Page 4
System Status Report Codes ......................4-7 Miscellaneous System Fields......................4-9 Pager Programming Fields........................ 4-13 Miscellaneous System Fields......................4-15 AUI Enable............................4-19 Keypad Programming Fields......................4-19 Menu Mode Programming........................5-1 About Zone Programming (∗56 and ∗58 Menu Modes) ..............5-1 ∗56 Zone Programming Procedure ....................5-1 Completing Zone Programming ......................
S E C T I O N Features and Installation Highlights • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This manual describes the installation of both the VISTA-12A and VISTA-12E.
Installation and Setup Guide Compatible Devices • Supports up to 8 Addressable Keypads: 6148/6150 Fixed-Word Display Keypads, 6164 Alpha Keypad, 6128RF/6128RFH/6150RF/6160RF Keypad/Transceivers, 6160V Voice Keypad • Supports up to two (2) Touch Screen (AUI) Devices (Symphony, 6270), which are in addition to the standard eight (8) addressable keypads.
Mounting and Wiring the Control S E C T I O N Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring this control and its peripheral devices.
Installation and Setup Guide Mounting the PC Board NOTE: The door of the metal cabinet may be 4. Insert top of circuit board into slots at top of removed to make it easier to install the PC board. cabinet. Make sure that circuit board rests in Remove the door as follows: slots as indicated in the diagram shown below.
Mounting and Wiring the Control Notes Wiring to Keypads • Typical Fixed-Word Display: Connect keypads to the control’s keypad 6128RF/6148/6150/6150RF/6150V terminals as shown on the Summary of • Typical Alpha Display: 6160/6160V/6164 Connections diagram. • The system supports up to 8 keypads, which Determine wire size using the Wiring Run can be assigned to partitions in any Chart below.
Page 10
Installation and Setup Guide Keypad Addresses Keypads powered from supplies Keypad Address Keypad Address that do not have a backup battery no. 1 16** no. 5 will not function if AC mains no. 2 no. 6 power is lost. Make sure to power no.
Mounting and Wiring the Control Sounder (Siren) Connections Wiring the AC Transformer Transformer: 1. Make sounder connections to alarm output Connect the Transformer to terminals 1 and 2 terminals 3 (+) and 4 (–). on the control board. See wiring table at bottom For supervised output, continue with steps 2 and of page for wire size to use.
Installation and Setup Guide Notes Backup Battery IMPORTANT: The panel will not power up 1. Place the 12-volt backup battery in the cabinet. initially on battery power only. You must plug 2. After all connections to the control are the transformer in first, and then connect the completed and AC mains power has been battery.
Page 13
Mounting and Wiring the Control AUXILIARY DEVICE CURRENT DRAIN WORKSHEET DEVICE CURRENT # UNITS TOTAL CURRENT 6128RF Keypad/Transceiver 90mA standby/120mA alarm 6150RF Keypad/Transceiver 80mA standby/105mA alarm 6148 Fixed-Word Keypad 30mA standby/55mA alarm 6150 Fixed-Word Keypad 40mA standby/90mA alarm 6160 Alpha Keypad 40mA standby/150mA alarm 6150V Fixed-Word Display 60mA standby/160mA alarm...
Installation and Setup Guide Notes Basic Wired Zones • EOLR: If the EOLR is not at the end of the Normally Open Zones/Normally Open EOLR loop, the zone is not properly supervised and Zones the system may not respond to an “open” on Connect open circuit devices in parallel across the zone.
Mounting and Wiring the Control Notes Smoke Detectors • • • • Fire Verification (zone type 16): The control 4-Wire Smoke Detectors panel will “verify” a fire alarm by resetting the Connect 4-wire smoke detectors (up to 16, smoke detectors after the first alarm trigger, depending on detector current drain) to any and then waiting 90 seconds for a second zone from 2-8 as shown on the next page.
Installation and Setup Guide Notes 4219/4229 Expansion Zones • Supports up to 8 expansion zones (NO or Connect each module to the control’s keypad NC) using 4219/4229 Zone Expander terminals. Modules as follows: If power supervision is required, use the Trigger •...
Mounting and Wiring the Control • Enter 6164 keypad program mode by 6164 Keypad Expansion Zones pressing and holding down both the [1] Connect each keypad to the control’s keypad and [3] keys within 60 seconds of power terminals. If power supervision is required, use the •...
