set to "00" 2) A wrong address is set.
Page 288
[ IX Troubleshooting ] In case of ME remote controller 4. Phenomena "88" appears on the remote controller when the address is registered or confirmed. (1) Cause, check method and remedy Cause Check method and remedy An error occurs when the address is registered or con- firmed.
Page 289
[ IX Troubleshooting ] Both for MA remote controller and ME remote controller 1. Phenomena Although cooling operation starts with the normal remote controller display, the capacity is not enough (1) Cause, check method and remedy Cause Check method and remedy Compressor frequency does not rise sufficiently.
Page 290
[ IX Troubleshooting ] Cause Check method and remedy Long piping length Check the piping length to determine if it is contrib- The cooling capacity varies greatly depending on the uting to performance loss. pressure loss. (When the pressure loss is large, the Piping pressure loss can be estimated from the cooling capacity drops.) temperature difference between the indoor unit...
Page 291
[ IX Troubleshooting ] 2. Phenomena Although heating operation starts with the normal remote controller display, the capacity is not enough. (1) Cause, check method and remedy Cause Check method and remedy Compressor frequency does not rise sufficiently. Check pressure difference between the detected Faulty detection of pressure sensor.
Page 292
[ IX Troubleshooting ] Cause Check method and remedy Indoor unit LEV malfunction Refer to the page of LEV troubleshooting ( [4] -5- Insufficient refrigerant flows due to LEV malfunction ).(page 297) (not enough opening). Temperature reading error on the indoor unit piping Check the thermistor.
Page 293
[ IX Troubleshooting ] 3. Phenomena Outdoor unit stops at times during operation. (1) Cause, check method and remedy Cause Check method and remedy The first stop is not considered as an error, as the Check the mode operated in the past by displaying unit turns to anti-restart mode for 3 minutes as a pre- preliminary error history on LED display with SW1.
[ IX Troubleshooting ] [3] Investigation of Transmission Wave Shape/Noise 1. M-NET transmission Control is performed by exchanging signals between the outdoor unit and the indoor unit (ME remote controller) through M- NET transmission. Noise interference on the transmission line will interrupt the normal transmission, leading to erroneous op- eration.
Page 295
[ IX Troubleshooting ] (3) Check method and remedy 1) Measures against noise Check the followings when noise exists on the wave or the errors described in (1) occur. Error code definition Remedy Check that the wiring 1. The transmission line and Isolate the transmission line from the power line (5cm [1-31/32"] or work is performed ac- the power line are not...
Page 296
[ IX Troubleshooting ] 2. MA remote controller transmission The communication between the MA remote controller and the indoor unit is performed with current tone burst. (1) Symptoms caused by noise interference on the transmission line If noise is generated on the transmission line, and the communication between the MA remote controller and the indoor unit is interrupted for 3 minutes in a row, MA transmission error (6831) will occur.
[ IX Troubleshooting ] [4] Troubleshooting Principal Parts -1- High-Pressure Sensor (63HS1, PS1, PS3) 1. Compare the pressure that is detected by the high pressure sensor, and the high-pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the high- pressure sensor appears on the LED1 on the control board.
Page 298
[ IX Troubleshooting ] -2- Low-Pressure Sensor (63LS) 1. Compare the pressure that is detected by the low pressure sensor, and the low pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the low- pressure sensor appears on the LED1 on the control board.
Page 299
[ IX Troubleshooting ] -3- Solenoid Valve Check whether the output signal from the control board and the operation of the solenoid valve match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED's. Each LED shows whether the relays for the following parts are ON or OFF.
Page 303
[ IX Troubleshooting ] (5) In the case of SV5b (Bypass valve) This solenoid valve closes when energized (when the relay is on). This valve turns off for five minutes after the completion of the defrost cycle, or when SV9 is on turned ON and the value of 63HS1 is greater than 3.5 MPa [507psi] during Heating-only or Heating-main operation at the minimum frequency.
Page 304
[ IX Troubleshooting ] -4- Outdoor Unit Fan (1) Fan motor To check the revolution of the fan, check the inverter output state on the self-diagnosis LED, as the inverter on the outdoor fan controls the revolutions of the fan.The revolution of the fan is approximately 680rpm(P72 model),790rpm(P96 model), 630rpm (P120 model), 750rpm (P144 model) at full speed.
