Chapter 5
Removal and Replacement Procedures
Figure 5-64 Handling a DC-Input Power Supply
0
Tighten the power supply captive installation screws. (See
Step 4
Figure 5-65 2500 W DC-Input Power Supply
DC power cable
terminal block
Power supply captive installation screws must be tight to ensure protective grounding continuity.
Warning
Remove the two screws securing the terminal block cover, and slide the cover off of the terminal block
Step 5
(Figure
Attach the appropriate lugs to the DC-input wires. The maximum width of a lug is 0.300 inch (7.6 mm).
Step 6
The wire should be sized according to local and national installation requirements. Use only copper wire.
OL-4503-24
I
INPU T
FAN
OUT PUT
OK
OK
FAIL
Terminal block
cover
I
0
Power
switch
Captive installation
screw
5-65).
Figure
INP UT
FAN
OUT PUT
OK
OK
FAIL
Status LEDs
Cisco 7600 Series Router Installation Guide
Removing and Replacing the Power Supply
5-65.)
5-61