Installation and Setup Guide Notes Installing the RF Receiver • The receiver is supervised and a trouble Use one of the following receivers: report is sent (“CHECK 100” displayed) if RF Receiver Number of Zones communication between the panel and 5881ENL up to 8 (including keyfob receiver is interrupted, or if no valid RF...
Mounting and Wiring the Control Notes Installing a 5800TM Module • Use this module only in 345Hz RF Mount the 5800TM next to the RF receiver systems and if you are using one or more (between one and two feet from the receiver’s wireless bi-directional keypads or keyfob;...
Installation and Setup Guide • When using a keyswitch, the zone it is Installing a Keyswitch connected to is no longer available for use Connect the 4146 keyswitch's normally open as a protective zone. momentary switch to a zone’s terminals •...
Mounting and Wiring the Control Relay Module Addresses Connecting Relay Modules † †† 4204/6164 Address 4229/6164 Address Mount either remotely or in the control panel. (zn 17-24) Connect to control’s keypad terminals using † Use these addresses if using only relays the connector harness supplied with the module.
Installation and Setup Guide Notes Powerline Carrier Devices • When using Powerline Carrier devices, Install up to 4 powerline carrier devices (if no you must use a Powerline Carrier Device relays are used) according to the instructions Modulator. It supplies signals from the included with each.
Mounting and Wiring the Control Notes Trigger Module and On-Board • Triggers There are two on-board triggers that can be used to activate output devices. IMPORTANT: Make all wiring connections to • These outputs are normally high, and go the Trigger Module before mounting the module low upon programmed condition.
Installation and Setup Guide ABLE) Figure 11. Trigger Module Notes Phone Line Connections • If you are using an Audio Alarm VISTA-12E Verification (AAV) unit, refer to Audio Connect incoming phone line and handset wiring Alarm Verification (AAV) section for to the main terminal block (via an RJ31X jack) as special wiring connections.
Mounting and Wiring the Control Notes Audio Alarm Verification • Connections (AAV, “Listen-In”) Set field *91 for AAV and program the appropriate output (output 17 or 18) using Refer to the connection diagram below. *80 Menu mode (select zone type “60”). Connections use one of the on-board triggers.
S E C T I O N Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming You can program the system at any time, even at the installer's premises prior to the actual installation.
Installation and Setup Guide Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or *58 Expert Programming mode. Refer to those sections for detailed procedures. The system can control three independent areas of protection (known as partitions) for use by independent users, if desired.
Programming Overview Keypads Keypads are identified by predefined addresses (starting at address 16) as follows: Address Keypad Program Field NOTE. First keypad is • always enabled for partition 1, all sounds enabled. address 16 keypad 1 • data field *190 keypad 2 •...
Installation and Setup Guide Pager Programming The system can send various reports to up to 2 pagers. To program pager reporting, do the following: Enter the appropriate information in the following data fields: *160, *163 Pager Phone Numbers (for pagers 1and 2 respectively) *161, *164, Pager Prefix Characters (for pagers 1 and 2 respectively) *162, *165, Pager Reporting Options by Partition †...
Programming Overview Zone Type Definitions You must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Zone Type Description Type 00: Zone Not Used Program a zone with this zone type if the zone is not used. •...
Page 32
Installation and Setup Guide Zone Type Description • Usually assigned to a zone containing an emergency button. Type 06 • Sends a report to the central station but provides no keypad display or 24-hour Silent Alarm sounding. • Assign to a zone that has an emergency button. Type 07 •...
Page 33
Programming Overview Zone Type Description • Provides a fire alarm when zone is shorted, but only after alarm is Type 16 Fire w/Verification verified. • System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit within 90 seconds triggers fire alarm.
Installation and Setup Guide Zone Type Description • Used with special Blockschloss lock and key. Type 82 • System arms 5 seconds after the key is fully turned (arms MAXIMUM); Blockschloss key can then be removed. • When armed, the Blockschloss zone is shorted. An open circuit on this zone causes trouble condition.
Page 35
Programming Overview Data Field Programming Procedures (cont’d) Task Procedure When the desired field number appears, simply enter the digits Entering Data required. The keypad beeps three times after the last digit is entered and automatically displays the next data field in sequence. If entering less than the maximum digits available (e.g., phone number field), enter the desired digits, then press [ ∗...
Page 36
Installation and Setup Guide Table of Device Addresses †† This Device Uses Address Reports as Enabled By… RF Receiver *56 zone programming: input device type entry AUI 1 automatic if AUI enable field *189 enabled for AUI 1 AUI 2 automatic if AUI enable field *189 enabled for AUI 2 Alternative Communication automatic if output to ACM field *29 enabled...