Page 305
[ IX Troubleshooting ] Is the wiring between the Correct the wiring according to the wiring FAN board, 52F, and fan motor connected correctly? diagram. Does 52F operate on the Replace 52F. coil voltage (206-252V)? Is a voltage of between 188V and 253V (TJMU) or between 414V and 506V (YJMU) applied to the power supply input? Correct the wiring according to the...
Page 306
[ IX Troubleshooting ] -5- LEV LEV operation LEV are stepping-motor-driven valves that operate by receiving the pulse signals from the indoor and outdoor unit control boards. (1) Indoor LEV and BC controller LEV The valve opening changes according to the number of pulses. 1) Control boards and the LEV Outdoor control board Intermediate connector...
Page 307
[ IX Troubleshooting ] (2) Judgment methods and possible failure mode Malfunction Judgment method Remedy mode Microcomputer Disconnect the control board connector and connect When the drive circuit has a driver circuit fail- the check LED as shown in the figure below. problem, replace the control board.
[ IX Troubleshooting ] -6- Troubleshooting Principal Parts of BC Controller 1. Pressure sensor Troubleshooting flow chart for pressure sensor START Note 1 Check whether the pressure sensor or the connectors of P1 and P3 are connected, properly Repair the fault. Operating at the moment? Note 2 On the self-diagnosis monitor, measure...
Page 309
[ IX Troubleshooting ] 1) BC controller: Phenomena when the pressure sensor is connected wrongly (reverse connection of P1 and P3) to the board. Symptoms Cooling-only Cooling-main Heating only Heating main Indoor heating SC small Non-cooling Normal Non-cooling SC11 large SC11 large SC11 large Heating indoor Thermo ON...
[ IX Troubleshooting ] 2. Temperature sensor Troubleshooting instructions for thermistor START Note 1 Pull out the thermistor connector in trouble from the board. Note 2 Measure the temperature of the thermistor in trouble. (actual measurement value) Note 2 Check the thermistor resistor. Compare the temperature corresponding to the resistance measured by the thermistor and the temperature measured by a commercially...
Page 311
[ IX Troubleshooting ] 1) For the connectors on the board, TH11 and TH12 are connected to CN10, and TH15 and TH16 are connected to CN11. Dis- connect the connector in trouble, and check the sensor of each number. Pull out the sensor connector from the I/O board, Do not pull the sensor by holding the lead wire. Measure the resistance with such as a tester.
Page 312
[ IX Troubleshooting ] 3. Troubleshooting flow chart for LEV Solenoid valve (1) LEV No cooling capacity No heating capacity Note 1 Check whether the electric expansion valve and the solenoid valve connector are not disconnected or not loose. Fault is found. Repair the fault.
Page 313
[ IX Troubleshooting ] 1) BC controller: Phenomena when LEV is connected wrongly (reverse connection of LEV1 and LEV3) to the board. Phenomena Cooling-only Cooling-main Heating only Heating main Non-cooling Non-cooling and non-heating Indoor heating SC small Non-cooling SH12 small, SC11 small SH12 small, SC11 small PHM large Indoor heating SC small...
Page 314
[ IX Troubleshooting ] Self-diagnosis LED Measurement data Symbol SW1 setting value 1 2 3 4 5 6 7 8 9 10 LEV1 opening 1 2 3 4 5 6 7 8 9 10 LEV2 opening 1 2 3 4 5 6 7 8 9 10 G, GA, HA LEV3 opening (Standard...
Page 315
[ IX Troubleshooting ] Troubleshooting flow chart for solenoid valve body Start Check for pins not fully inserted on the connector and check the colors of the lead wires visually. Intermediate connector Control board When LEV is fully closed : tick sound When LEV is fully open : no sound Brown Brown...
Page 316
[ IX Troubleshooting ] (2) Solenoid valve (SVA, SVB, SVC) Faulty judgment of solenoid valve Stop the operation of the applied BC remote controller system. Stop the operation Check whether the wire to the solenoid valve is not connected wrongly, or the connector is not loose. No fault Repair the fault.
