Wired Zone Expander Module – Installation Instructions
GENERAL INFORMATION
The 4219 expander module adds up to eight normally closed or
eight
end-of-line
resistor
control/communicators via the control's keypad wiring.
The module may be mounted within the control's cabinet (if room
permits), or remotely. If mounted remotely, there are provisions to
tamper protect the unit.
supervised so that it cannot be disconnected from the keypad wiring
without detection by the control. If the wiring is cut, a tamper
alarm or signal will result, to indicate that this device (and possibly
other similarly connected devices) has become inoperative.
IMPORTANT: Some carbon monoxide detectors may not be
compatible with the Honeywell 4219 hardwire zone expanders.
When using carbon monoxide detectors in systems that support the
4219 zone expanders, install the detectors only on the basic
hardwire zones of the system control panel, and NOT on the zone
expanders.
INSTALLATION
1. Disconnect power before proceeding.
2.
Mount the 4219 before making any wire connections.
When the module is mounted remotely, holes on the back of the
module's housing permit it to be mounted horizontally or vertically.
Wires can exit from the side or the breakout on the back of its
housing. For tamper protection, attach the tamper magnet
(provided) (Figure 1) to the module inside cover. Place DIP switch
position #8 in the OFF position. Affix the connections label that
accompanies the module to the inside of the module's cover. When
the installation is complete, put the modules cover on. The magnet
attached to the cover, positioned near the reed switch, will cause a
tamper signal to be sent to the control if the cover is removed.
When the module is to be mounted inside the control's cabinet,
mount it horizontally to the raised tabs at the back of the cabinet.
Insert self-tapping screws (provided) in two adjacent raised tabs at
the back of the cabinet. Leave the heads projecting 1/8". Hang the
module on the screw heads via two slotted holes on the back of the
module's housing. When the module is installed in the control's
cabinet, it need not be tamper protected.
NOTE: For EN50131-3 compliance a tie-wrap must be secured
around the case of a remotely mounted 4219.
Apply tie-wrap around the case to the right of the large
zone wire opening (4-inch case width). This is in opposition
of the tamper switch and magnet.
Affix the connections label that accompanies the module to the
inside of the control's cover.
See the control's installation and setup guide for additional
information.
CONNECTIONS AND SETTINGS
Zone Connections
Make protection zone connections to the module's 12-position
terminal block TB1.
Set DIP switch 7 for the desired zone operation (NC or EOLR):
OFF = End of line resistor operation. Each zone that is used must
have a 2K-ohm end-of-line resistor connected across the
end of its loop, as shown in Figure 2.
UL: Set to OFF (EOLR)
ON =
Normally closed operation
The method of programming each zone for the type of alarm and
reporting code to the central monitoring station varies with the
control to which the module is connected. Refer to the Installation
and Setup Guide for that control unit.
supervised
zones
to
compatible
Communication to the module is
1. INSERT BOTTOM TABS FIRST.
2. ENGAGE TOP WITH CLIP.
Figure 1. Tamper Magnet Installation
Module Address
Set the module address using DIP switches 2-6.
Select one of 31 addresses, as shown in Figure 3, so the control can
identify the module and communicate with it properly. The address
to be set is determined by the particular control to be used, and the
control's installation instructions must be consulted.
Normal/Fast Response Time for all zones
Use DIP switch 1 to select normal or fast response time for all
zones:
OFF = fast response time of 10ms to an open circuit
ON =
normal response time of 300ms. All other module
protection zones have a nominal response time of 300ms.
Connection to the Control Panel
Connect the module to the control panel's keypad (ECP) terminals
via 4-terminal block TB2 or the 4-pin plug (wire color connections
are the same).
SPECIFICATIONS
Physical
6-7/16"W x 4-1/4"H x 1-1/4" D (163mm x
108mm x 32mm)
Electrical
Input Voltage:
12VDC (from control's remote keypad
connection points)
Current:
30mA
4219-002-V0

Advertisement

loading

Summary of Contents for Honeywell 4219

  • Page 1 4219 Wired Zone Expander Module – Installation Instructions GENERAL INFORMATION The 4219 expander module adds up to eight normally closed or eight end-of-line resistor supervised zones compatible control/communicators via the control’s keypad wiring. The module may be mounted within the control’s cabinet (if room permits), or remotely.
  • Page 2 Cet appareil ne doit pas causer d' interférences nuisibles. (2) Cet appareil doit accepter toute interference reçue y compris les interférences causant une réception indésirable. ÊN8924V4uŠ For the latest warranty information, please go to: http://www.security.honeywell.com/hsc/resources/wa 2 Corporate Center Drive, Suite 100 N8924V4 3/14 Rev. C P.O. Box 9040, Melville, NY 11747 Copyright © 2008 Honeywell International Inc.