S E C T I O N Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order.
Page 38
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Arming Prevention Override If no override is selected, system will not be able to be armed when there is either a supervision Entry 1: 0 = no arming prevention override 1 = allow system to arm with an RF failure, system low battery, AC mains loss, or a supervision failure...
Data Field Programming Zone Sounds & Timing FIELD TITLE and DATA ENTRIES EXPLANATION Single Alarm Sounding Per Zone Select whether a zone going into alarm should (per sound more than once per armed period. armed period) 0 = no limit on alarm sounding per zone 1 = limit alarm sounding to once per arming period for a given zone Fire Alarm Sounder Timeout...
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Confirmation Of Arming Ding Entry 1 for each partition selects whether arming Entry 1: 0 = no; 1 = yes, 1-second ding from wired keypads causes siren ding. (ding if armed from wired keypad) Confirmation of arming is an external sounder Entry 2: Enter 0-15 from table below.
Page 41
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Secondary Phone No. If you enter fewer than 30 digits, exit by pressing [∗]. To clear entries from field, press ∗42∗. See Enter up to 30 digits. 0–9, # + 11 for ‘ ✱ ’, # + 12 for ‘#’, # + 13 for a backup reporting note for field ∗41.
Page 42
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Burglary Dialer Delay Provides delay of “BURGLARY ALARM” report to the central station, which allows time for the 0 = no dial delay subscriber to avoid a false alarm transmission. This 1 = 15 seconds delay does not apply to zone type 24 alarms (silent 2 = 30 seconds...
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Dynamic Signaling Priority Intended for use with Alternative Communication Media reporting. 0 = Primary dialer first; You must also enable field ∗29, ECP Contact ID 1 = ECP Contact ID output first. Output for ACM.
Page 44
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION After arming the system, zones remaining open after Exit Error Report Code exit delay expires cause an alarm sound at the 0 = no report 1-F = report code; see description above keypad and external sounder (keypad also displays “EXIT ALARM”), and entry delay begins.
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Alarm Restores Alarm restore message will be sent upon condition selected. Send restore code (if fault cleared): 0 = at siren timeout (if restored) or at disarm (whether restored or not) 1 = dynamically as the fault clears 2 = only after a disarm Sent when an alarm zone is restored to its non-...
Page 46
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Auto-Stay Arm If enabled, the system will automatically change AWAY or MAXIMUM modes to STAY and 0 = no 1 = partition 1 only INSTANT modes respectively if the entry/exit door 2 = partition 2 only is not opened and closed within the exit delay time 4 = partition 3 only...
Page 47
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Misc. Fault Delay Time Used with zones assigned to a configurable zone type with fault delay on (selected in alarm/trouble 0 = 15 secs 6 = 2-1/2 min #+12 = 8 min 1 = 30 secs 7 = 3 min #+13 = 10 min...
Page 48
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Miscellaneous Options Entry 1: Select the desired options by adding the values of Entry 1 – AAV and Exit Delay Restart: 0 = none each desired option. 4 = using Audio Alarm Verification (AAV) unit ††“Exit Delay Restart/reset”...
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Enter the phone number of the downloading Download Phone Number computer. Enter up to 30 digits as follows: 0–9, # +11 for “∗”, # Do not fill unused spaces. End field by entering ∗. + 12 for “#”, # + 13 for a pause.
Page 50
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Pager 1 Characters Up to 16 optional characters may be sent as a prefix *161 to the 7-digit system status code sent to pager #1 (if Enter up to 16 characters used).
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION See field ∗161 for explanation. If fewer than 16 Pager 2 Characters *164 Enter up to 16 characters characters, exit by pressing [∗] and next field number. To clear entries, press ∗164∗. Pager 2 Report Options Enter the types of reports to be sent to pager 2 for *165...
Page 52
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Select desired options. Siren Options *176 Entry 1: 0 = external siren Entry 1: If entry 1 is not set to an external siren 1 = self-activated external siren (option 0 or 1), then the second entry is ignored. Entry 2: 0 = disable siren delay 1 = external siren delay and dialer Entry 2: Option 1 –...
Page 53
Data Field Programming FIELD TITLE and DATA ENTRIES EXPLANATION Zone Bypass Limit Select the maximum number of zones that can be *180 bypassed. 0 = unlimited zone bypasses in each partition 1-7 = number of zone bypasses allowed in Each partition individually uses this entry. each partition 8 = zone bypass disabled (no zones can be bypassed)
Page 54
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Display Options Select the desired keypad display options. *186 Entry 1: Latch first alarm in the display Entry 1: If enabled, only the first zone that went into 0 = disable; 1 = enable alarm is displayed.
