hit counter script

Requirements Specific To Perforated Cabinets - Cisco AJ732A - MDS 9134 Fabric Switch Installation Manual

Cisco nexus 5000 series hardware installation guide (ol-15902-01, november 2008)
Hide thumbs Also See for AJ732A - Cisco MDS 9134 Fabric Switch:
Table of Contents

Advertisement

Cabinet and Rack Requirements
S e n d d o c u m e n t a t i o n c o m m e n t s t o n e x u s 5 k d o c s @ c i s c o . c o m
Note

Requirements Specific to Perforated Cabinets

A perforated cabinet is defined here as a cabinet with perforated front and rear doors and solid side walls.
In addition to the requirements listed in the
page
A perforated cabinet that conforms to these requirements is available from Rittal Corporation:
Cisco Nexus 5000 Series Hardware Installation Guide
A-2
The minimum vertical rack space per 5010 chassis must be one RU (rack unit), equal to 1.75 inches
(4.4 cm).
The width between the rack-mounting rails must be at least 17.75 inches (45.1 cm) if the rear of the
switch is not attached to the rack. For four-post EIA racks, this is the distance between the two front
rails.
For four-post EIA cabinets (perforated or solid-walled):
The minimum spacing for the bend radius for fiber-optic cables should have the front-mounting
rails of the cabinet offset from the front door by a minimum of 3 inches (7.6 cm), and a
minimum of 5 inches (12.7 cm) if cable management brackets are installed on the front of the
chassis.
The distance between the outside face of the front mounting rail and the outside face of the back
mounting rail should be 23.5 to 34.0 inches (59.7 to 86.4 cm) to allow for rear-bracket
installation.
A minimum of 2.5 inches (6.4 cm) of clear space should exist between the side edge of the
chassis and the side wall of the cabinet. No sizeable flow obstructions should be immediately
in the way of chassis air intake or exhaust vents.
Optional jumper power cords are available for use in a cabinet. See the
section on page
C-10.
A-1, perforated cabinets must meet the following requirements:
The front and rear doors must have at least a 60 percent open area perforation pattern, with at least
15 square inches of open area per rack unit of door height.
The roof should be perforated with at least a 20 percent open area.
The cabinet floor should be open or perforated to enhance cooling
Rittal Corporation
One Rittal Place
Springfield, OH 45504
Contact: (800) 477–4220
Cabinet P/N: Rittal 9969427
Cabinet description: PS-DK/OEM Cabinet Assembly, (78.7 in.) 1998 mm X 23.6 in. (600 mm) X