Page 317
[ IX Troubleshooting ] Check whether the BC board output signal corresponds with the solenoid valve operation correspond. 1) SVA, SVB, SVC SVA, SVB, and SVC turn on or off according to the indoor unit operation mode. Mode Cooling Heating Stopped Defrost Port...
Page 318
[ IX Troubleshooting ] 4. BC controller transformer BC controller control board CNTR CN03 White Normal Abnormal CNTR(1)-(3) about 58 ohm. Open-phase or shorting CN03(1)-(3) about 1.6 ohm. * Before measuring the resistance, pull out the connector. HWE0913A - 309 -...
Page 319
[ IX Troubleshooting ] [TJMU-A] -7- Inverter (TJMU-A) Replace only the compressor if only the compressor is found to be defective. (Overcurrent will flow through the inverter if the compressor is damaged, however, the power supply is automatically cut when overcurrent is detected, protecting the inverter from damage.) Replace only the fan motor if only the fan motor is found to be defective.
Page 320
[ IX Troubleshooting ] [TJMU-A] Error display/failure condition Measure/inspection item Inverter related errors Check the details of the inverter error in the error log at X LED Monitor 4250, 4255, 4220, 4225, 4230, 4240,4260, 5301, 0403 Display on the Outdoor Unit Board. Take appropriate measures to the error code and the error details in ac- cordance with IX.
Page 321
[ IX Troubleshooting ] [TJMU-A] (2) Inverter output related troubles Items to be checked Phenomena Remedy <P72 model> IPM/overcurrent breaker trip Replace the INV board. Check the INV (4250 Detail code No. 101, 104, board error 105, 106, and 107) detection cir- (1) Disconnect the invert- Logic error...
Page 322
[ IX Troubleshooting ] [TJMU-A] Items to be checked Phenomena Remedy <P72 model> Inverter-related problems are de- Connect the short-circuit con- Check whether tected. nector to CN6, and go to sec- the inverter is tion [1]. damaged. Disconnect the inverter Inverter voltage is not output.
Page 323
[ IX Troubleshooting ] [TJMU-A] Items to be checked Phenomena Remedy Put the outdoor unit into oper- Overcurrent-related problems oc- Check items [1] through Check whether ation. cur immediately after compressor [3]. the inverter is Check the inverter output volt- startup.
Page 324
[ IX Troubleshooting ] [TJMU-A] (3) Trouble treatment when the main power breaker is tripped. Items to be checked Phenomena Remedy Perform Meg check between the Zero to several ohm, or Meg failure Check each part in the main inverter terminals on the power terminal circuit.
Page 325
[ IX Troubleshooting ] [TJMU-A] (4) Simple checking procedure for individual components of main inverter circuit Before checking, turn the power off and remove the parts to be checked from the control box. Part name Judgment method IGBT module See "Troubleshooting for IGBT Module ". ( IX [4] - 7 - (7) ) Diode stack Refer to "Diode stack"...
Page 326
[ IX Troubleshooting ] [TJMU-A] (5) Intelligent power module (P96, P120, P144 models) Measure resistances between each pair of terminals on the IPM with a tester, and use the results for troubleshooting. 1) Notes on measurement Check the polarity before measuring. (On the tester, black normally indicates plus.) Check that the resistance is not open ( ohm) or not shorted (to 0 ohm).
Page 327
[ IX Troubleshooting ] [TJMU-A] (6) Diode stack (P96, P120, P144 models) Measure resistances between each pair of terminals on the diode stack with a tester, and use the results for troubleshoot- ing.Refer to (5) " Intelligent power module (IPM) " for notes on measurement and tester selection. Judgment value (reference) Black ( + ) External view...
Page 329
[ IX Troubleshooting ] [YJMU-A] -7- Inverter (YJMU-A) Replace only the compressor if only the compressor is found to be defective. Replace only the fan motor if only the fan motor is found to be defective. Replace the defective components if the inverter is found to be defective. If both the compressor and the inverter are found to be defective, replace the defective component(s) of both devices.