Data Field Programming AUI Enable FIELD TITLE and DATA ENTRIES EXPLANATION AUI Device 1 and 2 Enable The System supports up to two touch screen style *189 keypads (e.g., Symphony Advanced User Interface, and (for Touch Screen Style Keypads) 6270 Touch Screen Keypad). 0 = disabled Enter each AUI’s home partition.
Page 56
Installation and Setup Guide FIELD TITLE and DATA ENTRIES EXPLANATION Exit Time Display Interval If enabled, keypads display the exit delay time *197 remaining after arming the system, with display 0 = no display 1-5 = seconds between display refreshing updates at the interval selected (i.e.
S E C T I O N Menu Mode Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming (∗...
Page 58
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Summary Screen A summary display appears. Zn ZT P RC In: L “IN: L” appears for wireless zones and indicates [∗] to continue 17 00 1 10 RF: 1 input type and loop. “IN: AD”...
Page 59
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION Response Time (RT) This prompt appears only for basic wired zones 02 Response Time 01-06 (zone 02 is used as an example in display). 0 = 10mSec 2 = 700mSec 1 = 400mSec 3 = 1.2 seconds NOTE: If zone doubling is being used, the [∗] to continue response time set for zones 01-06 automatically...
Page 60
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Serial number Entry and Used only when enrolling wireless transmitters. 17 INPUT S/N: a. Transmit two open/close sequences. If using a Loop Number Entry A 0 2 2 - 4 0 6 4 button-type transmitter, press and release the see explanation button twice, but wait about 4 seconds before...
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION Confirmation Option This prompt will only appear if you answered XMIT TO CONFIRM “Yes” at the first prompt in this section. Activate the loop input or button ✱ PRESS TO SKIP [∗] to continue The system will enter a confirmation mode so that the operation of the actual programmed input can be confirmed.
Installation and Setup Guide ∗ ∗ ∗ ∗ 58 Expert Programming Mode Procedures This method is designed for use by installers with previous experience in programming ADEMCO control panels. This mode is also used to program wireless keys using pre-defined templates. ∗...
Page 63
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION Zone Programming A summary screen with the selected zone’s Zn ZT P RC IN: L current programming appears. ZT = see Zone Type chart 00 1 10 RF 1 shown in *56 Menu Mode Begin programming zone information as follows: “Zone Type”...
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Confirm The prompt to confirm appears. This prompt will 10 XMIT TO CONFIRM only appear if the first prompt after entering ∗58 [∗] to continue PRESS ✱ TO SKIP was answered “Yes.” To confirm, activate the loop input or button that corresponds to this zone.
Page 65
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION Template Display 4. When [∗] is pressed, the selected template will 03 04 be displayed. [∗] to continue 21 23 Top line of display represents loop numbers, bottom line represents zone type assigned for each loop.
Page 66
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Confirm 13. If “Yes” was entered at the SET TO XMIT TO CONFIRM CONFIRM? prompt previously (see first [∗] to continue ✱ PRESS TO SKIP prompt following entry into the •58 Expert Programming Mode), the display on the left will appear.
Page 67
Menu Mode Programming Wireless Key Predefined Default Templates 5804 Wireless Key Transmitter 5804BD 2-Way Wireless Key Transmitter For 5804 For 5804BD Zone Zone Loop Function Loop Function TEMPLATE TEMPLATE Type Type No Response No Response Disarm No Response Arm Away Arm Away No Response Disarm...
Installation and Setup Guide About Output Device Programming (*79/*80 Menu Mode) Output Devices: The system supports up to 4 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 6 “outputs” are assigned to system-wide output numbers (01-06 and 17-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
Page 69
Menu Mode Programming 79 Menu Mode PROMPT VALID ENTRIES EXPLANATION This is the logical (or reference) relay number as Device Output Number ENTER OUTPUT NO. used in the system. Relays and X-10 devices are 01-04, 17-18 = relays/X-10 00 = QUIT numbered 01-04;...
Installation and Setup Guide *80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 12 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types.
Page 71
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION Summary Screen This screen displays a summary of the current A E P Trig output programming (for this example, Zone List [∗] to continue ?00 0 – ZL=1 has been selected-this is the default screen). A = Output Action;...
Page 72
Installation and Setup Guide PROMPT VALID EXPLANATION ENTRIES “B” Zone Type If zone type was selected, this screen appears. Otherwise skip to 01 Enter Zn type the next row. see list at right Perimeter Enter the desired zone type associated with this output number. See below for a list of available zone types.
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION “C” Zone Number If zone number was selected, this screen appears. 01 Enter Zn No. Enter the desired zone number associated with this output number. Press [ ∗ ] to continue. Enter the zone event that will activate this output. 0 = restore;...
Installation and Setup Guide Zone List Programming Zone List programming involves: Selecting an appropriate zone list number; Adding the desired zone numbers to be included in that list. ✱ Start Zone List Program Mode by pressing 81 while in Data Programming mode. The following prompts are displayed : *81 Menu Mode PROMPT...
Menu Mode Programming Programming Function Keys Function key programming involves: Assigning the function key number and partition; Selecting the desired function for that key. ∗ Start Function Key Programming mode by pressing 57 while in Data Programming mode. The following prompts are displayed: PROMPT VALID ENTRIES EXPLANATION...
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Define Key Function Enter the desired function for this key, 00 to 12, Key "A" Func from the options listed. (00 selected for example 00-10 = see list to right Zone 95 display shown at left) [∗] to continue †...
Page 77
Menu Mode Programming PROMPT VALID ENTRIES EXPLANATION Select Descriptor Type This prompt selects whether you are entering zone S e l Z o n e D e s = 0 (Zone Descriptor or Partition descriptors or entering partition descriptors. P a r t = 1 Descriptor Words) Pressing [0] goes to the next prompt to let you enter 0 = create zone descriptors (see...
Installation and Setup Guide Configurable Zone Type Programming (*83 Menu Mode) Start Configurable Zone Type Programming Mode by pressing ∗ 83 while in Data Programming mode. PROMPT VALID ENTRIES EXPLANATION Zone Type Number Enter the configurable zone type number being E n t e r Z o n e T y p e programmed.
Testing the System PROMPT VALID ENTRIES EXPLANATION Trouble Sounding Select type of sounding upon trouble conditions on 9 0 T R B L S O U N D zones assigned to this zone type. 0= none 1= one beep every minute 2= normal trouble sound (fast beeps) [∗] to continue...
Page 80
Installation and Setup Guide PROMPT VALID ENTRIES EXPLANATION Schedule Number Enter the desired schedule number. E N T E R S C H E D N O . 01-04 = end-user schedules 0 0 = Q U I T 05-08 = installer-only schedules [∗] to continue Enter Event Enter the desired event number for event you...
Page 81
Testing the System PROMPT VALID ENTRIES EXPLANATION Start Time Enter the event’s start time and days of the week S T A R T S M T W T F S † to occur. 01-12 (00-23) = hour 0 0 1 0 0 0 0 H H M M A M To select days, position the cursor under the 00-59 = minute...
S E C T I O N System Communication and Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Panel Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station.
Page 84
Installation and Setup Guide The following table describes each format in greater detail. FORMAT TYPE DESCRIPTION 3+1 and 4+1 Comprises a 3- (or 4-) digit subscriber number and a single-digit Standard Formats report code (e.g., Alarm, Trouble, Restore, Open, Close, etc). 3+1 and 4+1 Comprises a 3- (or 4-) digit subscriber number and a two-digit Expanded Formats...
Page 85
System Communication and Operation ** Characters in parenthesis are included in Robofon 8 format. Where: SSS or SSSS = Subscriber ID C = Close Code–1st Digit A = Alarm Code–1st digit*** U = User Number (in hex) Z = Typically Zone Number*–2nd digit Gg = Test Code (1st &...
Installation and Setup Guide Robofon 8 Format send data in a pulsed frequency format in the following protocol: Robofon 8 format First bit Last Bit Tone = 0, No tone = 1 Freq = 1000Hz ± 5Hz ‘U’ First Byte Last Byte 50 baud (20ms / bit) 200ms / char, 11 chars / message...
System Communication and Operation ® ADEMCO Contact ID ® ADEMCO and Robofon Contact ID Reporting takes the following format: CCCC(CCCCCC) Q EEE GG ZZZ where: CCCC(CCCCCC) =4-digit or 10-digit Customer (subscriber) ID Q = 1-digit Event qualifier, where: E = new event , and R = restore EEE =3-digit (hexadecimal) Event code (see central office receiver manual for a complete list of event codes) GG = 2-digit Partition Number (system messages show “00”)
Installation and Setup Guide Security Codes The system supports up to 16 security codes, which can each be assigned one of 5 authority levels. The authority level determines the functions each code can perform as follows: Authority Levels (authority levels can be assigned to users 3-49 only; users 1 and 2 cannot be changed) Level User No.