Page 330
[ IX Troubleshooting ] [YJMU-A] Error display/failure condition Measure/inspection item Inverter related errors Check the details of the inverter error in the error log at X LED Monitor 4250, 4255, 4220, 4225, 4230, 4240,4260, 5301, 0403 Display on the Outdoor Unit Board. Take appropriate measures to the error code and the error details in ac- cordance with IX.
Page 331
[ IX Troubleshooting ] [YJMU-A] (2) Inverter output related troubles Items to be checked Phenomena Remedy Disconnect the invert- Overcurrent error Replace the INV board. Check the er output wire from (4250 Detail code No. 101, 104, INV board er- the terminals of the 105, 106, and 107) ror detection...
Page 332
[ IX Troubleshooting ] [YJMU-A] Items to be checked Phenomena Remedy Put the outdoor unit into oper- Overcurrent-related problems oc- a.Check items [1] through [3] Check whether ation. cur immediately after compressor for problems. the inverter is Check the inverter output volt- startup.Error code : 4250Detail b.Check that high and low damaged.
Page 333
[ IX Troubleshooting ] [YJMU-A] (3) Trouble treatment when the main power breaker is tripped Items to be checked Phenomena Remedy Check the breaker capacity. Use of a non-specified break- Replace it with a specified breaker. Perform Meg check between the Zero to several ohm, or Meg Check each part and wiring.
Page 334
[ IX Troubleshooting ] [YJMU-A] (5) Simple checking procedure for individual components of main inverter circuit Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less.
Page 336
[ IX Troubleshooting ] [TJMU-A] -8- Control Circuit (TJMU-A) (1) Control power source function block 1) PURY-P72TJMU-A Power source system (AC 208 / 230 V) Control system (DC 5 ~ 30 V) Noise filter INV board Compressor Rectifier Smoothing capacitor Inverter Noise filter AC 208 / 230 V...
[ IX Troubleshooting ] [TJMU-A] 2) PURY-P96, P120, P144TJMU-A Power source system (AC 208 / 230 V) Control system (DC 5 ~ 30 V) Noise filter Compressor Smoothing capacitor Inverter Noise filter Rectifier AC 208 / 230 V INV board Inverter drive Fuse Terminal block for...
Page 338
[ IX Troubleshooting ] [TJMU-A] (2) Troubleshooting transmission power circuit of outdoor unit 1) PURY-P72TJMU-A Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit. DC 24 ~ 30 V Check whether the transmission line is disconnected, check for contact failure, and repair the problem.
Page 339
[ IX Troubleshooting ] [TJMU-A] 2) PURY-P96, P120, P144TJMU-A Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit. Check whether the transmission line is disconnected, DC 24 ~ 30 V check for contact failure, and repair the problem. Check the voltage at TB3 after removing transmission line from TB3.
Page 340
[ IX Troubleshooting ] [YJMU-A] -8- Control Circuit (YJMU-A) (1) Control power source function block 1) PURY-P72, P96, P120, P144YJMU-A Power source system (AC 230 / 460 V) Control system (DC 5 ~ 30 V) INV board Noise filter Smoothing capacitor Inverter Compressor Noise filter...
Page 341
[ IX Troubleshooting ] [YJMU-A] (2) Troubleshooting transmission power circuit of outdoor unit 1) PURY-P72, P96, P120, P144YJMU-A Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit. Check whether the transmission line is disconnected, DC 24 ~ 30 V check for contact failure, and repair the problem.
[ IX Troubleshooting ] [5] Refrigerant Leak 1. Leak spot: In the case of extension pipe for indoor unit (Cooling season) 1) Mount a pressure gauge on the service check joint (CJ2) on the low-pressure side. 2) Stop all the indoor units, and close the high-pressure side refrigerant service valve (BV2) on the outdoor unit while the com- pressor is being stopped.
Page 343
[ IX Troubleshooting ] 3. Leak spot: In the case of extension pipe for indoor unit (Heating season) (1) Run all the indoor units in heating test run mode. 1) To run the indoor unit in test run mode, turn SW3-2 from ON to OFF when SW3-1 on the outdoor control board is ON. 2) Change the setting of the remote controller for all the indoor units to the heating mode.
[ IX Troubleshooting ] [6] Compressor Replacement Instructions 1. Compressor Replacement Instructions [Compressor replacement procedures] Follow the procedures below (Steps 1 through 6) to remove the compressor components and replace the compressor. Reassemble them in the reverse order after replacing the compressor. 1.
Page 345
[ IX Troubleshooting ] Compressor covers (right and left) (The inside of the compressor cover is lined with sound insulation material.) Compressor cover (top) Belt heater 4. Remove the compressor cover (top). 5. Remove the compressor wires, compressor covers (right and left), and belt heater. Protection for the sealing material Suction piping...
Page 346
[ IX Troubleshooting ] 1. Solenoid valve block ASSY (SV4a, SV4b, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement instruc- tions * Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a). Replace them properly according to the procedures. 1.
Page 347
[ IX Troubleshooting ] 2) Remove the control box. 1) Remove the upper and lower service panels (Panel FU and FB). 3) Remove the cable that is fixed to the Frame ASSY MU (upper) and MB (lower), and remove the Frame ASSY MU and MB.
Page 348
[ IX Troubleshooting ] (2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures ① Remove the Solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4d) replacement procedures" on the front page. ② Debraze H-M parts (total 6 places), and remove the Check valve ASSY. ③...
Page 349
[ IX Troubleshooting ] Detailed View of Part A ②③ Brazing or debrazing pipes ③ Check valve replacement (φ28.6 [1-1/8"]) (φ15.88 [5/8"]) CV4a When replacing CV4a: CV6a Remove the brazing (φ15.88 [5/8"]) (φ28.6 [1-1/8"]) When replacing CV6a: (φ15.88 [5/8"]) Remove the brazing (φ15.88 (φ15.88 [5/8"]) [5/8"])
Page 350
[ IX Troubleshooting ] 2. Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement instructions * Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a, CV10a). Replace them properly according to the procedures. 1.
Page 351
[ IX Troubleshooting ] 2) Remove the control box and the partition plate. 1) Remove the upper and lower service panels (Panel FU and FB). 3) Remove the cable that is fixed to the Frame ASSY MU (upper) and MB (lower), and remove the Frame ASSY MU and MB.
Page 352
[ IX Troubleshooting ] (2) Check valve (CV4a, CV6a, CV8a, CV9a, CV10a) replacement procedures ① Remove the solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d) replacement procedures" on the front page. ② Debraze I-O parts (total 7 places), and remove the Check valve ASSY. ③...
Page 353
[ IX Troubleshooting ] Detailed View of Part A ②③Brazing or debrazing pipes ③Check valve replacement (φ15.88 [5/8"]) (φ28.6 [1-1/8"]) When replacing CV4a: Remove the brazing CV6a CV4a (φ15.88 [5/8"]) When replacing CV6a: Remove the brazing (φ28.6 [1-1/8"]) (φ25.4 [1"]) When replacing CV8a: Remove the brazing 3 (φ15.88 [5/8"])
Page 354
[ IX Troubleshooting ] 3. Solenoid valve block ASSY (SV4a, SV4b, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a) replacement instructions * Following instructions show procedures for replacing service parts for Solenoid valve block ASSY (SV4a, SV4b, SV4d), Check valve (CV4a, CV6a, CV8a, CV9a). Replace them properly according to the procedures. 1.
Page 355
[ IX Troubleshooting ] 2) Remove the control box. 3) Remove the cable that is fixed to 1) Remove the upper the Frame ASSY MU (upper) and and lower service MB (lower), and remove the panels (Panel FU Frame ASSY MU and MB. and FB).
Page 356
[ IX Troubleshooting ] (2) Check valve (CV4a, CV6a, CV8a, CV9a) replacement procedures Remove the solenoid valve block ASSY following "(1) Solenoid valve block ASSY (SV4a, SV4b, SV4c, SV4d) replacement procedures" on the front page. Debraze I-M parts (total 5 places), and remove the Check valve ASSY. Replace the Check valve (CV4a, CV6a, CV8a, CV9a) to be serviced while it is removed from the unit.