System Communication and Operation SUMMARY OF ARMING MODES Arming Mode Features for Each Arming Mode Exit Delay Entry Delay Perimeter Armed Interior Armed AWAY STAY NIGHT-STAY only those zones listed in Night-Stay zone list INSTANT MAXIMUM Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual.
Installation and Setup Guide Keypad Commands (cont’d) Function Description Disarming Enter code + OFF [1]. If entry delay or an alarm is active, you do not need to press OFF; entering the security code alone disarms the system. Bypassing Zones Enter code + BYPASS [6] + zone number(s).
System Communication and Operation Follow-Me Feature This feature lets users enter up to three phone numbers (system-wide) that the system will call in the event of an alarm in any partition at the protected premises, thus alerting the user to the alarm. •...
Installation and Setup Guide From a FIXED-WORD KEYPAD: User code + [#] + [6] [2] • The first follow-me phone number (if one exists) is displayed one digit at a time. When done, the keypad beeps twice then displays the number “1,” indicating phone number 1. •...
System Communication and Operation Various System Trouble Displays Alpha Display Fixed Disp. Meaning ALARM CANCELED Appears if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open and the zone was not auto-bypassed), but the system was disarmed during the Entry Delay time.
Page 94
Installation and Setup Guide Various System Trouble Displays (cont’d) If this remains displayed for more than 1 minute, the system is Busy-Standby disabled. Modem Comm The system is in communication with the central station for change of function or status verification. Power Failure no display no display...
S E C T I O N Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly.
Installation and Setup Guide Checking Zones Using One-Man Walk Test (Sniffer Mode) Use this mode to test all zones (wired and wireless) that have been programmed. Make sure all partitions are disarmed before trying to enter this mode, since this is a system-wide command. Press [Installer code] + [#] + 3.
Testing the System Dialer Communication Test TEST Enter Installer Code + 5 [ ], then press “1” at the prompt to start the Dialer Test. 1=DIAL, 0=WALK (no special display on Fixed-Word keypads) The following will be displayed (accompanied by 2 beeps) if test is successful: PHONE OKAY (“Cd”...
Installation and Setup Guide COMPATIBLE DEVICES Keypads: 6128RF, 6148, 6150, 6150RF, 6150V, 6160V, 6164 Wireless Receivers: 5881ENL: accepts up to 8 transmitters 5881ENM: accepts up to 16 transmitters 5881ENH: accepts up to system maximum transmitters 5883M: accepts up to 16 transmitters 5883H: accepts up to system maximum transmitters 6128RF: accepts up to 16 transmitters plus 8 wireless keys 6150RF: accepts up to 16 transmitters...
Specifications & Accessories 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones).
Page 102
Installation and Setup Guide Compatible 5800 Series Transmitters Table (cont’d) Model Product Input Type Description • House ID must be set. 5804BD Bi-Directional BR Only • Requires 5800TM Transmitter Module or 5883 Wireless Key Transceiver. • Can indicate system status via its 2 LEDs and built-in sounder.
Page 103
Specifications & Accessories Compatible 5800 Series Transmitters Table (cont’d) Model Product Input Type Description • Has built-in shock sensor. 5819WHS Shock Processor • Has built-in tampered cover switch. 5819BRS Transmitter • Has 3 unique input (loop) codes: Loop 1: Built-in shock sensor loop wired to TB1 (normally closed).
S E C T I O N Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or...
Page 106
Installation and Setup Guide • Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms.
Page 107
Limitations and Warranty LIMITED WARRANTY Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product(s) or, for product(s) not having a manufacturer’s date stamp, for 12 months from date of original purchase unless the installation...
S E C T I O N Index • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 1321 ........2-5 Audio Alarm Verification Factory Defaults ....3-10...
Page 110
Installation and Setup Guide Pager Programming Fields ..4-13 Reports In Armed Period..4-12 System Status Report Codes.4-7 Pager Report Options ..4-14 response time ..2-10, 4-11, 5-2 System Test ......7-1 Paging .........4-12 RF House ID Code..3-3, 4-2 tamper switch.......2-14 Panic Keys......6-8 RF Interference ....