Page 357
[ IX Troubleshooting ] Detailed View of Part A Check valve replacement CV6a CV4a When replacing CV4a: (ø15.88[5/8”]) Remove the brazing 1. When replacing CV6a: (ø25.4[1”]) Remove the brazing 2. (ø25.4[1”]) When replacing CV8a: Remove the brazing 3 and 4. (ø25.4[1”]) CV9a When replacing CV9a:...
Page 358
[ IX Troubleshooting ] 4. Solenoid valve (SV1a), Capillary tube ASSY (CP1) replacement instructions 1. Applicable models PURY-P72TJMU-A(-BS), PURY-P72YJMU-A(-BS) ……Low pressure twinning kit (optional accessory) is built in. * The parts can be replaced without removing the Solenoid valve ASSY on the unit for the units that do not have built-in low pressure twinning kit (optional accessory).
[ IX Troubleshooting ] [7] Servicing the BC controller 1. Service panel *Special care must be taken when replacing heavy parts. Work procedure Explanatory figure 1) Remove the two lock nuts on the control box, loosen the other two, and remove the control box. 2) Remove the three fixing screws on the service panel, Ceiling panel Loosen...
Page 360
[ IX Troubleshooting ] 3. Thermistor (liquid pipe/gas pipe temperature detection) *Special care must be taken when replacing heavy parts. Work procedure Explanatory figure (1) Remove the service panel. 1) For TH11, TH12, and TH15, refer to 1. 1) - 2). 2) For TH16, refer to 1.
Page 361
[ IX Troubleshooting ] 5. LEV Work procedure Explanatory figure (1) Remove the service panel.(Refer to 1. 1) - 3) (2) Replace the LEV in trouble. LEV3 Secure enough service space in the ceiling for welding operation, and conduct the work carefully.If required, LEV1 dismount the unit from the ceiling, and conduct the work.
[ IX Troubleshooting ] [8] Troubleshooting Using the Outdoor Unit LED Error Display If the LED error display appear as follows while all the SW1 switches are set to OFF, check the items under the applicable item numbers below. 1. Error code appears on the LED display. Refer to IX [2] Responding to Error Display on the Remote Controller.
Page 363
[ IX Troubleshooting ] HWE0913A - 354 -...
[ X LED Monitor Display on the Outdoor Unit Board ] X LED Monitor Display on the Outdoor Unit Board [1] How to Read the LED on the Service Monitor 1. How to read the LED By setting the DIP SW 1-1 through 1-10 (Switch number 10 is represented by 0), the operating condition of the unit can be monitored on the service monitor.
Page 367
[ X LED Monitor Display on the Outdoor Unit Board ] 3. Time data storage function The outdoor unit has a simple clock function that enables the unit to calculate the current time with an internal timer by receiv- ing the time set by the system controller, such as G(B)-50A. If an error (including a preliminary error) occurs, the error history data and the error detection time are stored into the service memory.
Page 368
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 359 -...
Page 369
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 360 -...
Page 370
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 361 -...
Page 371
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 362 -...
Page 372
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 363 -...
Page 373
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 364 -...
Page 374
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 365 -...
Page 375
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 366 -...
Page 376
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 367 -...
Page 377
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 368 -...
Page 378
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 369 -...
Page 379
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 370 -...
Page 380
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 371 -...
Page 381
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 372 -...
Page 382
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 373 -...
Page 383
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 374 -...
Page 384
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 375 -...
Page 385
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 376 -...
Page 386
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 377 -...
Page 387
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 378 -...
Page 388
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 379 -...
Page 389
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 380 -...
Page 390
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 381 -...
Page 391
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 382 -...
Page 392
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 383 -...
Page 393
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 384 -...
Page 394
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 385 -...
Page 395
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 386 -...
Page 396
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 387 -...
Page 397
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 388 -...
Page 398
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 389 -...
Page 399
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 390 -...
Page 400
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 391 -...
Page 401
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 392 -...
Page 402
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 393 -...
Page 403
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 394 -...
Page 404
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 395 -...
Page 405
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 396 -...
Page 406
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 397 -...
Page 407
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 398 -...
Page 408
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 399 -...
Page 409
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 400 -...
Page 410
[ X LED Monitor Display on the Outdoor Unit Board ] HWE0913A - 401 -...